| Hardware | list | 000A00000016 |
| Downloaderkennung | list | download took place |
| Müll | list | disabled |
| Objekte | list | disabled |
| Number of fan coil channels | list | 1 fan coil channel (maximum of 6 fan levels) |
| Type of fan coil system | list | 2-pipe only heating |
| Type of fan coil system
Channel 1 | list | 2-pipe only heating |
| Art_FanCoil_Download_Kanal1 | list | 2-conductor system only heating (mode 1) |
| Ventilkonfig_Download_Kanal1 | list | common valve for h/c (2-conductor) |
| Type of fan coil system
Channel 2 | list | 2-pipe only heating |
| Art_FanCoil_Download_Kanal2 | list | 2-conductor system only heating (mode 1) |
| Ventilkonfig_Download_Kanal2 | list | common valve for h/c (2-conductor) |
| Verzögerung nach Busspannungswiederkehr
Tage (0...7) | unsignedInt 0…7 | 0 |
| Verzögerung nach Busspannungswiederkehr
Stunden (0...23) | unsignedInt 0…23 | 0 |
| Delay after bus voltage return
Minutes (0...59) | unsignedInt 0…59 | 0 |
| Seconds (0...59) | unsignedInt 0…59 | 17 |
| Verzögerung nach Busspannungswiederkehr
Millisekunden (0...9 * 100 ms) | unsignedInt 0…9 | 0 |
| Zeit für zykl. Senden der Rückmeldungen
Tage (0...7) | unsignedInt 0…7 | 0 |
| Time for cycl. transm. of the feedback telegrams
Hours (0...23) | unsignedInt 0…23 | 0 |
| Minutes (0...59) | unsignedInt 0…59 | 2 |
| Zeit für zykl. Senden der Rückmeldungen
Sekunden (0...59) | unsignedInt 0…59 | 0 |
| Zeit für zykl. Senden der Rückmeldungen
Millisekunden (0...9 * 100 ms) | unsignedInt 0…9 | 0 |
| Behaviour after ETS programming | list | switch off all valve & fan outputs |
| Behaviour in case of bus voltage failure | list | switch off all valve & fan outputs |
| Behaviour after bus or
mains voltage return | list | switch off all valve & fan outputs |
| Read request to
"Heating/cooling change-over" object? | list | no |
| Verzögerungszeit für Leseanforderung
Tage (0...7) | unsignedInt 0…7 | 0 |
| Verzögerungszeit für Leseanforderung
Stunden (0...23) | unsignedInt 0…23 | 0 |
| Verzögerungszeit für Leseanforderung
Minuten (0...59) | unsignedInt 0…59 | 0 |
| Delay time for read request
Seconds (0...59) | unsignedInt 0…59 | 30 |
| Millisekunden (0...9 * 100 ms) | unsignedInt 0…9 | 0 |
| Valve protection | list | deactivated |
| Fan protection | list | deactivated |
| Number of fan levels | list | 6 |
| Number of fan levels | list | 3 |
| Controlling the fan levels | list | only one fan output switches (change-over princip) |
| Command value lower limit for
fan level 1 (1...100 %) | unsignedInt 1…100 | 5 |
| Command value lower limit for
fan level 2 (1...100 %) | unsignedInt 1…100 | 20 |
| Untergrenze Stellgröße für
Lüfterstufe 2 (1...100 %) | unsignedInt 0…127 | 127 |
| Command value lower limit for
fan level 3 (1...100 %) | unsignedInt 1…100 | 40 |
| Untergrenze Stellgröße für
Lüfterstufe 3 (1...100 %) | unsignedInt 0…127 | 127 |
| Command value lower limit for
fan level 4 (1...100 %) | unsignedInt 1…100 | 60 |
| Untergrenze Stellgröße für
Lüfterstufe 4 (1...100 %) | unsignedInt 0…127 | 127 |
| Command value lower limit for
fan level 5 (1...100 %) | unsignedInt 1…100 | 80 |
| Untergrenze Stellgröße für
Lüfterstufe 5 (1...100 %) | unsignedInt 0…127 | 127 |
| Command value lower limit for
fan level 6 (1...100 %) | unsignedInt 1…100 | 95 |
| Untergrenze Stellgröße für
