M/FCHC.4.1 M/FCHC 1605 F002
HDL · Order number M/FCHC 1605 F002 · Environment
HDL DIN Rail FCH & 6CH Heating & Compressor - KNX
Download .knxprod FCHC Actuator(V1.1) 1.1 · 212 KB
Product
| Manufacturer | HDL |
|---|---|
| Product name | M/FCHC.4.1 |
| Order number | M/FCHC 1605 F002 |
| Hardware | M/FCHC.4.1 |
| Medium | Twisted Pair |
| Bus current (mA) | 21 |
| Rail mounted | No |
| Registration | Certified · 2017-05-08 |
| Languages | en-US, zh-CN |
| Catalog entry | M-0073_H-M.2FFCHC.201605.20F002-10_HP-2250-11-C606_CI-M.2FFCHC.201605.20F002-4 |
| Fingerprint | C606 |
| SHA-256 | 5bf9aa2cae2ea3a805d89d0c0c47a0f49e87d075f0f5df516d7a43a0cfa0d708 |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: FCHC Actuator(V1.1) 1.1
| Application number | $2250 |
|---|---|
| Version | 1.1 |
| Mask version | MV-07B0 (System B) |
| KNX Data Secure | No |
| Minimum ETS version | 3.0f |
| Parameters | 909 |
| Group objects | 392 |
Group objects (392)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | Heartbeat | Send value "0" | 1 Bit | 1.3 enable | CRTU |
| 1 | Heartbeat | Send value "1" | 1 Bit | 1.3 enable | CRTU |
| 1 | Heartbeat | Send value "0/1" | 1 Bit | 1.3 enable | CRTU |
| 2 | Slave clock | Network datetime | 8 Bytes | 19.1 date time | CWTU |
| 3 | Slave clock | Network date | 3 Bytes | 11.1 date | CWTU |
| 4 | Slave clock | Network time of day | 3 Bytes | 10.1 time of day | CWTU |
| 5 | FloorHeating | Reduce valve pressure signal | 1 Bit | 1.3 enable | CRTU |
| 6 | Local temperature | Measured by local sensor | 2 Bytes | 9.1 temperature (°C) | CRT |
| 7 | Local temperature | Local sensor error signal | 1 Bit | 1.5 alarm | CRT |
| 8 | Local temperature | Ultra temperature alarm signal | 1 Bit | 1.5 alarm | CRT |
| 9 | General | System ON/OFF | 1 Bit | 1.1 switch | CW |
| 11 | Actual temperature | Actual temperature 1 | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 11 | Fan ABC | Actual temperature 1 | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 12 | Actual temperature | Actual temperature 2 | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 12 | Fan ABC | Actual temperature 2 | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 13 | Fan DEF | Actual temperature 1 | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 13 | Actual temperature | Actual temperature 3 | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 14 | Fan DEF | Actual temperature 2 | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 14 | Actual temperature | Actual temperature 4 | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 15 | NULL | NULL | 1 Bit | ||
| 16 | Actual temperature | Actual temp. 1 error signal | 1 Bit | 1.5 alarm | CRT |
| 16 | Fan ABC | Actual temp. 1 error signal | 1 Bit | 1.5 alarm | CRT |
| 17 | Actual temperature | Actual temp. 2 error signal | 1 Bit | 1.5 alarm | CRT |
| 17 | Fan ABC | Actual temp. 2 error signal | 1 Bit | 1.5 alarm | CRT |
| 18 | Fan DEF | Actual temp. 1 error signal | 1 Bit | 1.5 alarm | CRT |
| 19 | Fan DEF | Actual temp. 2 error signal | 1 Bit | 1.5 alarm | CRT |
| 20 | Actual temperature | Frost/heat alarm error signal | 1 Bit | 1.5 alarm | CRT |
| 21 | HVAC setpoint | Base setpoint temperature | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 21 | Fan ABC | Base setpoint temperature | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 21 | Compressor 1 & 2 | Base setpoint temperature | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 21 | Control value A | Heating/Cooling | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 21 | Control value A | Heating or Cooling | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 21 | Control value A | Heating | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 21 | Fan ABC | Control value A | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 21 | Compressor 1 & 2 | Control value A | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 21 | Floor heating A | Control value A | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 22 | HVAC setpoint | Instantaneous setpoint temp. | 2 Bytes | 9.1 temperature (°C) | CRT |
| 22 | Control value B | Heating/Cooling | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 22 | Control value B | Cooling | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 22 | Fan ABC | Control value B | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 22 | Compressor 1 & 2 | Control value B | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 22 | Floor heating B | Control value B | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 23 | Fan DEF | Control value C | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 23 | Floor heating C | Control value C | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 24 | Fan DEF | Control value D | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 24 | Floor heating D | Control value D | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 25 | Floor heating E | Control value E | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 26 | Fan DEF | Base setpoint temperature | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 26 | Floor heating F | Control value F | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 27 | NULL | NULL | 1 Bit | ||
| 28 | Toggle heat/cool | Heat-1,Cool-0 | 1 Bit | 1.1 switch | CWTU |
| 28 | Toggle heat/cool | Heat-0,Cool-1 | 1 Bit | 1.1 switch | CWTU |
| 28 | Toggle heat/cool | A-1,B-0 | 1 Bit | 1.1 switch | CWTU |
| 28 | Toggle heat/cool | A-0,B-1 | 1 Bit | 1.1 switch | CWTU |
| 28 | Fan ABC | Toggle A/B (0-A,1-B) | 1 Bit | 1.1 switch | CWTU |
| 28 | Compressor 1 & 2 | Toggle A/B (0-A,1-B) | 1 Bit | 1.1 switch | CWTU |
| 29 | Fan DEF | Toggle C/D (0-C,1-D) | 1 Bit | 1.1 switch | CWTU |
| 30 | NULL | NULL | 1 Bit | ||
| 31 | Control value A | Control value error signal 1 | 1 Bit | 1.5 alarm | CRT |
| 31 | Fan ABC | Control value error signal | 1 Bit | 1.5 alarm | CRT |
| 31 | Compressor 1 & 2 | Control value error signal | 1 Bit | 1.5 alarm | CRT |
