GVS 1AFVFx17GA AFVFT-07/10.1

AFVFT-07/10.1 1AFVFx17GA

GVS · Order number 1AFVFx17GA · Actuator › Fan coil

Fan Coil Actuator with 0-10V

Download .knxprod Fan Coil Actuator with 0-10V 2.2 · 305 KB

Product

ManufacturerGVS
Product nameAFVFT-07/10.1
Order number1AFVFx17GA
Product textFan Coil Actuator with 0-10V
HardwareAFVFT-07/10.1
MediumTwisted Pair
Bus current (mA)12
Rail mountedYes
Width (mm)72
RegistrationCertified · 2019-05-03
Languagesen-US
Catalog entryM-0085_H-AF17GA-1_HP-0033-22-81DC_CI-1AFVFx17GA-2
Fingerprint81DC
SHA-2562dbb5f00c92c644adcb959c6ff94c1834c3637d6b3d8272c26182066ecceb424
First seen2026-11-25
Markets69 markets

Application program: Fan Coil Actuator with 0-10V 2.2

Application number$0033
Version2.2
Mask versionMV-07B0 (System B)
KNX Data SecureNo
Minimum ETS version5.0
Parameters1080
Group objects126
Group objects (126)
NoNameFunctionSizeDPTFlags
1GeneralIn operation1 Bit1.1 switchCT
2GeneralCentral switch1 Bit1.1 switchCW
3GeneralOperation status for HVAC1 ByteCRT
4Input setpointBase setpoint2 Bytes9.1 temperature (°C)CW
5Input setpointSetpoint adjustment2 Bytes9.1 temperature (°C)CW
6Output setpointInstantaneous setpoint2 Bytes9.1 temperature (°C)CRT
7TemperatureActual temperature output2 Bytes9.1 temperature (°C)CRT
8TemperatureLocal sensor error output1 Bit1.5 alarmCRT
9TemperatureExternal sensor2 Bytes9.1 temperature (°C)CWTU
10FanFan speed1 Bit1.1 switchCW
10FanFan speed1 Byte5.1 percentage (0..100%)CW
11FanFan speed 11 Bit1.1 switchCW
12FanFan speed 21 Bit1.1 switchCW
13FanFan speed 31 Bit1.1 switchCW
14FanFan speed Up/Down1 Bit1.8 up/downCW
15FanStatus Fan ON/OFF1 Bit1.1 switchCRT
16FanStatus Fan speed1 Byte5.10 counter pulses (0..255)CRT
17FanStatus Fan speed 11 Bit1.1 switchCRT
18FanStatus Fan speed 21 Bit1.1 switchCRT
19FanStatus Fan speed 31 Bit1.1 switchCRT
20FanAutomatic function1 Bit1.3 enableCW
21FanStatus Automatic1 Bit1.3 enableCRT
22FanFan Limitation 11 Bit1.3 enableCW
23FanFan Limitation 21 Bit1.3 enableCW
24FanFan Limitation 31 Bit1.3 enableCW
25FanFan Limitation 41 Bit1.3 enableCW
26FanForced operation1 Bit1.3 enableCW
27HVACScene1 Byte18.1 scene controlCW
28HVACDisable,heating1 Bit1.3 enableCW
28HVACDisable,heating/cooling1 Bit1.3 enableCW
29HVACDisable,cooling1 Bit1.3 enableCW
30HVACSwitch heating/cooling mode1 Bit1.100 cooling/heatingCW
31HVAC modeComfort mode1 Bit1.1 switchCW
31HVAC modeHVAC mode1 Byte20.102 HVAC modeCW
32HVAC modeNight mode1 Bit1.1 switchCW
33HVAC modeFrost/heat protection mode1 Bit1.1 switchCW
34Valve HeatingControl value1 Byte5.1 percentage (0..100%)CW
34Valve HeatingControl value1 Bit1.1 switchCW
34Valve Heating/CoolingControl value1 Bit1.1 switchCW
34Valve Heating/CoolingControl value1 Byte5.1 percentage (0..100%)CW
34HVAC modeStandby mode1 Bit1.1 switchCW
35Valve HeatingTrigger valve purge1 Bit1.3 enableCW
35Valve Heating/CoolingTrigger valve purge1 Bit1.3 enableCW
36Valve HeatingStatus of valve purge1 Bit1.3 enableCRT
36Valve Heating/CoolingStatus of valve purge1 Bit1.3 enableCRT
37Valve HeatingStatus of valve position1 Bit1.1 switchCRT
37Valve Heating/CoolingStatus of valve position1 Bit1.1 switchCRT
38Valve CoolingControl value1 Byte5.1 percentage (0..100%)CW
38Valve CoolingControl value1 Bit1.1 switchCW
38HVACHeating mode enable1 Bit1.3 enableCW
39Valve CoolingTrigger valve purge1 Bit1.3 enableCW
39HVACCooling mode enable1 Bit1.3 enableCW
40Valve CoolingStatus of valve purge1 Bit1.3 enableCRT
41Valve CoolingStatus of valve position1 Bit1.1 switchCRT
42HVACControl value fault1 Bit1.5 alarmCRT
42HVAC StatusHVAC mode1 Byte20.102 HVAC modeCRT
