KNX Database

KNX pulse gateway 3 channels TXE773

Hager Electro · Order number TXE773 · Meter › Pulse meter

Download .knxprod STXE773 1.0 · 113 KB

Product

ManufacturerHager Electro
Product nameKNX pulse gateway 3 channels
Order numberTXE773
HardwareTXE773
MediumTwisted Pair
Bus current (mA)8
Rail mountedNo
RegistrationRegistered · 2016-10-05
Languagesfr-FR, de-DE, en-US, es-ES, it-IT, nl-NL, pt-PT, nb-NO, sv-SE
Catalog entryM-0009_H-9.20.2F.2F.20TXE773-1_HP-E0C0-10-F08A_CI-TXE773-1
FingerprintF08A
SHA-256285d62a5ffed96eb4c5053f9e7e90e0446d83139ccf464265457dc125ce2d062
First seen2026-11-25
Markets69 markets

Application program: STXE773 1.0

Application number$E0C0
Version1.0
Mask versionMV-0701 (7.1)
KNX Data SecureNo
Minimum ETS version4.0
Parameters239
Group objects78
Group objects (78)
NoNameFunctionSizeDPTFlags
0Input 1Total energy timestamped14 BytesCRTU
1Input 1Partial energy timestamped14 BytesCRTU
2Input 1Total energy timestamped12 BytesCRTU
3Input 1Partial energy timestamped12 BytesCRTU
4Input 1Total volume timestamped12 BytesCRTU
5Input 1Partial volume timestamped12 BytesCRTU
6Input 1Power timestamped12 BytesCRTU
7Input 1Flow rate timestamped12 BytesCRTU
8Input 1Total energy6 BytesCRTU
9Input 1Partial energy6 BytesCRTU
10Input 1Total energy4 Bytes13.10 active energy (Wh)CRTU
11Input 1Partial energy4 Bytes13.10 active energy (Wh)CRTU
12Input 1Total volume4 Bytes14.76 volume (m³)CRTU
13Input 1Partial volume4 Bytes14.76 volume (m³)CRTU
14Input 1Power4 Bytes14.56 power (W)CRTU
15Input 1Flow rate4 Bytes14.77 volume flux (m³/s)CRTU
16Input 1Pulse1 Bit1.2 booleanCRTU
17Input 1Partial meter reset activation1 Bit1.15 resetCRW
18Input 1Dynamic mode activation1 Bit1.3 enableCRW
19Input 1Set total energy6 BytesCRW
20Input 1Set total energy4 Bytes13.10 active energy (Wh)CRW
21Input 1Set total volume4 Bytes14.76 volume (m³)CRW
22Input 1History request1 Bit1.10 start/stopCRW
23Input 2Total energy timestamped14 BytesCRTU
24Input 2Partial energy timestamped14 BytesCRTU
25Input 2Total energy timestamped12 BytesCRTU
26Input 2Partial energy timestamped12 BytesCRTU
27Input 2Total volume timestamped12 BytesCRTU
28Input 2Partial volume timestamped12 BytesCRTU
29Input 2Power timestamped12 BytesCRTU
30Input 2Flow rate timestamped12 BytesCRTU
31Input 2Total energy6 BytesCRTU
32Input 2Partial energy6 BytesCRTU
33Input 2Total energy4 Bytes13.10 active energy (Wh)CRTU
34Input 2Partial energy4 Bytes13.10 active energy (Wh)CRTU
35Input 2Total volume4 Bytes14.76 volume (m³)CRTU
36Input 2Partial volume4 Bytes14.76 volume (m³)CRTU
37Input 2Power4 Bytes14.56 power (W)CRTU
38Input 2Flow rate4 Bytes14.77 volume flux (m³/s)CRTU
39Input 2Pulse1 Bit1.2 booleanCRTU
40Input 2Partial meter reset activation1 Bit1.15 resetCRW
41Input 2Dynamic mode activation1 Bit1.3 enableCRW
42Input 2Set total energy6 BytesCRW
43Input 2Set total energy4 Bytes13.10 active energy (Wh)CRW
44Input 2Set total volume4 Bytes14.76 volume (m³)CRW
45Input 2History request1 Bit1.10 start/stopCRW
46Input 3Total energy timestamped14 BytesCRTU
47Input 3Partial energy timestamped14 BytesCRTU
48Input 3Total energy timestamped12 BytesCRTU
49Input 3Partial energy timestamped12 BytesCRTU
50Input 3Total volume timestamped12 BytesCRTU
51Input 3Partial volume timestamped12 BytesCRTU
52Input 3Power timestamped12 BytesCRTU
53Input 3Flow rate timestamped12 BytesCRTU