| 31 | Floor heating A | Control value error signal 1 | 1 Bit | 1.5 alarm | CRT |
| 32 | Control value B | Control value error signal 2 | 1 Bit | 1.5 alarm | CRT |
| 32 | Floor heating B | Control value error signal 2 | 1 Bit | 1.5 alarm | CRT |
| 33 | Fan DEF | Control value error signal | 1 Bit | 1.5 alarm | CRT |
| 33 | Floor heating C | Control value error signal 3 | 1 Bit | 1.5 alarm | CRT |
| 34 | Floor heating D | Control value error signal 4 | 1 Bit | 1.5 alarm | CRT |
| 35 | Floor heating E | Control value error signal 5 | 1 Bit | 1.5 alarm | CRT |
| 36 | Floor heating F | Control value error signal 6 | 1 Bit | 1.5 alarm | CRT |
| 37 | Actual temperature | Actual temperature 3 | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 37 | Fan ABC | Actual temperature 3 | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 37 | NULL | NULL | 1 Bit | ||
| 38 | Actual temperature | Actual temperature 4 | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 38 | Fan ABC | Actual temperature 4 | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 38 | NULL | NULL | 1 Bit | ||
| 39 | Fan DEF | Actual temperature 3 | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 39 | NULL | NULL | 1 Bit | ||
| 40 | Fan DEF | Actual temperature 4 | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 40 | NULL | NULL | 1 Bit | ||
| 41 | Fan ABC | Fan speed 1 | 1 Bit | 1.1 switch | CW |
| 41 | Floor heating A | Actual temperature | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 42 | Fan ABC | Fan speed 2 | 1 Bit | 1.1 switch | CW |
| 42 | Floor heating A | Actual temp. error signal | 1 Bit | 1.5 alarm | CRT |
| 43 | Fan ABC | Fan speed 3 | 1 Bit | 1.1 switch | CW |
| 43 | Floor heating A | Normal-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 44 | Fan ABC | Fan speed automatic | 1 Bit | 1.3 enable | CW |
| 44 | Floor heating A | Day-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 45 | Fan ABC | Fan speed % switch | 1 Byte | 5.1 percentage (0..100%) | CW |
| 45 | Fan ABC | Fan speed 0-3 switch | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 45 | Floor heating A | Night-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 46 | Fan ABC | Fan speed up/down | 1 Bit | 1.8 up/down | CW |
| 46 | Floor heating A | Away-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 47 | Fan ABC | Fan forced operation | 1 Bit | 1.1 switch | CW |
| 47 | Floor heating A | Preset 1 Temp. for timer mode | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 48 | Floor heating A | Time of day for preset 1 | 3 Bytes | 10.1 time of day | CRWTU |
| 49 | Floor heating A | Start/Stop heating for preset1 | 1 Bit | 1.10 start/stop | CRWT |
| 50 | Floor heating A | Preset 2 Temp. for timer mode | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 51 | Fan ABC | Status fan speed 1 | 1 Bit | 1.1 switch | CRT |
| 51 | Floor heating A | Time of day for preset 2 | 3 Bytes | 10.1 time of day | CRWTU |
| 52 | Fan ABC | Status fan speed 2 | 1 Bit | 1.1 switch | CRT |
| 52 | Floor heating A | Start/Stop heating for preset2 | 1 Bit | 1.10 start/stop | CRWT |
| 53 | Fan ABC | Status fan speed 3 | 1 Bit | 1.1 switch | CRT |
| 53 | Floor heating A | Preset 3 Temp. for timer mode | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 54 | Fan ABC | Status fan speed automatic | 1 Bit | 1.3 enable | CRT |
| 54 | Floor heating A | Time of day for preset 3 | 3 Bytes | 10.1 time of day | CRWTU |
| 55 | Fan ABC | Status fan speed | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 55 | Floor heating A | Start/Stop heating for preset3 | 1 Bit | 1.10 start/stop | CRWT |
| 56 | Fan ABC | Status fan ON/OFF | 1 Bit | 1.1 switch | CRT |
| 56 | Floor heating A | Floor heating(1-ON,0-OFF) | 1 Bit | 1.1 switch | CW |
| 56 | Floor heating A | Floor heating(1-ON,0-OFF) | 1 Bit | 1.1 switch | CRWTU |
| 57 | Fan ABC | Status fan forced operation | 1 Bit | 1.1 switch | CRT |
| 57 | Fan ABC | Status fan force operation | 1 Bit | 1.1 switch | CRT |
| 57 | Floor heating A | ON CMD for Normal-mode | 1 Bit | 1.1 switch | CRWTU |
| 58 | Floor heating A | ON CMD for Day-mode | 1 Bit | 1.1 switch | CRWTU |
| 59 | Floor heating A | ON CMD for Night-mode | 1 Bit | 1.1 switch | CRWTU |
| 60 | Floor heating A | ON CMD for Away-mode | 1 Bit | 1.1 switch | CRWTU |
| 61 | Fan ABC | Limitation 1 | 1 Bit | 1.3 enable | CRWT |
| 61 | Floor heating A | ON CMD for Timer-mode | 1 Bit | 1.1 switch | CRWTU |
| 62 | Fan ABC | Limitation 2 | 1 Bit | 1.3 enable | CRWT |
| 62 | Floor heating A | Status valve position | 1 Bit | 1.1 switch | CRT |
| 63 | Fan ABC | Limitation 3 | 1 Bit | 1.3 enable | CRWT |
| 63 | Floor heating A | Trigger valve purge | 1 Bit | 1.17 trigger | CW |
| 64 | Fan ABC | Limitation 4 | 1 Bit | 1.3 enable | CRWT |
| 64 | Floor heating A | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 65 | Floor heating A | Instantaneous setpoint temp. | 2 Bytes | 9.1 temperature (°C) | CRT |
| 66 | Floor heating A | Valve open/close directly | 1 Bit | 1.9 open/close | CW |
| 67 | Actual temperature | Actual temp. 3 error signal | 1 Bit | 1.5 alarm | CRT |
| 67 | Fan ABC | Actual temp. 3 error signal | 1 Bit | 1.5 alarm | CRT |
| 67 | NULL | NULL | 1 Bit | ||
| 68 | Actual temperature | Actual temp. 4 error signal | 1 Bit | 1.5 alarm | CRT |
| 68 | Fan ABC | Actual temp. 4 error signal | 1 Bit | 1.5 alarm | CRT |
| 68 | NULL | NULL | 1 Bit | ||
| 69 | Fan DEF | Actual temp. 3 error signal | 1 Bit | 1.5 alarm | CRT |
| 69 | NULL | NULL | 1 Bit | ||
| 70 | Fan DEF | Actual temp. 4 error signal | 1 Bit | 1.5 alarm | CRT |
| 70 | NULL | NULL | 1 Bit | ||
| 71 | HVAC controlling mode | HVAC control mode (byte) | 1 Byte | 20.105 HVAC control mode | CW |
| 71 | Floor heating B | Actual temperature | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 72 | HVAC controlling mode | Activation of heat | 1 Bit | 1.3 enable | CW |
| 72 | Floor heating B | Actual temp. error signal | 1 Bit | 1.5 alarm | CRT |
| 73 | HVAC controlling mode | Activation of cool | 1 Bit | 1.3 enable | CW |
