| Operation and send delay after bus recovery [5..250] | unsignedInt 5…250 | 10 |
| Send cycle of "In operation" telegram [1..240,0=inactive] | unsignedInt 0…240 | 0 |
| Manual operation | unsignedInt 0…1 | 1 |
| Manual to automatic by | list | Only long press |
| Delay time [10..6000] | unsignedInt 10…6000 | 10 |
| Central control for switch function | unsignedInt 0…1 | 0 |
| Input interface | unsignedInt 0…1 | 0 |
| Input 1 | list | Temperature probe(NTC 10K) |
| Input 2 | list | Disable |
| When bus failure,Fan speed is | list | Unchange |
| When bus recovery,Fan speed is | list | Unchange |
| After downloading,Fan speed is | list | Off |
| Forced operation on object value | list | 1=Force/0=Cancel |
| Behaviour on forced operation | list | Unchange |
| Time mode for function On | list | Switch Delay |
| Delay time [1..65535] | unsignedInt 1…65535 | 10 |
| Minimum time [1..65535] | unsignedInt 1…65535 | 10 |
| Time mode for function Off | list | Switch Delay |
| Fan speeds on 2 limit | unsignedInt 0…1 | 0 |
| Fan operation mode | list | Changeover switch |
| Delay between fan speed switchover [50..5000] | unsignedInt 50…5000 | 500 |
| Object datatype of 1byte fan speed | list | Percentage (DPT_5.001) |
| Min.threshold value for Fan speed 1 | list | 33 |
| Min.threshold value for Fan speed 2 | list | 67 |
| Min.threshold value for Fan speed 3 | list | 100 |
| Min.threshold value for Fan speed 1 | unsignedInt 0…255 | 1 |
| Min.threshold value for Fan speed 2 | unsignedInt 1…255 | 2 |
| Min.threshold value for Fan speed 3 | unsignedInt 1…255 | 3 |
| Forced operation function | unsignedInt 0…1 | 0 |
| Limitation on forced operation | list | Unchange |
| Auto. operation function | unsignedInt 0…1 | 0 |
| Obj. "Switch speed x " 1bit function | unsignedInt 0…1 | 0 |
| Delay time for function Off [0..65535] | unsignedInt 0…65535 | 0 |
| Starting characteristic of fan | unsignedInt 0…1 | 1 |
| Switch On over fan speed | list | 1 |
| Minimum time in switch [1..65535] | unsignedInt 1…65535 | 10 |
| Auto.operation on object value | list | 1=Auto/0=Cancel |
| State of Auto.operation after startup | list | Cancel |
| Automatically enable auto.operation | unsignedInt 0…1 | 0 |
| Enable auto.operation after[10..6000] | unsignedInt 10…6000 | 100 |
| Min.threshold value Off<->speed 1 [0..255] | unsignedInt 0…255 | 80 |
| Min.threshold value speed 1<->speed 2 [1..255] | unsignedInt 1…255 | 150 |
| Min.threshold value speed 2<->speed 3 [1..255] | unsignedInt 1…255 | 200 |
| Hysteresis threshold value in +/-[0..50] | unsignedInt 0…50 | 10 |
| Minimum time in fan speed [0..65535] | unsignedInt 0…65535 | 10 |
| Controller from | list | External controller->1 control value |
| Select by | list | Control value with switching object |
| Monitoring control value | unsignedInt 0…1 | 1 |
| Monitoring period of control value
[10..65535] | unsignedInt 10…65535 | 120 |
| Reply mode of Obj."Control value fault" | list | Respond after change |
| Control value after fault occurs [0..100] | unsignedInt 0…100 | 0 |
| Reply mode of Obj. "Status Fan On/Off"(1bit) | list | Respond after change |
| Reply mode of Obj. "Status Automatic"(1bit) | list | Respond after change |
| Reply mode of Obj. "Status Fan speed x"(1bit) | list | Respond after change |
| Reply mode of Obj. "Status Fan speed"(1byte) | list | Respond after change |
| Status value for Fan speed 1 | list | 33 |
| Status value for Fan speed 2 | list | 67 |
| Status value for Fan speed 3 | list | 100 |
| Status value for Fan speed 1 | unsignedInt 1…255 | 1 |