42HVAC StatusComfort mode1 Bit1.1 switchCRT
43HVAC StatusNight mode1 Bit1.1 switchCRT
44HVAC StatusFrost/heat protection mode1 Bit1.1 switchCRT
45HVAC StatusStandby mode1 Bit1.1 switchCRT
46HVAC StatusHeating/Cooling mode1 Bit1.100 cooling/heatingCRT
47Output ASwitch1 Bit1.1 switchCW
48Output ASwitch status1 Bit1.1 switchCRT
49Output AEnable time function1 Bit1.3 enableCW
50Output ADelay function1 Bit1.1 switchCW
50Output AFlashing function1 Bit1.1 switchCW
50Output AStaircase function1 Bit1.1 switchCW
51Output AOperation hours counter4 Bytes13.100 time lag (s)CRWTU
51Output AOperation hours counter2 Bytes7.7 time (h)CRWTU
52Output AScene1 Byte18.1 scene controlCW
53Output AForced output2 Bit2.1 switch controlCW
53Output AForced output1 Bit1.3 enableCW
54Output ALogic 11 Bit1.2 booleanCW
55Output ALogic 21 Bit1.2 booleanCW
56Output BSwitch1 Bit1.1 switchCW
57Output BSwitch status1 Bit1.1 switchCRT
58Output BEnable time function1 Bit1.3 enableCW
59Output BDelay function1 Bit1.1 switchCW
59Output BFlashing function1 Bit1.1 switchCW
59Output BStaircase function1 Bit1.1 switchCW
60Output BOperation hours counter4 Bytes13.100 time lag (s)CRWTU
60Output BOperation hours counter2 Bytes7.7 time (h)CRWTU
61Output BScene1 Byte18.1 scene controlCW
62Output BForced output2 Bit2.1 switch controlCW
62Output BForced output1 Bit1.3 enableCW
63Output BLogic 11 Bit1.2 booleanCW
64Output BLogic 21 Bit1.2 booleanCW
65Output CSwitch1 Bit1.1 switchCW
66Output CSwitch status1 Bit1.1 switchCRT
67Output CEnable time function1 Bit1.3 enableCW
68Output CDelay function1 Bit1.1 switchCW
68Output CFlashing function1 Bit1.1 switchCW
68Output CStaircase function1 Bit1.1 switchCW
69Output COperation hours counter4 Bytes13.100 time lag (s)CRWTU
69Output COperation hours counter2 Bytes7.7 time (h)CRWTU
70Output CScene1 Byte18.1 scene controlCW
71Output CForced output2 Bit2.1 switch controlCW
71Output CForced output1 Bit1.3 enableCW
72Output CLogic 11 Bit1.2 booleanCW
73Output CLogic 21 Bit1.2 booleanCW
74Output DSwitch1 Bit1.1 switchCW
75Output DSwitch status1 Bit1.1 switchCRT
76Output DEnable time function1 Bit1.3 enableCW
77Output DDelay function1 Bit1.1 switchCW
77Output DFlashing function1 Bit1.1 switchCW
77Output DStaircase function1 Bit1.1 switchCW
78Output DOperation hours counter4 Bytes13.100 time lag (s)CRWTU
78Output DOperation hours counter2 Bytes7.7 time (h)CRWTU
79Output DScene1 Byte18.1 scene controlCW
80Output DForced output2 Bit2.1 switch controlCW
80Output DForced output1 Bit1.3 enableCW
81Output DLogic 11 Bit1.2 booleanCW
82Output DLogic 21 Bit1.2 booleanCW
83Output ESwitch1 Bit1.1 switchCW
84Output ESwitch status1 Bit1.1 switchCRT
85Output EEnable time function1 Bit1.3 enableCW
86Output EDelay function1 Bit1.1 switchCW
86Output EFlashing function1 Bit1.1 switchCW
86Output EStaircase function1 Bit1.1 switchCW
87Output EOperation hours counter4 Bytes13.100 time lag (s)CRWTU
87Output EOperation hours counter2 Bytes7.7 time (h)CRWTU
88Output EScene1 Byte18.1 scene controlCW
89Output EForced output2 Bit2.1 switch controlCW
89Output EForced output1 Bit1.3 enableCW
90Output ELogic 11 Bit1.2 booleanCW
91Output ELogic 21 Bit1.2 booleanCW
Parameters (203)
ParameterTypeDefault
Relay operation delay after power voltage recovery[5...250s]unsignedInt 5…25010
Sending cycle of "In operation"telegram (1..240s,0=inactive)unsignedInt 0…2400
Manual operationlistEnable
Manual to automatic bylistOnly long press
Delay time*1s[10...6000]unsignedInt 10…600010
Report operation status function for HVAClistDisable
Central control for switch functionlistDisable
