MHVACSGW-KT.13 MHVACSGW 2508
HDL · Order number MHVACSGW 2508 · Environment
HDL KNX Indoor AC Gateway - KNX
Download .knxprod Indoor AC Gateway 1.0 · 123 KB
Product
| Manufacturer | HDL |
|---|---|
| Product name | MHVACSGW-KT.13 |
| Order number | MHVACSGW 2508 |
| Hardware | MHVACSGW-KT.13 |
| Medium | Twisted Pair |
| Bus current (mA) | 15 |
| Rail mounted | Yes |
| Registration | Registered · 2026-01-05 |
| Languages | en-US, zh-CN |
| Catalog entry | M-0073_H-MHVACSGW.202508-1_HP-2340-10-CE2A_CI-MHVACSGW.202508-1 |
| Fingerprint | CE2A |
| SHA-256 | 9e610842a3508d9ad8aa1212ce4442704cab83cdd677b00dfd209a48cb15a922 |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: Indoor AC Gateway 1.0
| Application number | $2340 |
|---|---|
| Version | 1.0 |
| Mask version | MV-07B0 (System B) |
| KNX Data Secure | No |
| Parameters | 134 |
| Group objects | 58 |
Group objects (58)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | General | Heartbeat telegram | 1 Bit | 1.3 enable | CT |
| 2 | Air Condition 1 | AC Switch ON/OFF(1bit) | 1 Bit | 1.1 switch | CWTU |
| 3 | Air Condition 1 | AC Switch ON/OFF Status(1bit) | 1 Bit | 1.1 switch | CRWTU |
| 4 | Air Condition 1 | AC Control Mode(1byte) | 1 Byte | 20.105 HVAC control mode | CWTU |
| 5 | Air Condition 1 | AC Control Mode Status(1byte) | 1 Byte | 20.105 HVAC control mode | CRWTU |
| 6 | Air Condition 1 | AC Humidity(1byte) | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 7 | Air Condition 1 | AC Humidity Status(1byte) | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 8 | Air Condition 1 | AC Circular Breath(1byte) | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 9 | Air Condition 1 | AC Circular Breath Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 10 | Air Condition 1 | AC Temperature Setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 11 | Air Condition 1 | AC Temperature Setpoint Status | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 12 | Air Condition 1 | AC Speed(1byte) | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 13 | Air Condition 1 | AC Speed Status(1byte) | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 14 | Air Condition 1 | AC Room Temperature(2byte) | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 15 | Air Condition 1 | AC Online/Offline Status(1bit) | 1 Bit | 1.1 switch | CRWTU |
| 16 | Air Condition 1 | AC Fault stutus(1bit) | 1 Bit | 1.1 switch | CRWTU |
| 17 | Air Condition 1 | AC Swing Mode(1byte) | 1 Byte | 5.100 fan stage (0..255) | CWTU |
| 18 | Air Condition 1 | AC Swing Mode Status(1byte) | 1 Byte | 5.100 fan stage (0..255) | CRWTU |
| 19 | Air Condition 1 | AC Clean Filter Reset(1bit) | 1 Bit | 1.1 switch | CWTU |
| 20 | Air Condition 1 | AC Clean Filter Reset Status | 1 Bit | 1.1 switch | CRWTU |
| 21 | Fresh Air 1 | Switch ON/OFF(1bit) | 1 Bit | 1.1 switch | CWTU |
| 22 | Fresh Air 1 | Switch ON/OFF Status(1bit) | 1 Bit | 1.1 switch | CRWTU |
| 23 | Fresh Air 1 | Mode(1byte) | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 24 | Fresh Air 1 | Mode Status(1byte) | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 25 | Fresh Air 1 | Fan Speed(1byte) | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 26 | Fresh Air 1 | Fan Speed Status(1byte) | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 27 | Fresh Air 1 | Setpoint Temperature(2byte) | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 28 | Fresh Air 1 | Setpoint Temperature Status | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 29 | Fresh Air 1 | Room Temperature(2byte) | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 30 | Fresh Air 1 | Air PM2.5(2byte) | 2 Bytes | 9.30 concentration (µg/m³) | CRWTU |
| 31 | Fresh Air 1 | Air VOC(2byte) | 2 Bytes | 9.30 concentration (µg/m³) | CRWTU |
