switching actuator 4fold A4FX-E-Q
Lingg & Janke · Order number A4FX-E-Q · binary output › eco+/quick series
Download .knxprod 4x switching, time, scene, announce, inh. 2025-21 2.1 · 93 KB
Product
| Manufacturer | Lingg & Janke |
|---|---|
| Product name | switching actuator 4fold |
| Order number | A4FX-E-Q |
| Product text | eco+/quick switching actuator 4f |
| Hardware | A4FX-E-Q |
| Medium | Twisted Pair |
| Bus current (mA) | 5 |
| Rail mounted | Yes |
| Width (mm) | 72 |
| Registration | Registered · 2016-08-31 |
| Languages | en-US, de-DE |
| Catalog entry | M-00E1_H-2015-1_HP-2025-21-D735_CI-A4FX.2DE.2DQ-1 |
| Fingerprint | D735 |
| SHA-256 | 501ed4dda8195d55fdb105a2f2be1fd5fa39a1fed6711cf3d185de1ae9ca387c |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: 4x switching, time, scene, announce, inh. 2025-21 2.1
| Application number | $2025 |
|---|---|
| Version | 2.1 |
| Mask version | MV-0021 (2.1) |
| KNX Data Secure | No |
| Parameters | 440 |
| Group objects | 64 |
Group objects (64)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | input A, CH1 switching | channel A, CH1 object 1 | 1 Bit | 1.1 switch | CW |
| 0 | input A1, CH1 OR | channel A, CH1 object 1 | 1 Bit | 1.1 switch | CW |
| 0 | input A1, CH1 EXOR | channel A, CH1 object 1 | 1 Bit | 1.1 switch | CW |
| 0 | input A1, CH1 AND | channel A, CH1 object 1 | 1 Bit | 1.1 switch | CW |
| 1 | input A2, CH1 OR | channel A, CH1 object 2 | 1 Bit | 1.1 switch | CW |
| 1 | input A2, CH1 EXOR | channel A, CH1 object 2 | 1 Bit | 1.1 switch | CW |
| 1 | input A2, CH1 AND | channel A, CH1 object 2 | 1 Bit | 1.1 switch | CW |
| 2 | output A, CH1 status | channel A, CH1 object 3 | 1 Bit | 1.1 switch | CT |
| 2 | output A, CH1 status INV | channel A, CH1 object 3 | 1 Bit | 1.1 switch | CT |
| 3 | input A, CH1 scenes | channel A, CH1 object 4 | 1 Byte | 18.1 scene control | CW |
| 4 | input A, CH1 announce | channel A, CH1 object 5 | 1 Bit | 1.1 switch | CW |
| 5 | input A, CH1 inhibit | channel A, CH1 object 6 | 1 Bit | 1.1 switch | CW |
| 6 | input A, CH1 reset hour meter | channel A, CH1 object 7 | 1 Bit | 1.15 reset | CW |
| 7 | output A, CH1 hour meter (h) | channel A, CH1 object 8 | 2 Bytes | 7.7 time (h) | CT |
| 7 | output A, CH1 hour meter (s) | channel A, CH1 object 8 | 4 Bytes | 13.100 time lag (s) | CT |
| 8 | output A, CH1 limit reached | channel A, CH1 object 9 | 1 Bit | 1.2 boolean | CT |
| 9 | input B1, CH2 OR | channel B, CH2 object 1 | 1 Bit | 1.1 switch | CW |
| 9 | input B1, CH2 EXOR | channel B, CH2 object 1 | 1 Bit | 1.1 switch | CW |
| 9 | input B1, CH2 AND | channel B, CH2 object 1 | 1 Bit | 1.1 switch | CW |
| 9 | input B, CH2 switching | channel B, CH2 object 1 | 1 Bit | 1.1 switch | CW |
| 10 | input B2, CH2 EXOR | channel B, CH2 object 2 | 1 Bit | 1.1 switch | CW |
| 10 | input B2, CH2 AND | channel B, CH2 object 2 | 1 Bit | 1.1 switch | CW |
| 10 | input B2, CH2 OR | channel B, CH2 object 2 | 1 Bit | 1.1 switch | CW |
| 11 | output B, CH2 status | channel B, CH2 object 3 | 1 Bit | 1.1 switch | CT |
| 11 | output B, CH2 status INV | channel B, CH2 object 3 | 1 Bit | 1.1 switch | CT |
| 12 | input B, CH2 scenes | channel B, CH2 object 4 | 1 Byte | 18.1 scene control | CW |
| 13 | input B, CH2 announce | channel B, CH2 object 5 | 1 Bit | 1.1 switch | CW |
| 14 | input B, CH2 inhibit | channel B, CH2 object 6 | 1 Bit | 1.1 switch | CW |
| 15 | input B, CH2 reset hour meter | channel B, CH2 object 7 | 1 Bit | 1.15 reset | CW |