Fan drive interfacelistDisable
HVAC Control modelistHeating and Cooling
Heating valve drive interfacelistRelay control(CH D)
Cooling valve drive interfacelistRelay control(CH E)
HVAC Systemlist4 pipes system
Heating/Cooling valve drive interfacelistRelay control(CH D)
Fan speed 1 voltage*0.5V[1...20]unsignedInt 1…205
Fan speed 2 voltage*0.5V[1...20]unsignedInt 1…2010
Fan speed 3 voltage*0.5V[1...20]unsignedInt 1…2015
If fan is one level,the setting of 2 and 3 will be ignoredlist<--Attention
Controller definelistLocal
Lower Hysteresis*0.1°C[0...200] (for heating)unsignedInt 0…20010
Upper Hysteresis*0.1°C[0...200] (for cooling)unsignedInt 0…20010
Heating speedlistNormal(12000/900)
Proportional range[0..65535](P value)unsignedInt 0…6553512000
Readjust time*s[0..65535](I value)unsignedInt 0…65535600
Control value object typelist1bit
Monitoring control valuelistYes
Monitoring period of control value*s[10...65535]unsignedInt 10…6553560
Reply mode of Obj"Control value fault" 1bit functionlistRespond after change
Control value after fault occurs[0...100]%unsignedInt 0…10020
Temperature measure bylistLocal sensor
Temperature calibration for local sensor*0.1°C[-50..50]signedInt -50…500
Reply error of local sensor measurementlistRespond after change
Object value of errorlist0=no error/1=error
Send actual temperature to buslistYes
Send temperature when the result change by*0.5°C[1...20]unsignedInt 1…204
Cyclically send actual temperature[0..255]*minunsignedInt 0…25510
Time period for requesting external sensor[0..255]*minunsignedInt 0…2551
Combination ratiolist50% Local to 50% External
Base setpoint temperature(°C)list20
When bus recovery,controller statuslistComfort mode
Extended comfort mode*min(0=inactive,1-255 is valid)unsignedInt 0…25530
Operating mode switchoverlist1bit
Operating mode statuslist1byte
Reduced heating in standby mode[0...10] °CunsignedInt 0…102
Reduced heating during night mode[0...10] °CunsignedInt 0…104
Actual temperature threshold in frost protection mode[2...10] °CunsignedInt 2…107
Limit value for setpoint heating [5...40]°CunsignedInt 5…4035
Valve control modelist2 state-ON/OFF
Valve typelistNormal (de-energised closed)
The Controller use 2-point control methodlist<--Attention
The Controller use PI control methodlist<--Attention
PWM cycle time*s[60-3000]unsignedInt 60…3000120
When bus failure,valve positionlistUnchange
Reply mode of Obj."status of valve position" 1bit functionlistRespond after change
Valve purge functionlistDisable
Duration of valve purge time*min[1...255]unsignedInt 1…25510
Automatic valve purgelistDisable
Purge Cycle in weeks[1...12]unsignedInt 1…121
Reply mode of Obj."status of valve purge" 1bit functionlistRespond after change
"Disable heating" object functionlistDisable
Trigger object valuelist0=Disable/1=Enable
Valve control modelist2 state-10V/0V
Valve adjustment only valid for Local controllerlist<--Attention
Valve adjustmentlistDisable
Minimum controller output for closed valve[0-100]%unsignedInt 0…1000
Maximum controller output for fully opened valve[0...100]%unsignedInt 0…100100
Lower limit of active valve opening range[0...100]%unsignedInt 0…1000
Upper limit of active valve opening range[0...100]%unsignedInt 0…100100
Scene functionlistEnable
1>Assignment scene number(1..64,0=no assignment)unsignedInt 0…640
HVAC ModelistStandby mode
Fan Speed(if fan type is one level,all 1/2/3 mean on)listUnchange
2>Assignment scene number(1..64,0=no assignment)unsignedInt 0…640
HVAC ModelistComfort mode
3>Assignment scene number(1..64,0=no assignment)unsignedInt 0…640
HVAC ModelistNight mode