| 32 | Fresh Air 1 | Air CO2(2byte) | 2 Bytes | 9.30 concentration (µg/m³) | CRWTU |
| 33 | Fresh Air 1 | Online/Offline Status(1bit) | 1 Bit | 1.1 switch | CRWTU |
| 34 | Fresh Air 1 | Fault stutus(1bit) | 1 Bit | 1.1 switch | CRWTU |
| 35 | Fresh Air 1 | Clean Filter Reset(1bit) | 1 Bit | 1.1 switch | CWTU |
| 36 | Fresh Air 1 | Clean Filter Reset Status | 1 Bit | 1.1 switch | CRWTU |
| 37 | Heating 1 | Switch ON/OFF | 1 Bit | 1.1 switch | CWTU |
| 38 | Heating 1 | Switch ON/OFF Status | 1 Bit | 1.1 switch | CRWTU |
| 39 | Heating 1 | Normal Mode ON/OFF | 1 Bit | 1.1 switch | CWTU |
| 40 | Heating 1 | Normal Mode ON/OFF Status | 1 Bit | 1.1 switch | CRWTU |
| 41 | Heating 1 | Day Mode ON/OFF | 1 Bit | 1.1 switch | CWTU |
| 42 | Heating 1 | Day Mode ON/OFF Status | 1 Bit | 1.1 switch | CRWTU |
| 43 | Heating 1 | Night Mode ON/OFF | 1 Bit | 1.1 switch | CWTU |
| 44 | Heating 1 | Night Mode ON/OFF Status | 1 Bit | 1.1 switch | CRWTU |
| 45 | Heating 1 | Away Mode ON/OFF | 1 Bit | 1.1 switch | CWTU |
| 46 | Heating 1 | Away Mode ON/OFF Status | 1 Bit | 1.1 switch | CRWTU |
| 47 | Heating 1 | Timer Mode ON/OFF | 1 Bit | 1.1 switch | CWTU |
| 48 | Heating 1 | Timer Mode ON/OFF Status | 1 Bit | 1.1 switch | CRWTU |
| 49 | Heating 1 | Mute Mode ON/OFF | 1 Bit | 1.1 switch | CWTU |
| 50 | Heating 1 | Mute Mode ON/OFF Status | 1 Bit | 1.1 switch | CRWTU |
| 51 | Heating 1 | Frost protection mode | 1 Bit | 1.1 switch | CWTU |
| 52 | Heating 1 | Frost protection mode Status | 1 Bit | 1.1 switch | CRWTU |
| 53 | Heating 1 | Temperature Setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 54 | Heating 1 | Temperature Setpoint Status | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 55 | Heating 1 | Room Temperature(2byte) | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 56 | Heating 1 | Outdoor Temperature(2byte) | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 57 | Heating 1 | Online/Offline Status(1bit) | 1 Bit | 1.1 switch | CRWTU |
| 58 | Heating 1 | Fault stutus(1bit) | 1 Bit | 1.1 switch | CRWTU |
Parameters (110)
| Parameter | Type | Default |
|---|---|---|
| Operation delay after power on(2..200s) | unsignedInt 2…255 | 2 |
| Heartbeat telegram | list | Disable |
| NULL | list | Disable |
| >Telegram is sent time interval(1..65535s) | unsignedInt 1…65535 | 60 |
| Work mode | list | Please select |
| Baud rate | list | 19200 |
| Parity | list | None |
| Data bits | list | 8 bits |
| Stop bits | list | 1 bit |
| AC Online/Offline report | list | Disable |
| AC Fault stutus report | list | Disable |
| AC Room temperature report | list | Disable |
| Control mode | list | Standard |
| Advanced control mode | list | Disable |
| --> Fan | unsignedInt 0…255 | 9 |
| --> Heat | unsignedInt 0…255 | 1 |
| --> Cool | unsignedInt 0…255 | 3 |
| --> Dehumidification | unsignedInt 0…255 | 14 |
| --> Sleep | unsignedInt 0…255 | 255 |
| --> Dry | unsignedInt 0…255 | 255 |
| --> Fresh and cool | unsignedInt 0…255 | 255 |
| --> Auto dehumidification | unsignedInt 0…255 | 255 |
| --> Strong heating | unsignedInt 0…255 | 255 |
| --> Heating_floor | unsignedInt 0…255 | 255 |
| --> Preheat | unsignedInt 0…255 | 255 |
| Humidity | list | Disable |
| --> Humidity_OFF | unsignedInt 0…255 | 0 |
| --> Humidity_1 | unsignedInt 0…255 | 75 |
| --> Humidity_2 | unsignedInt 0…255 | 155 |
| --> Humidity_3 | unsignedInt 0…255 | 255 |
| Circular breathing | list | Disable |
| --> OFF | unsignedInt 0…255 | 0 |
| --> Strong | unsignedInt 0…255 | 255 |
| --> Weak | unsignedInt 0…255 | 55 |
| --> Auto | unsignedInt 0…255 | 51 |
| --> High | unsignedInt 0…255 | 204 |
| --> Mid-High | unsignedInt 0…255 | 180 |
| --> Mid | unsignedInt 0…255 | 153 |
| --> Mid-Low | unsignedInt 0…255 | 125 |
| --> Low | unsignedInt 0…255 | 102 |
| --> Superstrong | unsignedInt 0…255 | 255 |