| 73 | Floor heating B | Normal-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 74 | HVAC controlling mode | Activation of fan only | 1 Bit | 1.3 enable | CW |
| 74 | Floor heating B | Day-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 75 | HVAC controlling mode | Activation of off | 1 Bit | 1.3 enable | CW |
| 75 | Floor heating B | Night-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 76 | HVAC controlling mode | Activation of auto | 1 Bit | 1.3 enable | CW |
| 76 | Floor heating B | Away-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 77 | Floor heating B | Preset 1 Temp. for timer mode | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 78 | Floor heating B | Time of day for preset 1 | 3 Bytes | 10.1 time of day | CRWTU |
| 79 | Floor heating B | Start/Stop heating for preset1 | 1 Bit | 1.10 start/stop | CRWT |
| 80 | Floor heating B | Preset 2 Temp. for timer mode | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 81 | HVAC operating mode | HVAC operating mode (byte) | 1 Byte | 20.102 HVAC mode | CW |
| 81 | Floor heating B | Time of day for preset 2 | 3 Bytes | 10.1 time of day | CRWTU |
| 82 | HVAC operating mode | ON CMD for comfort mode | 1 Bit | 1.1 switch | CW |
| 82 | Floor heating B | Start/Stop heating for preset2 | 1 Bit | 1.10 start/stop | CRWT |
| 83 | HVAC operating mode | ON CMD for standby mode | 1 Bit | 1.1 switch | CW |
| 83 | Floor heating B | Preset 3 Temp. for timer mode | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 84 | HVAC operating mode | ON CMD for economy mode | 1 Bit | 1.1 switch | CW |
| 84 | Floor heating B | Time of day for preset 3 | 3 Bytes | 10.1 time of day | CRWTU |
| 85 | HVAC operating mode | ON CMD for building protection | 1 Bit | 1.1 switch | CW |
| 85 | Floor heating B | Start/Stop heating for preset3 | 1 Bit | 1.10 start/stop | CRWT |
| 86 | HVAC alarm | Dew point alarm | 1 Bit | 1.5 alarm | CW |
| 86 | Floor heating B | Floor heating(1-ON,0-OFF) | 1 Bit | 1.1 switch | CW |
| 86 | Floor heating B | Floor heating(1-ON,0-OFF) | 1 Bit | 1.1 switch | CRWTU |
| 87 | Floor heating B | ON CMD for Normal-mode | 1 Bit | 1.1 switch | CRWTU |
| 88 | Floor heating B | ON CMD for Day-mode | 1 Bit | 1.1 switch | CRWTU |
| 89 | Floor heating B | ON CMD for Night-mode | 1 Bit | 1.1 switch | CRWTU |
| 90 | Floor heating B | ON CMD for Away-mode | 1 Bit | 1.1 switch | CRWTU |
| 91 | Valve Heating | Status valve position | 1 Bit | 1.1 switch | CRT |
| 91 | Valve Heating/Cooling | Status valve position | 1 Bit | 1.1 switch | CRT |
| 91 | Floor heating B | ON CMD for Timer-mode | 1 Bit | 1.1 switch | CRWTU |
| 92 | Valve Heating | Trigger valve purge | 1 Bit | 1.17 trigger | CW |
| 92 | Valve Heating/Cooling | Trigger valve purge | 1 Bit | 1.17 trigger | CW |
| 92 | Floor heating B | Status valve position | 1 Bit | 1.1 switch | CRT |
| 93 | Valve Heating | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 93 | Valve Heating/Cooling | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 93 | Floor heating B | Trigger valve purge | 1 Bit | 1.17 trigger | CW |
| 94 | Valve Heating/Cooling | Valve open/close directly | 1 Bit | 1.9 open/close | CW |
| 94 | Valve Heating | Valve open/close directly | 1 Bit | 1.9 open/close | CW |
| 94 | Floor heating B | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 95 | Floor heating B | Instantaneous setpoint temp. | 2 Bytes | 9.1 temperature (°C) | CRT |
| 96 | Valve Cooling | Status valve position | 1 Bit | 1.1 switch | CRT |
| 96 | Floor heating B | Valve open/close directly | 1 Bit | 1.9 open/close | CW |
| 97 | Valve Cooling | Trigger valve purge | 1 Bit | 1.17 trigger | CW |
| 98 | Valve Cooling | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 99 | Valve Cooling | Valve open/close directly | 1 Bit | 1.9 open/close | CW |
| 100 | NULL | NULL | 1 Bit | ||
| 101 | Switch D | Channel output | 1 Bit | 1.1 switch | CW |
| 101 | Floor heating C | Actual temperature | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 102 | Switch D | Switch status | 1 Bit | 1.1 switch | CRT |
| 102 | Floor heating C | Actual temp. error signal | 1 Bit | 1.5 alarm | CRT |
| 103 | Switch D | Read statistic for hours | 2 Bytes | 7.7 time (h) | CRT |
| 103 | Floor heating C | Normal-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 104 | Switch D | Alarm statistic for time out | 1 Bit | 1.5 alarm | CRT |
| 104 | Floor heating C | Day-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 105 | Switch D | Staircase light ON/OFF | 1 Bit | 1.1 switch | CW |
| 105 | Floor heating C | Night-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 106 | Switch D | Alarm staircase lighting | 1 Bit | 1.5 alarm | CRT |
| 106 | Floor heating C | Away-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 107 | Switch D | Write statistic for hours | 2 Bytes | 7.7 time (h) | CWT |
| 107 | Floor heating C | Preset 1 Temp. for timer mode | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 108 | Switch D | RW statistic for seconds | 4 Bytes | 13.100 time lag (s) | CRWT |
| 108 | Floor heating C | Time of day for preset 1 | 3 Bytes | 10.1 time of day | CRWTU |
| 109 | Floor heating C | Start/Stop heating for preset1 | 1 Bit | 1.10 start/stop | CRWT |
| 110 | Floor heating C | Preset 2 Temp. for timer mode | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 111 | Switch E | Channel output | 1 Bit | 1.1 switch | CW |
| 111 | Floor heating C | Time of day for preset 2 | 3 Bytes | 10.1 time of day | CRWTU |
| 112 | Switch E | Switch status | 1 Bit | 1.1 switch | CRT |
| 112 | Floor heating C | Start/Stop heating for preset2 | 1 Bit | 1.10 start/stop | CRWT |
| 113 | Switch E | Read statistic for hours | 2 Bytes | 7.7 time (h) | CRT |
| 113 | Floor heating C | Preset 3 Temp. for timer mode | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 114 | Switch E | Alarm statistic for time out | 1 Bit | 1.5 alarm | CRT |
| 114 | Floor heating C | Time of day for preset 3 | 3 Bytes | 10.1 time of day | CRWTU |