| Status value for Fan speed 2 | unsignedInt 1…255 | 2 |
| Status value for Fan speed 3 | unsignedInt 1…255 | 3 |
| HVAC control mode | list | Heating and Cooling |
| Valve mode and drive interface | list | Disable |
| Observe reversing time | list | 400ms |
| If bus failure, valve position | list | Unchange |
| If bus recovery, valve position | list | Unchange |
| Valve control time 0%->100% [50..6000] | unsignedInt 50…6000 | 100 |
| Automatic adjust valve position | unsignedInt 0…1 | 0 |
| Number of valve control up to adjust [1..65535] | unsignedInt 1…65535 | 200 |
| Correct Valve characteristic curve | unsignedInt 0…1 | 0 |
| Min. controller value for closed valve [0..100] | unsignedInt 0…100 | 0 |
| Max. controller value for fully opened valve [0..100] | unsignedInt 0…100 | 100 |
| Lower valve position for opening [0..100] | unsignedInt 0…100 | 0 |
| Upper valve position for opening [0..100] | unsignedInt 0…100 | 100 |
| Reply mode for valve status | list | Respond after change |
| Object type of valve status | list | 1byte |
| Object value with valve position >0 | list | 1 |
| Valve type | list | Normal(de-energised closed) |
| PWM cycle time [10..6000] | unsignedInt 10…6000 | 120 |
| Valve purge function | unsignedInt 0…1 | 0 |
| Duration of valve purge time [1..255] | unsignedInt 1…255 | 10 |
| Automatic valve purge | unsignedInt 0…1 | 0 |
| Purge Cycle in weeks [1..12] | unsignedInt 1…12 | 1 |
| Reply mode for valve purge status(1bit) | list | Respond after change |
| "Disable heating" object function | unsignedInt 0…1 | 0 |
| Trigger object value | list | 0=Disable/1=Enable |
| "Disable cooling" object function | unsignedInt 0…1 | 0 |
| HVAC System | list | 4 pipes system |
| "Disable heating/cooling" object function | unsignedInt 0…1 | 0 |
| Number of control value | list | 2 control value |
| Monitoring period of control value
[10..65535] | unsignedInt 10…65535 | 60 |
| Fan type and drive interface | list | One level->Relay control(CH A) |
| Output voltage for fan speed 1 [1..20] | unsignedInt 1…20 | 5 |
| Output voltage for fan speed 2 [1..20] | unsignedInt 1…20 | 10 |
| Output voltage for fan speed 3 [1..20] | unsignedInt 1…20 | 15 |
| Output voltage for fan speed [1..20] | unsignedInt 1…20 | 5 |
| If fan drive interface does not use output A,B&C, they serve as switch outputs | list | |
| If fan drive interface does not use output B&C, they serve as switch outputs | list | |
| If fan drive interface does not use output C, it serves as switch output | list | |
| Behavior from fan off to on when the valve is starting from fully close to open | list | Switch on immediately |
| Delay time [30..450] | unsignedInt 3…450 | 30 |
| Limitation function | unsignedInt 0…1 | 0 |
| Fan with limitation 1 | list | Disable |
| Fan with limitation 2 | list | Disable |
| Fan with limitation 3 | list | Disable |
| Fan with limitation 4 | list | Disable |
| Min. output voltage for fan speed | list | 0 |
| Max. output voltage for fan speed | list | 10.0 |
| Switch On over fan speed | unsignedInt 1…100 | 30 |
| Fan speed for function On | unsignedInt 1…100 | 30 |
| Room temperature controller | unsignedInt 0…1 | 0 |
| Room temperature reference from | list | Local sensor(Input 1) |
| Period for request external sensor [0...255,0=inactive] | unsignedInt 0…255 | 10 |
| Combination ratio | list | 50% Local to 50% External |
| Send temperature when the result change by | list | 1.0 |
| Cyclically send temperature [0...255,0=inactive] | unsignedInt 0…255 | 0 |
| Control value after temp. error[0..100]
