Heating actuator 6 gang triac 230V AC TYF646T

Hager Electro · Order number TYF646T · Heating, Air Conditioning › Heating actuators

Download .knxprod TL646A V1.1 1.1 · 95 KB

Product

ManufacturerHager Electro
Product nameHeating actuator 6 gang triac 230V AC
Order numberTYF646T
HardwareHeizungsaktor 6 fach Triac 230V AC REG
MediumTwisted Pair
Bus current (mA)6
Rail mountedYes
Width (mm)70
RegistrationCertified
Languagesde-DE, en-US
Catalog entryM-0009_H-9.20.2F.2F.20TYF646T-1-O000A_HP-20A2-11-1255-O000A_CI-TYF646T-1
Fingerprint1255
SHA-25670577c3651f6f0fca2c253d79835527b0460f1c1c2eb7baafe99cceb8d0ea6f3
First seen2026-11-25
Markets69 markets

Application program: TL646A V1.1 1.1

Application number$20A2
Version1.1
Mask versionMV-0012 (1.2)
KNX Data SecureNo
Parameters454
Group objects82
Group objects (82)
NoNameFunctionSizeDPTFlags
0Object 11 ByteCWT
0Manipulated variable output 1Input1 BitCW
0Manipulated variable output 1Input1 ByteCW
1Object 21 ByteCWT
1Manipulated variable output 2Input1 BitCW
1Manipulated variable output 2Input1 ByteCW
2Object 31 ByteCWT
2Manipulated variable output 3Input1 BitCW
2Manipulated variable output 3Input1 ByteCW
3Object 41 ByteCWT
3Manipulated variable output 4Input1 BitCW
3Manipulated variable output 4Input1 ByteCW
4Object 51 ByteCWT
4Manipulated variable output 5Input1 BitCW
4Manipulated variable output 5Input1 ByteCW
5Object 61 ByteCWT
5Manipulated variable output 6Input1 BitCW
5Manipulated variable output 6Input1 ByteCW
6Object 71 ByteCWT
6Manipulated variable output 1Status1 ByteCR
6Manipulated variable output 1Status1 BitCR
6Manipulated variable output 1Status1 ByteCT
6Manipulated variable output 1Status1 BitCT
7Object 81 BitCWT
7Manipulated variable output 2Status1 BitCR
7Manipulated variable output 2Status1 ByteCR
7Manipulated variable output 2Status1 BitCT
7Manipulated variable output 2Status1 ByteCT
8Object 91 BitCWT
8Manipulated variable output 3Status1 BitCR
8Manipulated variable output 3Status1 ByteCR
8Manipulated variable output 3Status1 BitCT
8Manipulated variable output 3Status1 ByteCT
9Object 101 BitCWT
9Manipulated variable output 4Status1 BitCR
9Manipulated variable output 4Status1 ByteCR
9Manipulated variable output 4Status1 BitCT
9Manipulated variable output 4Status1 ByteCT
10Object 111 BitCWT
10Manipulated variable output 5Status1 BitCR
10Manipulated variable output 5Status1 ByteCR
10Manipulated variable output 5Status1 BitCT
10Manipulated variable output 5Status1 ByteCT
11Object 121 BitCWT
11Manipulated variable output 6Status1 BitCR
11Manipulated variable output 6Status1 ByteCR
11Manipulated variable output 6Status1 BitCT
11Manipulated variable output 6Status1 ByteCT
12Object 131 BitCWT
12Forced position output 1Input1 BitCW
13Object 141 BitCWT
13Forced position output 2Input1 BitCW
14Object 151 BitCWT
14Forced position output 3Input1 BitCW
15Object 161 BitCWT
15Forced position output 4Input1 BitCW
16Object 171 BitCWT
16Forced position output 5Input1 BitCW
17Object 181 BitCWT
17Forced position output 6Input1 BitCW
18Object 191 BitCWT
18Output 1Overload / short circuit1 BitCT
19Object 201 BitCWT
19Output 2Overload / short circuit1 BitCT
20Object 211 BitCWT
20Output 3Overload / short circuit1 BitCT
21Object 221 BitCWT
21Output 4Overload / short circuit1 BitCT
22Object 231 BitCWT
22Output 5Overload / short circuit1 BitCT
23Object 241 BitCWT
23Output 6Overload / short circuit1 BitCT
24Object 251 BitCWT
24Power failureAlarm message1 BitCT
25Object 261 BitCWT
25All valves are closedStatus valves1 BitCT
26Object 271 BitCWT
26Cyclical monitoring of manipulated variablesAlarm message1 BitCT
27Object 281 BitCWT
27Summer / winterSwitch over1 BitCW
28Object 291 ByteCWT
28Largest manipulated variable of all outputsMax. value1 ByteCT
Parameters (80)
ParameterTypeDefault
ObjektelistObject value at power failure = 0
Init_KurzschlussmeldungunsignedInt 0…2550
Valve protectionlistYES
Status object: All valves are closed?listdisabled
Polarity of object: All valves are closedlistObject value if all valves are closed = 0
Transmit status of manipulated variablelistNo status
Status_VentilstellungenlistAt modification