| 115 | Switch E | Staircase light ON/OFF | 1 Bit | 1.1 switch | CW |
| 115 | Floor heating C | Start/Stop heating for preset3 | 1 Bit | 1.10 start/stop | CRWT |
| 116 | Switch E | Alarm staircase lighting | 1 Bit | 1.5 alarm | CRT |
| 116 | Floor heating C | Floor heating(1-ON,0-OFF) | 1 Bit | 1.1 switch | CW |
| 116 | Floor heating C | Floor heating(1-ON,0-OFF) | 1 Bit | 1.1 switch | CRWTU |
| 117 | Switch E | Write statistic for hours | 2 Bytes | 7.7 time (h) | CWT |
| 117 | Floor heating C | ON CMD for Normal-mode | 1 Bit | 1.1 switch | CRWTU |
| 118 | Switch E | RW statistic for seconds | 4 Bytes | 13.100 time lag (s) | CRWT |
| 118 | Floor heating C | ON CMD for Day-mode | 1 Bit | 1.1 switch | CRWTU |
| 119 | Floor heating C | ON CMD for Night-mode | 1 Bit | 1.1 switch | CRWTU |
| 120 | Floor heating C | ON CMD for Away-mode | 1 Bit | 1.1 switch | CRWTU |
| 121 | Switch F | Channel output | 1 Bit | 1.1 switch | CW |
| 121 | Floor heating C | ON CMD for Timer-mode | 1 Bit | 1.1 switch | CRWTU |
| 122 | Switch F | Switch status | 1 Bit | 1.1 switch | CRT |
| 122 | Floor heating C | Status valve position | 1 Bit | 1.1 switch | CRT |
| 123 | Switch F | Read statistic for hours | 2 Bytes | 7.7 time (h) | CRT |
| 123 | Floor heating C | Trigger valve purge | 1 Bit | 1.17 trigger | CW |
| 124 | Switch F | Alarm statistic for time out | 1 Bit | 1.5 alarm | CRT |
| 124 | Floor heating C | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 125 | Switch F | Staircase light ON/OFF | 1 Bit | 1.1 switch | CW |
| 125 | Floor heating C | Instantaneous setpoint temp. | 2 Bytes | 9.1 temperature (°C) | CRT |
| 126 | Switch F | Alarm staircase lighting | 1 Bit | 1.5 alarm | CRT |
| 126 | Floor heating C | Valve open/close directly | 1 Bit | 1.9 open/close | CW |
| 127 | Switch F | Write statistic for hours | 2 Bytes | 7.7 time (h) | CWT |
| 128 | Switch F | RW statistic for seconds | 4 Bytes | 13.100 time lag (s) | CRWT |
| 129 | NULL | NULL | 1 Bit | ||
| 130 | NULL | NULL | 1 Bit | ||
| 131 | Floor heating D | Actual temperature | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 132 | Floor heating D | Actual temp. error signal | 1 Bit | 1.5 alarm | CRT |
| 133 | Floor heating D | Normal-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 134 | Floor heating D | Day-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 135 | Floor heating D | Night-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 136 | Floor heating D | Away-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 137 | Floor heating D | Preset 1 Temp. for timer mode | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 138 | Floor heating D | Time of day for preset 1 | 3 Bytes | 10.1 time of day | CRWTU |
| 139 | Floor heating D | Start/Stop heating for preset1 | 1 Bit | 1.10 start/stop | CRWT |
| 140 | Floor heating D | Preset 2 Temp. for timer mode | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 141 | Fan DEF | Fan speed 1 | 1 Bit | 1.1 switch | CW |
| 141 | Floor heating D | Time of day for preset 2 | 3 Bytes | 10.1 time of day | CRWTU |
| 142 | Fan DEF | Fan speed 2 | 1 Bit | 1.1 switch | CW |
| 142 | Floor heating D | Start/Stop heating for preset2 | 1 Bit | 1.10 start/stop | CRWT |
| 143 | Fan DEF | Fan speed 3 | 1 Bit | 1.1 switch | CW |
| 143 | Floor heating D | Preset 3 Temp. for timer mode | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 144 | Fan DEF | Fan speed automatic | 1 Bit | 1.3 enable | CW |
| 144 | Floor heating D | Time of day for preset 3 | 3 Bytes | 10.1 time of day | CRWTU |
| 145 | Fan DEF | Fan speed % switch | 1 Byte | 5.1 percentage (0..100%) | CW |
| 145 | Fan DEF | Fan speed 0-3 switch | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 145 | Floor heating D | Start/Stop heating for preset3 | 1 Bit | 1.10 start/stop | CRWT |
| 146 | Fan DEF | Fan speed up/down | 1 Bit | 1.8 up/down | CW |
| 146 | Floor heating D | Floor heating(1-ON,0-OFF) | 1 Bit | 1.1 switch | CW |
| 146 | Floor heating D | Floor heating(1-ON,0-OFF) | 1 Bit | 1.1 switch | CRWTU |
| 147 | Fan DEF | Fan forced operation | 1 Bit | 1.1 switch | CW |
| 147 | Floor heating D | ON CMD for Normal-mode | 1 Bit | 1.1 switch | CRWTU |
| 148 | Floor heating D | ON CMD for Day-mode | 1 Bit | 1.1 switch | CRWTU |
| 149 | Floor heating D | ON CMD for Night-mode | 1 Bit | 1.1 switch | CRWTU |
| 150 | Floor heating D | ON CMD for Away-mode | 1 Bit | 1.1 switch | CRWTU |
| 151 | Fan DEF | Status fan speed 1 | 1 Bit | 1.1 switch | CRT |
| 151 | Floor heating D | ON CMD for Timer-mode | 1 Bit | 1.1 switch | CRWTU |
| 152 | Fan DEF | Status fan speed 2 | 1 Bit | 1.1 switch | CRT |
| 152 | Floor heating D | Status valve position | 1 Bit | 1.1 switch | CRT |
| 153 | Fan DEF | Status fan speed 3 | 1 Bit | 1.1 switch | CRT |
| 153 | Floor heating D | Trigger valve purge | 1 Bit | 1.17 trigger | CW |
| 154 | Fan DEF | Status fan speed automatic | 1 Bit | 1.3 enable | CRT |
| 154 | Floor heating D | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 155 | Fan DEF | Status fan speed | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 155 | Floor heating D | Instantaneous setpoint temp. | 2 Bytes | 9.1 temperature (°C) | CRT |
| 156 | Fan DEF | Status fan ON/OFF | 1 Bit | 1.1 switch | CRT |
| 156 | Floor heating D | Valve open/close directly | 1 Bit | 1.9 open/close | CW |
| 157 | Fan DEF | Status fan forced operation | 1 Bit | 1.1 switch | CRT |
| 158 | NULL | NULL | 1 Bit | ||
| 159 | NULL | NULL | 1 Bit | ||
| 160 | NULL | NULL | 1 Bit | ||
| 161 | Fan DEF | Limitation 1 | 1 Bit | 1.3 enable | CRWT |
| 161 | Floor heating E | Actual temperature | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 162 | Fan DEF | Limitation 2 | 1 Bit | 1.3 enable | CRWT |
| 162 | Floor heating E | Actual temp. error signal | 1 Bit | 1.5 alarm | CRT |
| 163 | Fan DEF | Limitation 3 | 1 Bit | 1.3 enable | CRWT |
| 163 | Floor heating E | Normal-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 164 | Fan DEF | Limitation 4 | 1 Bit | 1.3 enable | CRWT |