Lüfterstufe 6 (1...100 %) | unsignedInt 0…127 | 127 |
| Hysteresis for level change-over
(0...20 %; 0 = hysteresis deactivated) | unsignedInt 0…20 | 10 |
| Fan level when the fan
is switched on | list | fan level 1 |
| Fan level when the fan
is switched on | list | as specified by command value lower limit |
| Switch on to switch-on level | list | 2 |
| Verweildauer für Einschaltstufe
Tage (0...7) | unsignedInt 0…7 | 0 |
| Verweildauer für Einschaltstufe
Stunden (0...23) | unsignedInt 0…23 | 0 |
| Verweildauer für Einschaltstufe
Minuten (0...59) | unsignedInt 0…59 | 0 |
| Dwell time for switch-on level
Seconds (1...59) | unsignedInt 1…59 | 15 |
| Einschaltverzögerung Lüfter bei Heizen
Tage (0...7) | unsignedInt 0…7 | 0 |
| Einschaltverzögerung Lüfter bei Heizen
Stunden (0...23) | unsignedInt 0…23 | 0 |
| Fan switch-on delay for heating
Minutes (0...59) | unsignedInt 0…59 | 0 |
| Seconds (0...59) | unsignedInt 0…59 | 30 |
| Einschaltverzögerung Lüfter bei Heizen
Millisekunden (0...9 * 100 ms) | unsignedInt 0…9 | 0 |
| Ausschaltverzögerung Lüfter bei Kühlen
Tage (0...7) | unsignedInt 0…7 | 0 |
| Ausschaltverzögerung Lüfter bei Kühlen
Stunden (0...23) | unsignedInt 0…23 | 0 |
| Fan switch-off delay for cooling
Minutes (0...59) | unsignedInt 0…59 | 0 |
| Ausschaltverzögerung Lüfter bei Kühlen
Millisekunden (0...9 * 100 ms) | unsignedInt 0…9 | 0 |
| Pause "AUS" bei Stufenumschaltung
Tage (0...7) | unsignedInt 0…7 | 0 |
| Verweildauer bei Stufenumschaltung
Tage (0...7) | unsignedInt 0…7 | 0 |
| Pause "AUS" bei Stufenumschaltung
Stunden (0...23) | unsignedInt 0…23 | 0 |
| Verweildauer bei Stufenumschaltung
Stunden (0...23) | unsignedInt 0…23 | 0 |
| Pause "AUS" bei Stufenumschaltung
Minuten (0...59) | unsignedInt 0…59 | 0 |
| Verweildauer bei Stufenumschaltung
Minuten (0...59) | unsignedInt 0…59 | 0 |
| Pause "OFF" for level change-over
Seconds (0...2) | unsignedInt 0…2 | 1 |
| Dwell time for level change-over
Seconds (0...2) | unsignedInt 0…2 | 1 |
| Milliseconds (1...9 * 100 ms) | unsignedInt 1…9 | 1 |
| Level limitation via object | list | disabled |
| Fan level with limitation | list | switch off fan |
| Fan level with limitation | list | 1 |
| Feedback for the active fan level | list | no |
| RM_Freigabe_Download | list | none |
| Type of feedback | list | fan levels via value |
| Feedback object "Fan coil active" | list | disabled |
| Time delay for feedback telegrams
after bus voltage return? | list | no |
| Time delay for feedback
"Fan coil active" after bus vltg ret.? | list | no |
| Time delay for feedback
"active fan lev" after bus vltg ret.? | list | no |
| Cyclical transmission of the feedback telegrams? | list | no (transmit only in the event of an update) |
| Cyclical transmission of the feedback
"Fan coil active"? | list | no (transmit only in the event of an update) |
| Cyclical transmission of the feedback
"active fan level"? | list | no (transmit only in the event of an update) |
| Request object for feedback
"active fan level" | list | disabled |
| Request object for feedback telegrams | list | disabled |
| Request object for feedback
"Fan coil active" | list | disabled |
| Manual fan control | list | disabled |
| Activation of manual
fan control | list | via object "Man. fan lev. active/inactive" |
| Fan level change-over in case of
manual specification via | list | switching direction object (1 bit) |