54Input 3Total energy6 BytesCRTU
55Input 3Partial energy6 BytesCRTU
56Input 3Total energy4 Bytes13.10 active energy (Wh)CRTU
57Input 3Partial energy4 Bytes13.10 active energy (Wh)CRTU
58Input 3Total volume4 Bytes14.76 volume (m³)CRTU
59Input 3Partial volume4 Bytes14.76 volume (m³)CRTU
60Input 3Power4 Bytes14.56 power (W)CRTU
61Input 3Flow rate4 Bytes14.77 volume flux (m³/s)CRTU
62Input 3Pulse1 Bit1.2 booleanCRTU
63Input 3Partial meter reset activation1 Bit1.15 resetCRW
64Input 3Dynamic mode activation1 Bit1.3 enableCRW
65Input 3Set total energy6 BytesCRW
66Input 3Set total energy4 Bytes13.10 active energy (Wh)CRW
67Input 3Set total volume4 Bytes14.76 volume (m³)CRW
68Input 3History request1 Bit1.10 start/stopCRW
69Date and timeDate3 Bytes11.1 dateCRW
70Date and timeTime3 Bytes10.1 time of dayCRW
71Date and timeDate and time8 Bytes19.1 date timeCRW
72Date and timeDate and time request1 Bit1.10 start/stopCRTU
73TariffCurrent tariff request1 Bit1.10 start/stopCRTU
74TariffCurrent tariff1 Byte5.6 tariff (0..255)CRW
75GeneralBattery status1 Bit1.11 stateCRTU
76GeneralBus power cut over 30 days1 Bit1.2 booleanCRTU
77GeneralDate and time of bus power cut/return8 Bytes19.1 date timeCRTU
Parameters (88)
ParameterTypeDefault
Meter typelistVolume
TimestamplistWithout
Volume unitlistLiter
Volume pulse value (l)float 0.1…10001
Volume pulse value (m3)float 0.0001…1000.001
Energy unitlistWh
Energy pulse value (Wh)unsignedInt 1…1000100
Energy pulse value (kWh)unsignedInt 1…1001
Emission on bus every x pulseunsignedInt 1…655351
Volume meter: preset value (l)float 0…21474836470
Volume meter: preset value (m3)float 0…21474836470
Total counter preset (m3)float 0…21474836470
Energy meter: preset value (Wh)unsignedInt 0…42949672950
Energy meter: preset value (kWh)unsignedInt 0…42949672950
Total counter preset (Wh)unsignedInt 0…42949672950
Energy meter: preset value tariff 0 (Wh)unsignedInt 0…42949672950
Energy meter: preset value tariff 0 (kWh)unsignedInt 0…42949672950
Total counter preset Tariff 0 (Wh)unsignedInt 0…42949672950
Energy meter: preset value tariff 1 (Wh)unsignedInt 0…42949672950
Energy meter: preset value tariff 1 (kWh)unsignedInt 0…42949672950
Total energy counter preset Tariff 1 (Wh)unsignedInt 0…42949672950
Energy meter: preset value tariff 2 (Wh)unsignedInt 0…42949672950
Energy meter: preset value tariff 2 (kWh)unsignedInt 0…42949672950
Total counter preset Tariff 2 (Wh)unsignedInt 0…42949672950
Energy meter: preset value tariff 3 (Wh)unsignedInt 0…42949672950
Energy meter: preset value tariff 3 (kWh)unsignedInt 0…42949672950
Total counter preset Tariff 3 (Wh)unsignedInt 0…42949672950
Energy meter: preset value tariff 4 (Wh)unsignedInt 0…42949672950
Energy meter: preset value tariff 4 (kWh)unsignedInt 0…42949672950
Total counter preset Tariff 4 (Wh)unsignedInt 0…42949672950
Energy meter: preset value tariff 5 (Wh)unsignedInt 0…42949672950
Energy meter: preset value tariff 5 (kWh)unsignedInt 0…42949672950
Total counter preset Tariff 5 (Wh)unsignedInt 0…42949672950
Energy meter: preset value tariff 6 (Wh)unsignedInt 0…42949672950
Energy meter: preset value tariff 6 (kWh)unsignedInt 0…42949672950
Total counter preset Tariff 6 (Wh)unsignedInt 0…42949672950
Energy meter: preset value tariff 7 (Wh)unsignedInt 0…42949672950
Energy meter: preset value tariff 7 (kWh)unsignedInt 0…42949672950