| 164 | Floor heating E | Day-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 165 | Floor heating E | Night-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 166 | Floor heating E | Away-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 167 | Floor heating E | Preset 1 Temp. for timer mode | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 168 | Floor heating E | Time of day for preset 1 | 3 Bytes | 10.1 time of day | CRWTU |
| 169 | Floor heating E | Start/Stop heating for preset1 | 1 Bit | 1.10 start/stop | CRWT |
| 170 | Floor heating E | Preset 2 Temp. for timer mode | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 171 | Compressor 1 & 2 | Automatic control (1-ON,0=OFF) | 1 Bit | 1.1 switch | CW |
| 171 | Floor heating E | Time of day for preset 2 | 3 Bytes | 10.1 time of day | CRWTU |
| 172 | Compressor 1 | Direct control (1-ON,0=OFF) | 1 Bit | 1.1 switch | CW |
| 172 | Floor heating E | Start/Stop heating for preset2 | 1 Bit | 1.10 start/stop | CRWT |
| 173 | Compressor 2 | Direct control (1-ON,0=OFF) | 1 Bit | 1.1 switch | CW |
| 173 | Floor heating E | Preset 3 Temp. for timer mode | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 174 | Floor heating E | Time of day for preset 3 | 3 Bytes | 10.1 time of day | CRWTU |
| 175 | Floor heating E | Start/Stop heating for preset3 | 1 Bit | 1.10 start/stop | CRWT |
| 176 | Compressor 1 | Status (1-OFF,0-ON) | 1 Bit | 1.1 switch | CRT |
| 176 | Floor heating E | Floor heating(1-ON,0-OFF) | 1 Bit | 1.1 switch | CW |
| 176 | Floor heating E | Floor heating(1-ON,0-OFF) | 1 Bit | 1.1 switch | CRWTU |
| 177 | Compressor 2 | Status (1-OFF,0-ON) | 1 Bit | 1.1 switch | CRT |
| 177 | Floor heating E | ON CMD for Normal-mode | 1 Bit | 1.1 switch | CRWTU |
| 178 | Compressor 1 &2 | Automatic Status (1-OFF,0-ON) | 1 Bit | 1.1 switch | CRT |
| 178 | Floor heating E | ON CMD for Day-mode | 1 Bit | 1.1 switch | CRWTU |
| 179 | Floor heating E | ON CMD for Night-mode | 1 Bit | 1.1 switch | CRWTU |
| 180 | Floor heating E | ON CMD for Away-mode | 1 Bit | 1.1 switch | CRWTU |
| 181 | HVAC controlling status | Status of control (byte) | 1 Byte | 20.105 HVAC control mode | CRT |
| 181 | Floor heating E | ON CMD for Timer-mode | 1 Bit | 1.1 switch | CRWTU |
| 182 | HVAC controlling status | Status of heat | 1 Bit | 1.3 enable | CRT |
| 182 | Floor heating E | Status valve position | 1 Bit | 1.1 switch | CRT |
| 183 | HVAC controlling status | Status of cool | 1 Bit | 1.3 enable | CRT |
| 183 | Floor heating E | Trigger valve purge | 1 Bit | 1.17 trigger | CW |
| 184 | HVAC controlling status | Status of fan only | 1 Bit | 1.3 enable | CRT |
| 184 | Floor heating E | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 185 | HVAC controlling status | Status of off | 1 Bit | 1.3 enable | CRT |
| 185 | Floor heating E | Instantaneous setpoint temp. | 2 Bytes | 9.1 temperature (°C) | CRT |
| 186 | HVAC controlling status | Status of automatic | 1 Bit | 1.3 enable | CRT |
| 186 | Floor heating E | Valve open/close directly | 1 Bit | 1.9 open/close | CW |
| 187 | NULL | NULL | 1 Bit | ||
| 188 | NULL | NULL | 1 Bit | ||
| 189 | NULL | NULL | 1 Bit | ||
| 190 | NULL | NULL | 1 Bit | ||
| 191 | HVAC operating status | Status of operation (byte) | 1 Byte | 20.102 HVAC mode | CRT |
| 191 | Floor heating F | Actual temperature | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 192 | HVAC operating status | Status of comfort | 1 Bit | 1.1 switch | CRT |
| 192 | Floor heating F | Actual temp. error signal | 1 Bit | 1.5 alarm | CRT |
| 193 | HVAC operating status | Status of standby | 1 Bit | 1.1 switch | CRT |
| 193 | Floor heating F | Normal-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 194 | HVAC operating status | Status of economy | 1 Bit | 1.1 switch | CRT |
| 194 | Floor heating F | Day-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 195 | HVAC operating status | Status of protection | 1 Bit | 1.1 switch | CRT |
| 195 | Floor heating F | Night-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 196 | Floor heating F | Away-mode setpoint Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 197 | Floor heating F | Preset 1 Temp. for timer mode | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 198 | Floor heating F | Time of day for preset 1 | 3 Bytes | 10.1 time of day | CRWTU |
| 199 | Floor heating F | Start/Stop heating for preset1 | 1 Bit | 1.10 start/stop | CRWT |
| 200 | Floor heating F | Preset 2 Temp. for timer mode | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 201 | HVAC status | Status of HVAC (byte) | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 201 | Floor heating F | Time of day for preset 2 | 3 Bytes | 10.1 time of day | CRWTU |
| 202 | Floor heating F | Start/Stop heating for preset2 | 1 Bit | 1.10 start/stop | CRWT |
| 203 | Floor heating F | Preset 3 Temp. for timer mode | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 204 | Floor heating F | Time of day for preset 3 | 3 Bytes | 10.1 time of day | CRWTU |
| 205 | Floor heating F | Start/Stop heating for preset3 | 1 Bit | 1.10 start/stop | CRWT |
| 206 | Floor heating F | Floor heating(1-ON,0-OFF) | 1 Bit | 1.1 switch | CW |
| 206 | Floor heating F | Floor heating(1-ON,0-OFF) | 1 Bit | 1.1 switch | CRWTU |
| 207 | Floor heating F | ON CMD for Normal-mode | 1 Bit | 1.1 switch | CRWTU |
| 208 | Floor heating F | ON CMD for Day-mode | 1 Bit | 1.1 switch | CRWTU |
| 209 | Floor heating F | ON CMD for Night-mode | 1 Bit | 1.1 switch | CRWTU |
| 210 | Floor heating F | ON CMD for Away-mode | 1 Bit | 1.1 switch | CRWTU |
| 211 | Floor heating F | ON CMD for Timer-mode | 1 Bit | 1.1 switch | CRWTU |
| 212 | Floor heating F | Status valve position | 1 Bit | 1.1 switch | CRT |
| 213 | Floor heating F | Trigger valve purge | 1 Bit | 1.17 trigger | CW |
| 214 | Floor heating F | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 215 | Floor heating F | Instantaneous setpoint temp. | 2 Bytes | 9.1 temperature (°C) | CRT |