(if 2-point control, set value '0'=0, set value '>0'=1) | unsignedInt 0…100 | 0 |
| Room temperature control mode | list | Heating |
| Heating/Cooling switchover | list | Via object |
| Heating/Cooling status after download | list | Heating |
| Heating/Cooling status after voltage recovery | list | As before voltage failure |
| Room temperature control system | list | 4 pipes system |
| Operation mode | unsignedInt 0…1 | 0 |
| Initial setpoint temperature | list | 20.0 |
| Temperature error tip_setpoint/Max | unsignedInt 0…1 | 0 |
| Temperature error tip_setpoint/Min | unsignedInt 0…1 | 0 |
| Upper dead zone | list | 2.0 |
| Lower dead zone | list | 2.0 |
| Controller status after download | list | Comfort mode |
| Controller status after voltage recovery | list | As before voltage failure |
| Extended comfort mode [0..255,0=inactive] | unsignedInt 0…255 | 0 |
| 1 bit object function for operation mode | unsignedInt 0…1 | 0 |
| 1 bit object for standby mode | unsignedInt 0…1 | 1 |
| Fan speed auto.control function | unsignedInt 0…1 | 0 |
| Window contact input function | unsignedInt 0…1 | 0 |
| Delay for window contact [0..65535] | unsignedInt 0…65535 | 15 |
| Controller mode for open window | list | Frost/heat protection |
| Bus presence detector function | unsignedInt 0…1 | 0 |
| Setpoint method for operating mode | list | Absolute |
| Base setpoint temperature | list | 20.0 |
| Additional setpoint offset for setpoint adjustment | unsignedInt 0…1 | 0 |
| Step of setpoint offset | list | 0.5K |
| Min. setpoint offset [-10..0] | signedInt -10…0 | -5 |
| Max. setpoint offset [0..10] | unsignedInt 0…10 | 5 |
| Reduced heating in standby mode [0..10] | list | 2 |
| Reduced heating in economy mode [0..10] | list | 4 |
| Setpoint temperature in frost protection mode [5..10] | list | 7 |
| Increased cooling in standby mode [0..10] | list | 2 |
| Increased cooling in economy mode [0..10] | list | 4 |
| Setpoint temperature in heat protection mode [30..37] | list | 35 |
| Min. setpoint temperature [5..37] | list | 10 |
| Max. setpoint temperature [5..37] | list | 32 |
| Setpoint temperature in comfort mode [5..37] | list | 21 |
| Setpoint temperature in standby mode [5..37] | list | 19 |
| Setpoint temperature in economy mode [5..37] | list | 17 |
| Setpoint temperature in comfort mode [5..37] | list | 23 |
| Setpoint temperature in standby mode [5..37] | list | 25 |
| Setpoint temperature in economy mode [5..37] | list | 27 |
| Minimum zone between heating and cooling setpoint | list | 2.0 |
| Type of heating control | list | Switching On/Off(use 2-point control) |
| Invert control value | unsignedInt 0…1 | 0 |
| Lower Hysteresis [0..200] | unsignedInt 0…200 | 10 |
| Upper Hysteresis [0..200] | unsignedInt 0…200 | 10 |
| PWM cycle time [1..255] | unsignedInt 1…255 | 15 |
| Heating speed | list | Hot water heating(5K/150min) |
| Proportional range [10..100] | unsignedInt 0…100 | 40 |
| Reset time [0..255] | unsignedInt 0…255 | 150 |
| Send control value on change by [0..100,0=inactive] | unsignedInt 0…100 | 5 |
| Cyclically send control value [0..255] | unsignedInt 0…255 | 10 |
| Additional heating | unsignedInt 0…1 | 0 |
| Control type | list | 1bit |
| Temperature difference to switch on additional heating [-100..-5] | signedInt -100…-5 | -25 |
| Hysteresis to switch off additional heating [-20..-1] | signedInt -20…-1 | -5 |
| Cyclically send control value [0..255] | unsignedInt 0…255 | 0 |
| Type of cooling control | list | Switching On/Off(use 2-point control) |
| Cooling speed | list | Cooling ceiling (5K/240min) |