| Manual fan control only with
active heating? | list | no |
| Manual fan control only with
active cooling? | list | no |
| Manual fan control only with
active heating/cooling? | list | no |
| Activate manual fan control after bus
or mains vltg. return? | list | no |
| Cyclical monitoring of the command values | list | deactivated |
| Überwachungszeit
Tage (0...7) | unsignedInt 0…7 | 0 |
| Monitoring time
Hours (0...23) | unsignedInt 0…23 | 0 |
| Minutes (1...59) | unsignedInt 1…59 | 30 |
| Überwachungszeit
Sekunden (0...59) | unsignedInt 0…59 | 0 |
| Überwachungszeit
Millisekunden (0...9 * 100 ms) | unsignedInt 0…9 | 0 |
| Reaction at the end of the
monitoring time | list | switch off all valve & fan outputs |
| Fan level | list | 1 |
| Fault message at the end of the
monitoring time | list | disabled |
| Disabling function | list | deactivated |
| Polarity of the disabling object | list | 0 = enabled; 1 = disabled |
| Reaction at the beginning of the
disabling function | list | switch off all valve & fan outputs |
| Reaction at the end of the
disabling function | list | switch off all valve & fan outputs |
| Command value lower limit for
fan level 2 (1...100 %) | unsignedInt 1…100 | 30 |
| Command value lower limit for
fan level 3 (1...100 %) | unsignedInt 1…100 | 60 |
| Untergrenze Stellgröße für
Lüfterstufe 4 (1...100 %) | list | no |
| Untergrenze Stellgröße für
Lüfterstufe 5 (1...100 %) | list | no |
| Untergrenze Stellgröße für
Lüfterstufe 6 (1...100 %) | list | no |
| Manual control in case of bus voltage failure | list | enabled |
| Manual control during bus operation | list | enabled |
| Disabling function ? | list | no |
| Polarity of disabling object | list | 0 = enabled; 1 = disabled |
| Transmit status ? | list | no |
| Status object function and polarity | list | 0 = inactive; 1 = manual control active |
| Behaviour at the end of permanent
manual control during bus operation | list | no change |
| Bus control of the channels
during bus operation can be disabled ? | list | no |
| Output 1 | list | valve for heating |
| Output 1 | list | valve for cooling |
| Output 1 | list | combined valve for heating/cooling |
| Output 1 | list | Channel 1: valve for heating |
| Output 1 | list | Channel 1: valve for cooling |
| Output 1 | list | Channel 1: combined valve for heating/cooling |
| Output 2 | list | unused |
| Output 2 | list | valve for heating |
| Output 2 | list | Channel 1: fan level 1 |
| Output 3 | list | fan level 1 |
| Output 3 | list | Channel 1: fan level 2 |
| Output 3 | list | simple switching output |
| Output 4 | list | fan level 2 |
| Output 4 | list | simple switching output |
| Output 4 | list | Channel 1: fan level 3 |
| Output 5 | list | Channel 2: valve for heating |
| Output 5 | list | Channel 2: valve for cooling |
| Output 5 | list | Channel 2: combined valve for heating/cooling |
| Output 5 | list | fan level 3 |
| Output 5 | list | simple switching output |
| Output 6 | list | fan level 4 |
| Output 6 | list | simple switching output |
| Output 6 | list | Channel 2: fan level 1 |
| Output 7 | list | fan level 5 |
| Output 7 | list | simple switching output |
| Output 7 | list | Channel 2: fan level 2 |
| Output 8 | list | fan level 6 |
| Output 8 | list | simple switching output |
| Output 8 | list | Channel 2: fan level 3 |