| 216 | Floor heating F | Valve open/close directly | 1 Bit | 1.9 open/close | CW |
| 217 | Floor heating A | Status of Floor heating | 1 Bit | 1.1 switch | CRT |
| 217 | NULL | NULL | 1 Bit | ||
| 218 | Floor heating B | Status of Floor heating | 1 Bit | 1.1 switch | CRT |
| 218 | NULL | NULL | 1 Bit | ||
| 219 | Floor heating C | Status of Floor heating | 1 Bit | 1.1 switch | CRT |
| 219 | NULL | NULL | 1 Bit | ||
| 220 | Floor heating D | Status of Floor heating | 1 Bit | 1.1 switch | CRT |
| 220 | NULL | NULL | 1 Bit | ||
| 221 | Floor heating E | Status of Floor heating | 1 Bit | 1.1 switch | CRT |
| 221 | NULL | NULL | 1 Bit | ||
| 222 | Floor heating F | Status of Floor heating | 1 Bit | 1.1 switch | CRT |
| 222 | NULL | NULL | 1 Bit | ||
| 223 | NULL | NULL | 1 Bit | ||
| 224 | NULL | NULL | 1 Bit | ||
| 225 | NULL | NULL | 1 Bit | ||
| 226 | NULL | NULL | 1 Bit | ||
| 227 | NULL | NULL | 1 Bit | ||
| 228 | NULL | NULL | 1 Bit | ||
| 229 | NULL | NULL | 1 Bit | ||
| 230 | NULL | NULL | 1 Bit | ||
| 231 | HVAC Energy saving function | Trigger | 1 Bit | 1.17 trigger | CW |
| 232 | HVAC Energy saving function | Change delay time | 2 Bytes | 8.6 time lag (min) | CW |
| 233 | HVAC Energy saving function | Change saving mode | 1 Byte | 20.102 HVAC mode | CW |
| 234 | General | Status system ON/OFF | 1 Bit | 1.1 switch | CRT |
| 235 | HAVC Channel F | F Channel output | 1 Bit | 1.1 switch | CW |
| 236 | HAVC Channel F | F Switch status | 1 Bit | 1.1 switch | CRT |
Parameters (272)
| Parameter | Type | Default |
|---|---|---|
| NULL | list | False |
| System power-on delay[2..100s] | unsignedInt 2…100 | 2 |
| Heartbeat telegram | list | Disable |
| Telegram send interval[1..65535s] | unsignedInt 1…65535 | 10 |
| Control mode selection | list | HVAC |
| Enable active control | list | Enable |
| HVAC pipe system | list | 2 pipe system |
| ->Supported function | list | Heating |
| Heating channel was off,delay off fan (0..255s) | unsignedInt 0…255 | 0 |
| Cooling channel was off,delay off fan (0..255s) | unsignedInt 0…255 | 0 |
| Heating/cooling channel was off,delay off fan (0..255s) | unsignedInt 0…255 | 0 |
| Fan was off,off heating channel | list | Disable |
| Fan was off,off cooling channel | list | Disable |
| Fan was off,off heating/cooling channel | list | Disable |
| System ON/OFF on bus voltage recovery | list | OFF |
| Enable fan ABC | list | Enable |
| Enable fan DEF | list | Enable |
| Enable D as switch actuator | list | Disable |
| Enable E as switch actuator | list | Disable |
| Enable F as switch actuator | list | Disable |
| Enable channel A | list | Active control |
| Enable channel B | list | Disable |
| Enable channel C | list | Disable |
| Enable channel D | list | Disable |
| Enable channel E | list | Disable |
| Enable channel F | list | Disable |
| Enbale slave clock | list | Disable |
| Enbale reduce pressure when all channel'valve OFF | list | Disable |
| ->Reduce pressure check interval[1..65535s] | unsignedInt 1…65535 | 600 |
| ->Reduce pressure valve open interval[1..100s] | unsignedInt 1…100 | 20 |
| Switch state on bus voltage failure | list | Unchanged |
| Switch state on bus voltage recovery | list | Recovery |
| Object value for switching ON | list | '0' |
| Enable 1bit object"Status switch" | list | Disable |
| ->Send object value | list | Only after change |
| ->Object value with valve ON | list | '1' |
| Time function | list | Disable |
| -->Delay for switching ON:(0..255 Min) | unsignedInt 0…255 | 0 |
| -->Delay for switching ON:(0..59 Sec) | unsignedInt 0…59 | 0 |
| -->Delay for switching OFF:(0..255 Min) | unsignedInt 0…255 | 0 |
| -->Delay for switching OFF:(0..59 Sec) | unsignedInt 0…59 | 0 |
| Local temperature sensor correction value[-10..10C] | list | 0.0 |
| Local temperature sensor serial number[0..255] | unsignedInt 0…255 | 100 |
| Local temperature measuring interval[1..100min] | unsignedInt 1…100 | 2 |
| Enable cyclic send local temperature | list | Disable |
| ->Local temperature cyclic sending | list | Always response |
| ->Period for cyclic sending[1..255s] | unsignedInt 1…255 | 2 |
| Enable local ultra temperature alarm | list | Disable |
| ->Upper threshold temperature[30..100C] | unsignedInt 30…100 | 40 |
| ->Lower threshold temperature[-10..10C] | list | 0C |
| ->Alarm send interval[1..100s] | unsignedInt 1…100 | 1 |
| Enable monitoring local sensor | list | Disable |
| ->Sending period of local sensor error signal[2..100s] | unsignedInt 2…100 | 2 |
| ->Cycles of sending error signal[1..255,0-unlimited] | unsignedInt 0…255 | 1 |
| Source of operating temperature | list | Local sensor(0<count<=6) |
| ->Temperature correction value[-10..10C] | list | 0.0 |
| Enable send actual temperature | list | Disable |
| ->Sending period of actual temperture[1..255s] | unsignedInt 1…255 | 30 |
| Temperature1 sensor serial number[0..255] | unsignedInt 0…255 | 100 |
| ->Temperature1 correction value[-10..10C] | list | 0.0 |
| Enable send actual temperature1 | list | Disable |
| ->Sending period of actual temperture1[1..255s] | unsignedInt 1…255 | 30 |
| Enable temperature2 | list | Disable |
| Temperature2 sensor serial number[0..255] | unsignedInt 0…255 | 100 |
| ->Temperature2 correction value[-10..10C] | list | 0.0 |
| Enable send actual temperature2 | list | Disable |
| ->Sending period of actual temperture2[1..255s] | unsignedInt 1…255 | 30 |
| Enable temperature3 | list | Disable |
| Temperature3 sensor serial number[0..255] | unsignedInt 0…255 | 100 |
| ->Temperature3 correction value[-10..10C] | list | 0.0 |
| Enable send actual temperature3 | list | Disable |
| ->Sending period of actual temperture3[1..255s] | unsignedInt 1…255 | 30 |
| Enable temperature4 | list | Disable |
| Temperature4 sensor serial number[0..255] | unsignedInt 0…255 | 100 |
| ->Temperature4 correction value[-10..10C] | list | 0.0 |
| Enable send actual temperature4 | list | Disable |
| ->Sending period of actual temperture4[1..255s] | unsignedInt 1…255 | 30 |
| Enable monitoring EIB temperature | list | Disable |