| Proportional range [10..100] | unsignedInt 10…100 | 40 |
| Additional cooling | unsignedInt 0…1 | 0 |
| Temperature difference to switch on additional cooling [5..100] | unsignedInt 5…100 | 25 |
| Hysteresis to switch off additional cooling [1..20] | unsignedInt 1…20 | 5 |
| Type of heating/cooling control | list | Switching On/Off(use 2-point control) |
| Additional heating/cooling | unsignedInt 0…1 | 0 |
| Auto. operation on object value | list | Auto=1/Man.=0 |
| Output value for fan speed low | unsignedInt 1…255 | 1 |
| Output value for fan speed medium | unsignedInt 1…255 | 2 |
| Output value for fan speed high | unsignedInt 1…255 | 3 |
| Output value for fan speed low | unsignedInt 1…100 | 33 |
| Output value for fan speed medium | unsignedInt 1…100 | 67 |
| Output value for fan speed high | unsignedInt 1…100 | 100 |
| 1 bit object function for fan speed | unsignedInt 0…1 | 0 |
| 1 bit object for fan speed off | unsignedInt 0…1 | 0 |
| Threshold value speed OFF<-->low [0..255] | unsignedInt 0…255 | 80 |
| Threshold value speed low<-->medium [1..255] | unsignedInt 1…255 | 150 |
| Threshold value speed medium<-->high [1..255] | unsignedInt 1…255 | 200 |
| Temperature difference speed OFF<-->low [0..200] | unsignedInt 0…200 | 20 |
| Temperature difference speed low<-->medium [1..200] | unsignedInt 1…200 | 30 |
| Temperature difference speed medium<-->high [1..200] | unsignedInt 1…200 | 40 |
| Hysteresis temperature difference in [0..50] | unsignedInt 0…50 | 10 |
| Minimum time in fan speed [0..65535] | unsignedInt 0…65535 | 60 |
| Room temperature reference from | list | Local sensor(Input 2) |
| Min.threshold value 1 [0..255] | unsignedInt 0…255 | 80 |
| Min.threshold value 2 [1..255] | unsignedInt 1…255 | 150 |
| Min.threshold value 3 [1..255] | unsignedInt 1…255 | 200 |
| Fan speed for min. threshold value 1 [1..100] | unsignedInt 1…100 | 30 |
| Fan speed for min. threshold value 2 [1..100] | unsignedInt 1…100 | 60 |
| Fan speed for min. threshold value 3 [1..100] | unsignedInt 1…100 | 80 |
| Limitation 1 lower limit | unsignedInt 0…100 | 0 |
| Limitation 2 lower limit | unsignedInt 0…100 | 0 |
| Limitation 3 lower limit | unsignedInt 0…100 | 0 |
| Limitation 4 lower limit | unsignedInt 0…100 | 0 |
| Controller from | list | Disable |
| If valve drive interface does not use output D, they serve as switch outputs | list | |
| If valve drive interface does not use output E, they serve as switch outputs | list | |
| If valve drive interface does not use output D&E, they serve as switch outputs | list | |
| Scene function | unsignedInt 0…1 | 0 |
| Overwrite scene stored values during download | unsignedInt 0…1 | 0 |
| 1>Assignment scene number
(1-64 is active,0 is no assignment) | unsignedInt 0…64 | 0 |
| Operation mode | list | Comfort mode |
| Fan speed | list | Unchange |
| Heating/Cooling | list | Unchange |
| 2>Assignment scene number
(1-64 is active,0 is no assignment) | unsignedInt 0…64 | 0 |
| 3>Assignment scene number
(1-64 is active,0 is no assignment) | unsignedInt 0…64 | 0 |
| 4>Assignment scene number
(1-64 is active,0 is no assignment) | unsignedInt 0…64 | 0 |
| 5>Assignment scene number
(1-64 is active,0 is no assignment) | unsignedInt 0…64 | 0 |
| 6>Assignment scene number
(1-64 is active,0 is no assignment) | unsignedInt 0…64 | 0 |
| 7>Assignment scene number
(1-64 is active,0 is no assignment) | unsignedInt 0…64 | 0 |
| 8>Assignment scene number
(1-64 is active,0 is no assignment) | unsignedInt 0…64 | 0 |
| When bus failure,Fan speed is | list | Off |