Total counter preset Tariff 7 (Wh)unsignedInt 0…42949672950
Energy meter: preset value tariff 8 (Wh)unsignedInt 0…42949672950
Energy meter: preset value tariff 8 (kWh)unsignedInt 0…42949672950
Total counter preset Tariff 8 (Wh)unsignedInt 0…42949672950
Energy meter: preset value tariff 9 (Wh)unsignedInt 0…42949672950
Energy meter: preset value tariff 9 (kWh)unsignedInt 0…42949672950
Total counter preset Tariff 9 (Wh)unsignedInt 0…42949672950
Energy meter: preset value tariff 10 (Wh)unsignedInt 0…42949672950
Energy meter: preset value tariff 10 (kWh)unsignedInt 0…42949672950
Total counter preset Tariff 10 (Wh)unsignedInt 0…42949672950
Total energy emission modelistOn change and periodically
Total volume emission modelistOn change and periodically
Emission total volume by variation of (l)float 0.1…214748364710
Emission total volume by variation of (m3)float 0.0001…21474836470.01
Total counter on change value (m3)float 0.0001…21474836470.01
Emission total energy by variation of (kWh)unsignedInt 1…42949672951
Emission total energy by variation of (Wh)unsignedInt 1…4294967295100
Total counter on change value (Wh)unsignedInt 1…4294967295100
Emission of total energy everylist2 min 30 s
Emission of total volume everylist2 min 30 s
Partial energy emission modelistOn change and periodically
Partial volume emission modelistOn change and periodically
Emission partial volume by variation of (m3)float 0.0001…21474836470.01
Partial counter On change value (m3)float 0.0001…21474836470.01
Emission partial energy by variation of (kWh)unsignedInt 1…42949672951
Emission partial energy by variation of (Wh)unsignedInt 1…4294967295100
Partial counter On change value (Wh)unsignedInt 1…4294967295100
Emission of partial energy everylist2 min 30 s
Emission of partial volume everylist2 min 30 s
Emission partial volume by variation of (l)float 0.1…214748364710
Flow rate emission modelistOn change and periodically
Power emission modelistOn change and periodically
Emission of flow rate by variation of (l/h)float 0.1…214748364710
Emission of flow rate by variation of (m3/h)float 0.0001…21474836470.01
Flow rate On Change Value (m3/s)float 2.5e-8…21474836470.000002777777777777778
Emission of power by variation of (W)float 1…2147483647500
Emission of power by variation of (kW)float 0.001…21474836471
Power On change value (W)float 1…2147483647500
Emission of flow rate everylist2 min 30 s
Emission of power everylist2 min 30 s
Dynamic mode durationlist15 min
Emission of flow rate (dynamic mode) by variation of (l/h)float 0.1…21474836475
Emission of flow rate (dynamic mode) by variation of (m3/h)float 0.0001…21474836470.005
Dynamic mode Flow rate On change value (m3/s)float 0…21474836470.000001388888888888889
Emission of power (dynamic mode) by variation of (W)float 1…214748364710
Emission of power (dynamic mode) by variation of (kW)float 0.001…21474836470.01
Dynamic mode Power On change value (W)float 0.0001…214748364710
Application software versiontext1.0.12
Version of translation filetext0.0.3
Dynamic mode Flow rate On change value (m3/h)float 0…21474836470.000001388888888888889

Version history

ApplicationApp noFingerprintFirst seenSizeFile
STXE773 1.0 latest$E0C0F08A2026-11-25113 KBDownload

About this file

This is the official ETS product database for the Hager Electro KNX pulse gateway 3 channels (TXE773), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.