| ->Monitoring period of EIB temperture[2..100min] | unsignedInt 2…100 | 2 |
| -> Number of times sending error signal[1..255,0-unlimited] | unsignedInt 0…255 | 1 |
| Base setpoint temperature[10..35C] | unsignedInt 10…35 | 25 |
| Power on status | list | Comfort mode |
| Conrtol mode at power on | list | Unchanged |
| Energy saving function | list | Disable |
| -->Delay time (1..65535 min) | unsignedInt 1…65535 | 60 |
| -->Change delay time via bus | list | No |
| -->Trigger mode to | list | Economy mode |
| -->Change mode via bus | list | No |
| Heating mode actived object value | list | '1' |
| Fan only mode actived object value | list | '1' |
| Turn off mode actived object value | list | '1' |
| Comfort mode actived object value | list | '1' |
| Reduced heating in standby mode[0..10C] | unsignedInt 0…10 | 2 |
| Standby mode actived object value | list | '1' |
| Reduced heating during economy mode[0..10C] | unsignedInt 0…10 | 4 |
| Economy mode actived object value | list | '1' |
| Temperature threshold in frost protection mode[2..10C] | unsignedInt 2…10 | 7 |
| Protect mode actived object value | list | '1' |
| Limitation for maximum setpoint heating[5..45C] | unsignedInt 5…45 | 35 |
| Automatically switch to building protection mode | list | Enable |
| PI speed for fan | list | Medium |
| Cooling mode actived object value | list | '1' |
| Increased cooling in standby mode[0..10C] | unsignedInt 0…10 | 2 |
| Increased cooling during economy mode[0..10C] | unsignedInt 0…10 | 4 |
| Temperature threshold in heat protection mode[35..40C] | unsignedInt 35…40 | 40 |
| Limitation for minimum setpoint cooling[5..45C] | unsignedInt 5…45 | 15 |
| Insensitive zone for toggling heating and cooling[0..10'C] | list | 1C |
| Automatic mode actived object value | list | '1' |
| Enable 1bit object"HVAC controlling status" | list | Disable |
| ->Send object range | list | Only actived status object |
| Enable 1byte object"HVAC controlling status" | list | Disable |
| Enable 1bit object"HVAC operating status" | list | Disable |
| Enable 1byte object"HVAC operating status" | list | Disable |
| Enable 1byte object"HVAC status (byte)" | list | Disable |
| HVAC system | list | 1 Control value/2-pipe |
| ->Toggle object configuration | list | '0'-Cool,'1'-Heat |
| ->Toggle object configuration | list | '0'-B,'1'-A |
| Enable monitoring control value | list | Disable |
| ->Monitoring interval[2..100min] | unsignedInt 2…100 | 2 |
| ->Send object value'Control value error signal' | list | Only after change |
| ->Set control value during fault | list | Disable |
| ->Control value default[0..100%] | unsignedInt 0…100 | 50 |
| Enable set default control value after system restart working | list | Disable |
| -->Default control value[0..100%] | unsignedInt 0…100 | 0 |
| Heating and cooling channels are mutually exclusive | list | Enable |
| Types of control | list | Two-step control(ON/OFF) |
| ->PI speed for Valve heating | list | Medium |
| ->PWM cycle time[1..30min] | unsignedInt 1…30 | 1 |
| ->Minimum duty | list | 0% |
| Valve type | list | Normally(de-energized closed) |
| Reaction on bus voltage failure | list | Opened |
| Enable valve purge | list | Disable |
| ->Period of valve purge[1..255min] | unsignedInt 1…255 | 1 |
| ->Automatic valve purge | list | NO |
| Enable 1bit object"Heating valve status" | list | Disable |
| ->PI speed for Valve cooling | list | Medium |
| Enable 1bit object"Cooling valve status" | list | Disable |
| ->PI speed for Valve heating/cooling | list | Medium |
| Enable 1bit object"Heating/Cooling valve status" | list | Disable |
| Enable operate valve open/close directly | list | Disable |
| Fan speed range | list | 3-speed fan |
| Fan operation mode | list | Changeover switch |
| Fan speed on bus voltage failure | list | OFF |
| Fan speed on bus voltage recovery | list | Recovery |
| Fan switch ON delay[0..255s] | unsignedInt 0…255 | 0 |
| Fan switch OFF delay[0..255s] | unsignedInt 0…255 | 0 |
| Changeover delay between speeds [1..10s] | list | 1s |
| Minimum duration in fan speed[1..65535s] | unsignedInt 1…65535 | 2 |
| Start-up behavior | list | Disable |
| ->Start-up speed of fan | list | Start at speed 2 |
| ->Duration in start-up speed[2..100s] | unsignedInt 2…100 | 2 |
| ->Start-up speed of fan | list | Start at speed 3 |
| Enable 1bit object"Forced operation" | list | Disable |
| ->Forced operation correspond to value | list | '1' |
| ->Reaction on forced operation | list | OFF |
| Enable automatic control | list | Disable |
| Enable direct control | list | Enable |
| Enable 1byte object"Status fan speed" | list | Disable |
| ->Meaning | list | Current speed |
| ->Fan speed-1 value[1..255] | unsignedInt 1…255 | 255 |
| Enable 1bit object"Status fan ON/OFF" | list | Disable |
| Enable 1bit object"Status fan speed x" | list | Disable |
| ->Object sending range | list | Only actived status object |
| ->Fan speed-2 value[1..255] | unsignedInt 1…255 | 255 |
| ->Fan speed-3 value[1..255] | unsignedInt 1…255 | 255 |
| Fan automatic control activated by object value | list | '1' |
| Wind speed 0 operating state | list | OFF |
| Threshold value speed 0<->speed 1 [1..100%] | unsignedInt 1…100 | 30 |
| Threshold hysteresis value[0..10%] | unsignedInt 0…10 | 5 |
| Enable 1 bit object"Status fan speed automatic" | list | Disable |
| Enable limitations | list | Disable |
| ->Speed limitation 1 | list | Unchanged |
| ->Speed limitation 2 | list | Unchanged |
| ->Speed limitation 3 | list | Unchanged |
| ->Speed limitation 4 | list | Unchanged |
| Threshold value speed 1<->speed 2 [1..100%] | unsignedInt 1…100 | 60 |
| Threshold value speed 2<->speed 3 [1..100%] | unsignedInt 1…100 | 90 |
| Enable 1bit object"Fan speed x" | list | Enable |
| Enable 1byte object"Fan speed switch" | list | Disable |
| ->Fan control encoded mode | list | Encoded by 1 byte percent value 0-100% |
| ->Fan speed-1 value[0..255] | unsignedInt 0…255 | 255 |
| Enable 1bit object"Fan speed up/down" | list | Disable |