| When bus recovery,Fan speed is | list | Off |
| Temperature | list | Unchange |
| If bus failure, valve position | list | |
| Min.temperature difference Off<->speed 1 [0..200] | unsignedInt 0…200 | 20 |
| Min.temperature difference speed 1<->speed 2 [1..200] | unsignedInt 1…200 | 30 |
| Min.temperature difference speed 2<->speed 3 [1..200] | unsignedInt 1…200 | 40 |
| Min.temperature difference 1 [0..200] | unsignedInt 0…200 | 20 |
| Min.temperature difference 2 [1..200] | unsignedInt 1…200 | 30 |
| Min.temperature difference 3 [1..200] | unsignedInt 1…200 | 40 |
| Fan speed for min. temperature difference 1 [1..100] | unsignedInt 1…100 | 30 |
| Fan speed for min. temperature difference 2 [1..100] | unsignedInt 1…100 | 60 |
| Fan speed for min. temperature difference 3 [1..100] | unsignedInt 1…100 | 80 |
| Min.threshold value Off<->On[1..255] | unsignedInt 1…255 | 80 |
| Min.temperature difference Off<->On[1..200] | unsignedInt 1…200 | 20 |
| Fan speed control method | list | Three level according to control value |
| Limitation 1 upper limit | unsignedInt 0…100 | 100 |
| Limitation 2 upper limit | unsignedInt 0…100 | 100 |
| Limitation 3 upper limit | unsignedInt 0…100 | 100 |
| Limitation 4 upper limit | unsignedInt 0…100 | 100 |
| Function | list | BI: Switch sensor |
| Description (max 30char.) | text | |
| B value of temperature sensor
(must refer to the characteristic of component) | list | 3950 |
| Temperature calibration | list | 0.0 |
| Cyclically send temperature [0...255] | unsignedInt 0…255 | 0 |
| Reply error of sensor measurement | list | No respond |
| Object value of error | list | 0=no error/1=error |
| Lower threshold value for error report | list | 0 |
| Upper threshold value for error report | list | 60 |
| Distinction between short and long operation | unsignedInt 0…1 | 0 |
| Reaction on close the contact | list | TOGGLE |
| Reaction on open the contact | list | No reaction |
| Send object value after voltage recovery
(valid if reaction is not toggle) | unsignedInt 0…1 | 0 |
| Number of objects | list | 1 |
| Long operation after [3..25] | unsignedInt 3…25 | 5 |
| Connected contact type | list | Normally open |
| Reaction on short operation | list | TOGGLE |
| Reaction on long operation | list | No reaction |
| Disable function | list | Disable |
| Reaction on close the contact | list | Recall scene |
| 8 bit scene number | list | Scene No.2 |
| Reaction on short operation | list | Recall scene |
| Reaction on close the contact | list | Send Value |
| String (14byte) value | text | Hello, world ! |
| Send object value after voltage recovery | unsignedInt 0…1 | 0 |
| Reaction on short operation | list | Send Value |
| Interval of tele. cyclic send [0..60000] (0=send once) | unsignedInt 0…60000 | 0 |
| Behaviour from disable to enable
(valid if reaction is not toggle) | list | No reaction |
| Work mode of the channel is | list | Switch actuator |
| Central function of channel | unsignedInt 0…1 | 0 |
| If bus recovery, output status is | list | Unchange |
| If bus failure, output status is | list | Unchange |
| After downloading,output status is | list | Contact open |
| Object value of "switch" after bus recovery | list | 0 |
| Set the reply mode of switch status | list | Respond after change |
| Object value of switch status | list | 1=contact close;0=contact open |
| Output status for the telegram "1"
(telegram "0" is opposite of selection) | list | Contact close |
| Extension function | unsignedInt 0…1 | 0 |
| Function of "Time" | unsignedInt 0…1 | 0 |