Summer/winter mode switch over ?listNO
Polarity of object: Summer/winter switch overlistSummer = 0 / winter = 1
Operating mode after commisioninglistWinter mode
Feedback of the largest manip. variable? (only 1 Byte values)listNO
Cycle time of the PWM periode (only 1 Byte values)list15 min (e.g. floor heating, several heatings)
Telegrammratenbegrenzung (Anzahl der Telegramme in 17 s)unsignedInt 0…12730
Monitoring of manipulated variable?listdisabled
Monitoring time at cyclical monitoring of manipulated variablelist11 min
Polarity of object: Cycl. monitoring of manip. variablelistObject value at lack of man. variable = 1
Alarm message at power failure?listNO
Polarity of object: Power failurelistObject value at power failure = 1
Manipulated variable at summer emergency modelist50%
Manipulated variable at emergency modelist50%
Manipulated variable at winter emergency modelist50%
Output 1:listOnly at bus voltage failure
Output 1:listOnly at bus voltage restore
Output 1:listNO
Output 1:listOnly at lack of cycl. manipulated variable
Output 1:listBus voltage restore + lack of cycl. man. variable
Output 1:listBus voltage failure + lack of cycl. man. variable
Output 1:listBus volt. fail./restore + lack of cycl. man. var.
Output 1:listAt bus voltage failure + restore
Output 2:listAt bus voltage failure + restore
Output 2:listNO
Output 2:listOnly at bus voltage restore
Output 2:listOnly at bus voltage failure
Output 2:listOnly at lack of cycl. manipulated variable
Output 2:listBus voltage restore + lack of cycl. man. variable
Output 2:listBus voltage failure + lack of cycl. man. variable
Output 2:listBus volt. fail./restore + lack of cycl. man. var.
Output 3:listNO
Output 3:listOnly at bus voltage restore
Output 3:listOnly at bus voltage failure
Output 3:listAt bus voltage failure + restore
Output 3:listOnly at lack of cycl. manipulated variable
Output 3:listBus voltage restore + lack of cycl. man. variable
Output 3:listBus volt. fail./restore + lack of cycl. man. var.
Output 3:listBus voltage failure + lack of cycl. man. variable
Output 4:listNO
Output 4:listOnly at bus voltage restore
Output 4:listOnly at bus voltage failure
Output 4:listAt bus voltage failure + restore
Output 4:listOnly at lack of cycl. manipulated variable
Output 4:listBus voltage restore + lack of cycl. man. variable
Output 4:listBus volt. fail./restore + lack of cycl. man. var.
Output 4:listBus voltage failure + lack of cycl. man. variable
Output 5:listBus voltage restore + lack of cycl. man. variable
Output 5:listOnly at lack of cycl. manipulated variable
Output 5:listBus volt. fail./restore + lack of cycl. man. var.
Output 5:listBus voltage failure + lack of cycl. man. variable
Output 5:listNO
Output 5:listOnly at bus voltage restore
Output 5:listOnly at bus voltage failure
Output 5:listAt bus voltage failure + restore
Output 6:listBus voltage restore + lack of cycl. man. variable
Output 6:listOnly at lack of cycl. manipulated variable
Output 6:listBus volt. fail./restore + lack of cycl. man. var.
Output 6:listBus voltage failure + lack of cycl. man. variable
Output 6:listNO
Output 6:listOnly at bus voltage restore
Output 6:listOnly at bus voltage failure
Output 6:listAt bus voltage failure + restore
Mode of operation of valve/valve drive combinationlistCurrent-free closed
Type of manipulated variablelistSwitching (1 Bit)
Cycl. monitoring of manipulated variablelistdisabled
Forced position?listdisabled
Manipulated variable at summer forced positionlist40%
Manipulated variable at forced positionlist40%
Manipulated variable at winter forced positionlist40%
Behaviour after bus voltage failurelistMan. variable of emergency mode
Behaviour after bus voltage returnlistValve closes
Object: Overload / short circuit?listdisabled
Polarity of object: Overload/short circuitlistObject value at overload / short circuit = 0

Version history

ApplicationApp noFingerprintFirst seenSizeFile
TL646A V1.1 1.1 latest$20A212552026-11-2595 KBDownload

About this file

This is the official ETS product database for the Hager Electro Heating actuator 6 gang triac 230V AC (TYF646T), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.