| ->Fan speed-2 value[0..255] | unsignedInt 0…255 | 255 |
| ->Fan speed-3 value[0..255] | unsignedInt 0…255 | 255 |
| Source of operating temperature | list | Local sensor(0<count<=3) |
| Temperature sensor count for fan ABC | list | 1 |
| ->NO.1 sensor serial number[0..255] | unsignedInt 0…255 | 30 |
| ->NO.2 sensor serial number[0..255] | unsignedInt 0…255 | 60 |
| ->NO.3 sensor serial number[0..255] | unsignedInt 0…255 | 90 |
| Base setpoint temperature for fan ABC[10..35C] | unsignedInt 10…35 | 25 |
| PI speed for fan ABC | list | Medium |
| Temperature sensor count for fan DEF | list | 1 |
| ->NO.1 sensor serial number[0..255] | unsignedInt 0…255 | 130 |
| ->NO.2 sensor serial number[0..255] | unsignedInt 0…255 | 160 |
| ->NO.3 sensor serial number[0..255] | unsignedInt 0…255 | 190 |
| Base setpoint temperature for fan DEF[10..35C] | unsignedInt 10…35 | 25 |
| PI speed for fan DEF | list | Medium |
| Number of control value for fan ABC | list | 1 |
| ->Control value selected by | list | Largest |
| Number of control value for fan DEF | list | 1 |
| ->Control value default[0..100%] | unsignedInt 0…100 | 10 |
| Fan switch on delay[0..255s] | unsignedInt 0…255 | 0 |
| Fan switch off delay[0..255s] | unsignedInt 0…255 | 0 |
| ->Forced operation on object value | list | '1' |
| Threshold value OFF<->speed 1 [1..100%] | unsignedInt 1…100 | 30 |
| Statistic for ON switching time | list | Disable |
| ->Alarm when time out[1..65535hours,0-invalid] | unsignedInt 0…65535 | 1 |
| ->Alarm send interval[1..255s] | unsignedInt 1…255 | 1 |
| Enable staircase lighting | list | Disable |
| ->Staircase lighting control type | list | ON with 1,OFF with 0 |
| ->Externd staircase lighting time | list | Disable |
| ->Time for OFF[0..255min] | unsignedInt 0…255 | 0 |
| ->Time for OFF[0..59s] | unsignedInt 0…59 | 2 |
| ->Waring staircase lighting[ON->OFF->ON] | list | Disable |
| ->Waring before end of time[2..50s] | unsignedInt 2…50 | 3 |
| ->Duration time for waring[2..10s] | unsignedInt 2…10 | 2 |
| Temperature sensor count | list | 1 |
| PI speed for control | list | Medium |
| Number of control value for compressor 1 | list | 1 |
| Motor status on bus voltage failure | list | Unchanged |
| Motor status on bus voltage recovery | list | Recovery |
| Motor protection time[2..100min] | unsignedInt 2…100 | 2 |
| Enable 1bit object"Motor 1 ON/OFF" | list | Disable |
| Enable 1bit object"Motor 2 ON/OFF" | list | Disable |
| Enable motor automatic control | list | Disable |
| Threshold value OFF<->ON[1..100%] | unsignedInt 1…100 | 30 |
| Enable coordinate control | list | Enable |
| ->Threshold value for both working [1..100%] | unsignedInt 1…100 | 40 |
| Enable economize operational life span | list | Disable |
| ->Working time for compressor 1[2..255min] | unsignedInt 2…255 | 20 |
| ->Working time for compressor 2[2..255min] | unsignedInt 2…255 | 20 |
| Enable 1bit object"Status motor 1 ON/OFF" | list | Disable |
| Enable 1bit object"Status motor 2 ON/OFF" | list | Disable |
| Source of operating temperature | list | Local sensor(0<count<=1) |
| ->Temperature sensor serial number[0..255] | unsignedInt 0…255 | 10 |
| Enable monitoring temperature | list | Disable |
| ->Monitoring period of actual temperture[2..100min] | unsignedInt 2…100 | 2 |
| The operation mode after bus voltage recovery | list | Normal |
| Normal mode setpoint temperature[5..120C] | unsignedInt 5…120 | 25 |
| Day mode setpoint temperature[5..120C] | unsignedInt 5…120 | 23 |
| Night mode setpoint temperature[5..120C] | unsignedInt 5…120 | 20 |
| Away mode setpoint temperature[5..120C] | unsignedInt 5…120 | 15 |
| Enable timer mode[Preset 1..Preset 3] | list | Disable |
| ->Preset 1 temperature[5..120C] | unsignedInt 5…120 | 25 |
| ->Start/Stop floor heating | list | Start |
| ->Start tine for hour[0..23h] | unsignedInt 0…23 | 0 |
| ->Start tine for munite[0..59min] | unsignedInt 0…59 | 15 |
| ->Preset 2 temperature[5..120C] | unsignedInt 5…120 | 23 |
| ->Preset 3 temperature[5..120C] | unsignedInt 5…120 | 20 |
| Normal mode is actived by object value | list | 1 |
| Day mode is actived by object value | list | 1 |
| Night mode is actived by object value | list | 1 |
| Away mode is actived by object value | list | 1 |
| Timer mode is actived by object value | list | 1 |
| ->PI speed for heating | list | Medium |
| ->Minimum heating duty | list | 0% |
| Reaction on bus voltage failure | list | Unchanged |
| Enable 1 bit object"Valve position status" | list | Disable |
| ->Object value with valve ON | list | 0 |
| ->Time of valve purge[1..255min] | unsignedInt 1…255 | 1 |
| Enable respond to reduce pressure | list | Disable |
| Enable monitoring control value A | list | Disable |
| ->Temperature sensor serial number[0..255] | unsignedInt 0…255 | 20 |
| Enable monitoring control value B | list | Disable |
| ->Temperature sensor serial number[0..255] | unsignedInt 0…255 | 30 |
| Enable monitoring control value C | list | Disable |
| ->Temperature sensor serial number[0..255] | unsignedInt 0…255 | 40 |
| Enable monitoring control value D | list | Disable |
| ->Temperature sensor serial number[0..255] | unsignedInt 0…255 | 50 |
| Enable monitoring control value E | list | Disable |
| ->Temperature sensor serial number[0..255] | unsignedInt 0…255 | 60 |
| Enable monitoring control value F | list | Disable |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| FCHC Actuator(V1.1) 1.1 latest | $2250 | C606 | 2026-11-25 | 212 KB | Download |
About this file
This is the official ETS product database for the HDL M/FCHC.4.1 (M/FCHC 1605 F002), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from HDL
- M/CBVRV.GW.1 M/CBVRVGW1905
- M/FCU01.10.1 M/FCU01 1206 F001
- MHVACMGW-KT.13 MHVACMGW 2508
- MHVACSGW-KT.13 MHVACSGW 2508
- M/AG40B.1 M/AG40B 1811 W006
- M/DA6.10.1 M/DA 1110 D005
- MDL64-KT.53 M/DALI 1410 2603
- M/DALI.1 M/DALI 1410 DL001
- MDL64-KT.53 M/DALI 1410 DL002
- M/DLP04.1-A2 M/DLP 1209 P001
- M/DM02.1 M/DM02C1902
- M/DM02.1 M/DM02C2604