4>Assignment scene number(1..64,0=no assignment)unsignedInt 0…640
HVAC ModelistFrost/heat protection
5>Assignment scene number(1..64,0=no assignment)unsignedInt 0…640
6>Assignment scene number(1..64,0=no assignment)unsignedInt 0…640
7>Assignment scene number(1..64,0=no assignment)unsignedInt 0…640
8>Assignment scene number(1..64,0=no assignment)unsignedInt 0…640
Control Value(if Valve is 2 state-ON/OFF,value>0 means on)unsignedInt 0…2550
Control Value(if Valve is 2 state-ON/OFF,value>0 means on)unsignedInt 0…25510
Control Value(if Valve is 2 state-ON/OFF,value>0 means on)unsignedInt 0…25520
Control Value(if Valve is 2 state-ON/OFF,value>0 means on)unsignedInt 0…25530
Control Value(if Valve is 2 state-ON/OFF,value>0 means on)unsignedInt 0…25540
Control Value(if Valve is 2 state-ON/OFF,value>0 means on)unsignedInt 0…25550
Control Value(if Valve is 2 state-ON/OFF,value>0 means on)unsignedInt 0…25560
Control Value(if Valve is 2 state-ON/OFF,value>0 means on)unsignedInt 0…25570
Cooling speedlistNormal(12000/900)
Increased cooling in standby mode[0...10] °CunsignedInt 0…102
Increased cooling during night mode[0...10] °CunsignedInt 0…104
Actual temperature threshold in heat protection mode[5...40] °CunsignedInt 5…4040
Limit value for setpoint cooling [5...60]°CunsignedInt 5…6015
"Disable cooling" object functionlistDisable
Heating or Cooling switch bylistLocal
Number of Heating/Cooling switch objectlist1 object
Insensitive zone between heating and coolinglist1°C
Minimum changeover time between heating and cooling*min[0...255](0=inactive)unsignedInt 0…2555
Number of control valuelist2 control value
"Disable heating/cooling" object functionlistDisable
Heating/Cooling(only used for 4-pipes of bus controller)listUnchange
Switch functionlistDisable
Central function of channellistEnable
When bus recovery,contact islistUnchange
When bus failure,contact islistUnchange
After downloading,contact islistOpen
Object value of "switch" after bus recovery or downloadinglist0
Reply mode of switch statuslistRespond after change
Object value of switch statuslist1=contact close;0=contact open
Contact position if tele.value is"1" ("0"is opposite of "1" if changed)listClose
Special function of channellistDisable
Function of "time"listDisable
Function of "logic"listDisable
Function of "scene"listDisable
Function of "Forced"listDisable
Force operation typelist1Bit
Contact position if forced operationlistUnchange
Function of "Operation hours counter"listDisable
Object datatype of "Operation hours counter"list2 byte Value in h (DPT 7.007)
Cyclically send counter value in hour[0...100](0 = no send,only for readingunsignedInt 0…1000
Type of time functionlistDelay
Delay for switch on: --(0...240min)unsignedInt 0…2400
--(0...59s)unsignedInt 0…590
Delay for switch off: --(0...240min)unsignedInt 0…2400
Number of ON-implused (1...255,0=no limited)unsignedInt 0…2550
Contact position after flashinglistUnchange
The control mode of flashinglistStart with "1",Stop with "0"
Duration of staircase lighting: --(0...1000min)unsignedInt 0…10001
Control mode of staircase lightinglistStart with "1",Stop with "0"
During the lighting time,if receive the "start" telegramlistRestart duration of staircase lighting
Enable input 0listDisable
Input 0 reverselistNo
The input 1 of logiclistEnable
Logic function typelistAND
Input 1 reverselistNo
Result reverselistNo
Value of input 1 after bus recoverylist0
The input 2 of logiclistEnable
Input 2 reverselistNo
Value of input 2 after bus recoverylist0
Overwrite scene stored values during downloadlistEnable