| 16 | output B, CH2 hour meter (h) | channel B, CH2 object 8 | 2 Bytes | 7.7 time (h) | CT |
| 16 | output B, CH2 hour meter (s) | channel B, CH2 object 8 | 4 Bytes | 13.100 time lag (s) | CT |
| 17 | output B, CH2 limit reached | channel B, CH2 object 9 | 1 Bit | 1.2 boolean | CT |
| 18 | input C1, CH3 OR | channel C, CH3 object 1 | 1 Bit | 1.1 switch | CW |
| 18 | input C1, CH3 EXOR | channel C, CH3 object 1 | 1 Bit | 1.1 switch | CW |
| 18 | input C1, CH3 AND | channel C, CH3 object 1 | 1 Bit | 1.1 switch | CW |
| 18 | input C, CH3 switching | channel C, CH3 object 1 | 1 Bit | 1.1 switch | CW |
| 19 | input C2, CH3 AND | channel C, CH3 object 2 | 1 Bit | 1.1 switch | CW |
| 19 | input C2, CH3 OR | channel C, CH3 object 2 | 1 Bit | 1.1 switch | CW |
| 19 | input C2, CH3 EXOR | channel C, CH3 object 2 | 1 Bit | 1.1 switch | CW |
| 20 | output C, CH3 status | channel C, CH3 object 3 | 1 Bit | 1.1 switch | CT |
| 20 | output C, CH3 status INV | channel C, CH3 object 3 | 1 Bit | 1.1 switch | CT |
| 21 | input C, CH3 scenes | channel C, CH3 object 4 | 1 Byte | 18.1 scene control | CW |
| 22 | input C, CH3 announce | channel C, CH3 object 5 | 1 Bit | 1.1 switch | CW |
| 23 | input C, CH3 inhibit | channel C, CH3 object 6 | 1 Bit | 1.1 switch | CW |
| 24 | input C, CH3 reset hour meter | channel C, CH3 object 7 | 1 Bit | 1.15 reset | CW |
| 25 | output C, CH3 hour meter (h) | channel C, CH3 object 8 | 2 Bytes | 7.7 time (h) | CT |
| 25 | output C, CH3 hour meter (s) | channel C, CH3 object 8 | 4 Bytes | 13.100 time lag (s) | CT |
| 26 | output C, CH3 limit reached | channel C, CH3 object 9 | 1 Bit | 1.2 boolean | CT |
| 27 | input D1, CH4 OR | channel D, CH4 object 1 | 1 Bit | 1.1 switch | CW |
| 27 | input D1, CH4 EXOR | channel D, CH4 object 1 | 1 Bit | 1.1 switch | CW |
| 27 | input D1, CH4 AND | channel D, CH4 object 1 | 1 Bit | 1.1 switch | CW |
| 27 | input D, CH4 switching | channel D, CH4 object 1 | 1 Bit | 1.1 switch | CW |
| 28 | input D2, CH4 AND | channel D, CH4 object 2 | 1 Bit | 1.1 switch | CW |
| 28 | input D2, CH4 OR | channel D, CH4 object 2 | 1 Bit | 1.1 switch | CW |
| 28 | input D2, CH4 EXOR | channel D, CH4 object 2 | 1 Bit | 1.1 switch | CW |
| 29 | output D, CH4 status | channel D, CH4 object 3 | 1 Bit | 1.1 switch | CT |
| 29 | output D, CH4 status INV | channel D, CH4 object 3 | 1 Bit | 1.1 switch | CT |
| 30 | input D, CH4 scenes | channel D, CH4 object 4 | 1 Byte | 18.1 scene control | CW |
| 31 | input D, CH4 announce | channel D, CH4 object 5 | 1 Bit | 1.1 switch | CW |
| 32 | input D, CH4 inhibit | channel D, CH4 object 6 | 1 Bit | 1.1 switch | CW |
| 33 | input D, CH4 reset hour meter | channel D, CH4 object 7 | 1 Bit | 1.15 reset | CW |
| 34 | output D, CH4 hour meter (h) | channel D, CH4 object 8 | 2 Bytes | 7.7 time (h) | CT |
| 34 | output D, CH4 hour meter (s) | channel D, CH4 object 8 | 4 Bytes | 13.100 time lag (s) | CT |
| 35 | output D, CH4 limit reached | channel D, CH4 object 9 | 1 Bit | 1.2 boolean | CT |
Parameters (75)
| Parameter | Type | Default |
|---|---|---|
| usage | list | enabled |
| at buspower recovery set switching object to | list | do not initialize |
| relay contact is | list | NO (norm. open) |
| at buspower failure contact is | list | no change |
| timing functions | list | no |
| logic combination | list | no |
| status | list | no |
| scenes | list | no |
| announce function | list | no |
| inhibit function | list | no |
| hour meter | list | no |
| switch on delay | list | no |