| --> Ultrstatic | unsignedInt 0…255 | 51 |
| Swing | list | Disable |
| --> Swing up down and left right | unsignedInt 0…255 | 0 |
| --> Swing up down P1 | unsignedInt 0…255 | 1 |
| --> Swing up down P2 | unsignedInt 0…255 | 2 |
| --> Swing up down P3 | unsignedInt 0…255 | 3 |
| --> Swing up down P4 | unsignedInt 0…255 | 4 |
| --> Swing up down P5 | unsignedInt 0…255 | 5 |
| --> Swing up down P6 | unsignedInt 0…255 | 6 |
| --> Swing left right P1 | unsignedInt 0…255 | 7 |
| --> Swing left right P2 | unsignedInt 0…255 | 8 |
| --> Swing left right P3 | unsignedInt 0…255 | 9 |
| --> Swing left right P4 | unsignedInt 0…255 | 10 |
| --> Swing left right P5 | unsignedInt 0…255 | 11 |
| --> Swing left right P6 | unsignedInt 0…255 | 12 |
| --> Set temperature Min | unsignedInt 0…32 | 0 |
| --> Set temperature Max | unsignedInt 0…32 | 32 |
| Clean filter | list | Disable |
| Fresh Online/Offline report | list | Disable |
| Fresh Fault stutus report | list | Disable |
| Fresh Room temperature report | list | Disable |
| Fresh Air quality report | list | Disable |
| --> Change | unsignedInt 0…255 | 1 |
| --> Exhaust | unsignedInt 0…255 | 2 |
| --> Smart | unsignedInt 0…255 | 3 |
| --> Strong | unsignedInt 0…255 | 4 |
| --> Blowing-in | unsignedInt 0…255 | 255 |
| --> Bypass | unsignedInt 0…255 | 255 |
| --> Quick clean | unsignedInt 0…255 | 255 |
| --> Comfort | unsignedInt 0…255 | 255 |
| --> Cool breeze | unsignedInt 0…255 | 255 |
| --> Manual operation | unsignedInt 0…255 | 255 |
| --> Silence | unsignedInt 0…255 | 255 |
| --> Fresh air | unsignedInt 0…255 | 255 |
| --> Cool | unsignedInt 0…255 | 255 |
| --> Heat | unsignedInt 0…255 | 255 |
| --> Dehumidification | unsignedInt 0…255 | 255 |
| --> Heat exchange | unsignedInt 0…255 | 255 |
| --> Internal recycle | unsignedInt 0…255 | 255 |
| --> Outside loop | unsignedInt 0…255 | 255 |
| --> Mixed air | unsignedInt 0…255 | 255 |
| --> Close | unsignedInt 0…255 | 255 |
| --> Fresh air dehumidifies | unsignedInt 0…255 | 255 |
| --> Tming | unsignedInt 0…255 | 255 |
| --> Haze removal | unsignedInt 0…255 | 255 |
| --> Defrost | unsignedInt 0…255 | 255 |
| --> Internal dehumidification | unsignedInt 0…255 | 255 |
| --> Auto | unsignedInt 0…255 | 102 |
| --> Mid-Low | unsignedInt 0…255 | 120 |
| --> Close | unsignedInt 0…255 | 0 |
| Heat Online/Offline report | list | Disable |
| Heat Fault stutus report | list | Disable |
| Heat Room temperature report | list | Disable |
| Heat Temperature sensor | list | Disable |
| Heat Frost protection mode | list | Disable |
| --> ON/OFF Value | list | 1-ON/0-OFF |
| Normal Mode | list | Disable |
| --> Normal Mode Default Temp | unsignedInt 0…255 | 25 |
| Day Mode | list | Disable |
| --> Day Mode Default Temp | unsignedInt 0…255 | 25 |
| Night Mode | list | Disable |
| --> Night Mode Default Temp | unsignedInt 0…255 | 25 |
| Away Mode | list | Disable |
| --> Away Mode Default Temp | unsignedInt 0…255 | 25 |
| Timer Mode | list | Disable |
| --> Timer Mode Default Temp | unsignedInt 0…255 | 25 |
| Mute | list | Disable |
| --> Set temperature Min | unsignedInt 0…55 | 0 |
| --> Set temperature Max | unsignedInt 0…55 | 55 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Indoor AC Gateway 1.0 latest | $2340 | CE2A | 2026-11-25 | 123 KB | Download |
About this file
This is the official ETS product database for the HDL MHVACSGW-KT.13 (MHVACSGW 2508), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from HDL
- M/CBVRV.GW.1 M/CBVRVGW1905
- M/FCHC.4.1 M/FCHC 1605 F002
- M/FCU01.10.1 M/FCU01 1206 F001
- MHVACMGW-KT.13 MHVACMGW 2508
- M/AG40B.1 M/AG40B 1811 W006
- M/DA6.10.1 M/DA 1110 D005
- MDL64-KT.53 M/DALI 1410 2603
- M/DALI.1 M/DALI 1410 DL001
- MDL64-KT.53 M/DALI 1410 DL002
- M/DLP04.1-A2 M/DLP 1209 P001
- M/DM02.1 M/DM02C1902
- M/DM02.1 M/DM02C2604