1> channel is assigned to (1...64,0=no assignment)unsignedInt 0…640
Standard output value islistOFF
2> channel is assigned to (1...64,0=no assignment)unsignedInt 0…640
3> channel is assigned to (1...64,0=no assignment)unsignedInt 0…640
4> channel is assigned to (1...64,0=no assignment)unsignedInt 0…640
5> channel is assigned to (1...64,0=no assignment)unsignedInt 0…640
6> channel is assigned to (1...64,0=no assignment)unsignedInt 0…640
7> channel is assigned to (1...64,0=no assignment)unsignedInt 0…640
8> channel is assigned to (1...64,0=no assignment)unsignedInt 0…640
Fan typelistMulti-level
When bus failure,Fan speed islistUnchange
When bus recovery, fan speed islistUnchange
After downloading, fan speed islistOFF
"Forced operation" functionlistDisable
Forced operation on object valuelist1=Force/0=Cancel
Behaviour on Forced operationlistUnchange
Auto. operation function (only for HVAC)listDisable
Time mode for function ONlistSwitch Delay
Delay time*0.1s[1...65535]unsignedInt 1…6553510
Minimum time*s[1...65535]unsignedInt 1…6553510
Time mode for function OFFlistSwitch Delay
Fan speeds on 2 limitlistNo
Fan operation modelistChangeover switch
Delay between fan speed switch*ms[50...5000]unsignedInt 50…5000500
Threshold value for Fan speed 1[1...255]unsignedInt 1…25550
Threshold value for Fan speed 2[1...255]unsignedInt 1…255150
Threshold value for Fan speed 3[1...255]unsignedInt 1…255255
Limitation on forced operationlistUnchange
Direct operation functionlistEnable
Obj. "Switch speed x " 1bit functionlistEnable
Obj. "Fan speed Up/Down" 1bit functionlistEnable
Delay time for function OFF *0.1s[0...65535]unsignedInt 0…655350
Starting characteristic of fanlistEnable
Switch on over fan speedlist2
Minimum time in switch*s[1...65535]unsignedInt 1…6553510
Auto.operation on object valuelist1=Auto/0=Cancel
State of Auto.operation after startuplistDisable auto.operation
Automatically enable auto.operationlistNo
Enable auto.operation after [10..6000]minunsignedInt 10…6000100
Threshold value OFF<-->ON[1..255](For 2 point,it's Tem.difference*0.1°C)unsignedInt 1…255100
Hysteresis value is threshold value in +/-[0...50](For 2 point,it is unused)unsignedInt 0…5010
Limitation functionlistDisable
Fan with limitation 1listDisable
Fan with limitation 2listDisable
Fan with limitation 3listDisable
Fan with limitation 4listDisable
Reply mode of Obj. "status ON/OFF mode" 1bit functionlistRespond after change
Reply mode of Obj. "status Auto. mode" 1bit functionlistRespond after change
Threshold value OFF<-->speed 1[1..255](For 2 point,it's Tem.difference*0.1°C)unsignedInt 1…255100
Threshold value speed 1<-->speed 2[1..255](For 2 point,it's Tem.difference*0.1°CunsignedInt 1…255150
Threshold value speed 2<-->speed 3[1..255](For 2 point,it's Tem.difference*0.1°CunsignedInt 1…255200
Minimum time in fan speed[0...65535]*sunsignedInt 0…6553510
Fan with limitation 1listUnchange
Fan with limitation 2list1,OFF
Fan with limitation 3list2,1
Fan with limitation 4list3,2,1
Reply mode of Obj. "Status fan speed x" 1bit functionlistRespond after change
Reply mode of Obj. "Status fan speed" 1byte functionlistRespond after change
Object value for Status Fan speed 1[1...255]unsignedInt 1…25584
Object value for Status Fan speed 2[1...255]unsignedInt 1…255168
Object value for Status Fan speed 3[1...255]unsignedInt 1…255255

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Fan Coil Actuator with 0-10V 2.2 latest$003381DC2026-11-25305 KBDownload

About this file

This is the official ETS product database for the GVS AFVFT-07/10.1 (1AFVFx17GA), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.