| delay time (1..255 sec) | unsignedInt 1…255 | 5 |
| switch off delay | list | no |
| staircase function / blinking | list | no |
| on time (1..255 sec) | unsignedInt 1…255 | 3 |
| off time (1..255 sec) | unsignedInt 1…255 | 3 |
| staircase on time (1..64800 sec) | unsignedInt 1…64800 | 180 |
| retrigger staircase time (only, if on/off delay disabled) | list | yes |
| staircase prewarning | list | no |
| prewarning off time (1..30 *100 ms) | unsignedInt 1…30 | 5 |
| prewarning on time (1..255 sec) | unsignedInt 1…255 | 3 |
| number of prewarnings (1..7) | unsignedInt 1…7 | 3 |
| logic combination | list | none |
| at buspower recovery set logic object to | list | "1" |
| status is transmitted | list | at value change |
| status send delay time (0..120 *100 ms) | unsignedInt 0…120 | 1 |
| scene 1 | list | no action |
| scene 2 | list | no action |
| scene 3 | list | no action |
| scene 4 | list | no action |
| scene 5 | list | no action |
| scene 6 | list | no action |
| scene 7 | list | no action |
| scene 8 | list | no action |
| scene 9 | list | no action |
| scene 10 | list | no action |
| scene 11 | list | no action |
| scene 12 | list | no action |
| scene 13 | list | no action |
| scene 14 | list | no action |
| scene 15 | list | no action |
| scene 16 | list | no action |
| scene 17 | list | no action |
| scene 18 | list | no action |
| scene 19 | list | no action |
| scene 20 | list | no action |
| scene 21 | list | no action |
| scene 22 | list | no action |
| scene 23 | list | no action |
| scene 24 | list | no action |
| scene 25 | list | no action |
| scene 26 | list | no action |
| scene 27 | list | no action |
| scene 28 | list | no action |
| scene 29 | list | no action |
| scene 30 | list | no action |
| scene 31 | list | no action |
| scene 32 | list | no action |
| enable scene saving | list | no |
| announce with | list | "1" |
| at bus voltage recovery set announce object to | list | "0" |
| action when announce starts | list | no action |
| on time (1..15 sec) | unsignedInt 1…15 | 3 |
| off time (1..15 sec) | unsignedInt 1…15 | 3 |
| action when announce ends | list | no action |
| inhibit with | list | "1" |
| at bus voltage recovery set inhibit object to | list | "0" |
| action when inhibit starts | list | no action |
| action when inhibit ends | list | no action |
| hour meter values are presented in | list | DPT 7.007 hours (16bit unsigned int EIS10) |
| hour meter reading is transmitted | list | cyclically |
| cycle time | list | 5 min |
| hour meter limit monitoring | list | no |
| limit (1..65000 h) | unsignedInt 1…65535 | 1000 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| 4x switching, time, scene, announce, inh. 2025-21 2.1 latest | $2025 | D735 | 2026-11-25 | 93 KB | Download |
About this file
This is the official ETS product database for the Lingg & Janke switching actuator 4fold (A4FX-E-Q), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Lingg & Janke
- AH3F16H-SEC switching actuator 3fold 79236-SEC
- AH5F16H-SEC switching actuator 5fold 79237-SEC
- AH9F16H-SEC switching actuator 9fold 79238-SEC
- switching actuator 2fold A2FX-E-Q
- L&J secure switching actuator 2fold A2FX-SEC
- switching actor 2x6fold 16A hand A2X6F16H
- switching actuator 2x6fold A2X6F16H-2
- switching actuator 3fold A3FX-E-Q
- L&J secure switching actuator 3fold A3FX-SEC
- L&J secure switching actuator 4fold A4FX-SEC
- switching actuator 5fold A5FX-E-Q
- L&J secure switching actuator 5fold A5FX-SEC