| Function of "Logic" | unsignedInt 0…1 | 0 |
| Function of "Scene" | unsignedInt 0…1 | 0 |
| Function of "Forced" | unsignedInt 0…1 | 0 |
| Force operation type | list | 1Bit |
| Output status if forced operation | list | Unchange |
| Function of "Operation hours counter" | unsignedInt 0…1 | 0 |
| Object datatype of "Operation hours counter" | list | 4 byte Value in s(DPT13.100) |
| Cyclically send counter value in [0...100] (0 = not send,only for reading) | unsignedInt 0…100 | 0 |
| Type of time function | list | Delay |
| Delay for switch on(contact close)
--(0...240) | unsignedInt 0…240 | 0 |
| --(0...59) | unsignedInt 0…59 | 0 |
| Delay for switch off(contact open)
--(0...240) | unsignedInt 0…240 | 0 |
| Duration of staircase lighting
--(0...1000) | unsignedInt 0…1000 | 1 |
| Control mode of staircase lighting | list | Start with "1",Stop with"0" |
| During the lighting time,if receive the "start" telegram | list | Restart duration of staircase lighting |
| Modify the duration via object [0...60059] | unsignedInt 0…1 | 0 |
| Duration of switch on(contact close)
--(0...240) | unsignedInt 0…240 | 0 |
| Duration of switch off(contact open)
--(0...240) | unsignedInt 0…240 | 0 |
| Number of ON-implused [1...255,0=no limited] | unsignedInt 0…255 | 0 |
| Output status after flashing | list | Unchange |
| Control mode of flashing | list | Start with "1",Stop with"0" |
| Enable input 0 | unsignedInt 0…1 | 0 |
| Input 0 reverse | unsignedInt 0…1 | 0 |
| The input 1 of logic | unsignedInt 0…1 | 0 |
| Logic function type | list | AND |
| Input 1 reverse | unsignedInt 0…1 | 0 |
| Invert result(if no,1=contact close,0=contact open;while yes is opposite) | unsignedInt 0…1 | 0 |
| Value of input1 after bus recovery | list | 0 |
| The input 2 of logic | unsignedInt 0…1 | 0 |
| Input 2 reverse | unsignedInt 0…1 | 0 |
| Value of input2 after bus recovery | list | 0 |
| Overwrite scene stored values during download | unsignedInt 0…1 | 1 |
| 1> channel is assigned to (1...64,0=no assignment) | unsignedInt 0…64 | 0 |
| Output status is | list | Contact open |
| 2> channel is assigned to (1...64,0=no assignment) | unsignedInt 0…64 | 0 |
| 3> channel is assigned to (1...64,0=no assignment) | unsignedInt 0…64 | 0 |
| 4> channel is assigned to (1...64,0=no assignment) | unsignedInt 0…64 | 0 |
| 5> channel is assigned to (1...64,0=no assignment) | unsignedInt 0…64 | 0 |
| 6> channel is assigned to (1...64,0=no assignment) | unsignedInt 0…64 | 0 |
| 7> channel is assigned to (1...64,0=no assignment) | unsignedInt 0…64 | 0 |
| 8> channel is assigned to (1...64,0=no assignment) | unsignedInt 0…64 | 0 |
| Valve type | list | Normal (de-energised closed) |
| If bus recovery, valve position | list | 0%[Closed] |
| PWM cycle time for continuous [60...65535] | unsignedInt 60…65535 | 120 |
| Control type | list | 1bit (on-off control or PWM) |
| Reply the status for continuous control | list | No reply |
| Reply the status of contact state | list | Yes, 1=contact close; 0=contact open |
| Function of monitoring | unsignedInt 0…1 | 1 |
| Cyclic monitoring control value
[0…65535] | unsignedInt 0…65535 | 120 |
| Valve position during fault | list | Unchange |
| Report fault status | unsignedInt 0…1 | 1 |
| Function of forced operation | unsignedInt 0…1 | 0 |
| Valve position during forced operation | list | Unchange |
| Output A Switch | unsignedInt 0…1 | 0 |
| Output B Switch | unsignedInt 0…1 | 0 |
| Output C Switch | unsignedInt 0…1 | 0 |
| Output D Switch | unsignedInt 0…1 | 0 |
| Output E Switch | unsignedInt 0…1 | 0 |