GVS AFVFT-07/10.S 0-10V Fan Coil Actuator with Secure

0-10V Fan Coil Actuator with Secure AFVFT-07/10.S

GVS · Order number AFVFT-07/10.S · Actuator › Fan coil

Download .knxprod 0-10V Fan Coil Actuator with Secure/00E4 2.0 2.0 · 230 KB

Product

ManufacturerGVS
Product name0-10V Fan Coil Actuator with Secure
Order numberAFVFT-07/10.S
Hardware0-10V Fan Coil Actuator with Secure
MediumTwisted Pair
Bus current (mA)43
Rail mountedYes
Width (mm)72
RegistrationCertified · 2026-01-09
Languagesen-US, zh-CN
Catalog entryM-0085_H-AF25DG-1_HP-00E4-20-A321_CI-AFVFT.2D07.2F10.2ES-1
FingerprintA321
SHA-256b8e4ed916b5f850012a9b1480c8e9129ff70dc60d753a0c64f7c3d19d7098736
First seen2026-11-25
Markets69 markets

Application program: 0-10V Fan Coil Actuator with Secure/00E4 2.0 2.0

Application number$00E4
Version2.0
Mask versionMV-07B0 (System B)
KNX Data SecureYes
Minimum ETS version5.0
Parameters589
Group objects228
Group objects (228)
NoNameFunctionSizeDPTFlags
0Input 1 - {{0:...}}Disable1 Bit1.3 enableCW
0Input 2 - {{0:...}}Disable1 Bit1.3 enableCW
0Output A-{{0:...}}Switch1 Bit1.1 switchCW
0Output A-{{0:...}}On-off control value1 Bit1.1 switchCW
0Output B-{{0:...}}Switch1 Bit1.1 switchCW
0Output B-{{0:...}}On-off control value1 Bit1.1 switchCW
0Output C-{{0:...}}Switch1 Bit1.1 switchCW
0Output C-{{0:...}}On-off control value1 Bit1.1 switchCW
0Output D-{{0:...}}Switch1 Bit1.1 switchCW
0Output D-{{0:...}}On-off control value1 Bit1.1 switchCW
0Output E-{{0:...}}Switch1 Bit1.1 switchCW
0Output E-{{0:...}}On-off control value1 Bit1.1 switchCW
1GeneralIn operation1 Bit1.1 switchCRT
1Input 1 - {{0:...}}Actual temperature, Sensor2 Bytes9.1 temperature (°C)CRT
1Input 1 - {{0:...}}Switch1 Bit1.1 switchCRWTU
1Input 1 - {{0:...}}Close, Switch1 Bit1.1 switchCRWTU
1Input 1 - {{0:...}}Short, Switch1 Bit1.1 switchCRWTU
1Input 1 - {{0:...}}Scene1 Byte18.1 scene controlCT
1Input 1 - {{0:...}}Close, Scene1 Byte18.1 scene controlCT
1Input 1 - {{0:...}}Short, Scene1 Byte18.1 scene controlCT
1Input 1 - {{0:...}}String14 Bytes16.1 Character String (ISO 8859-1)CT
1Input 1 - {{0:...}}Close, String14 Bytes16.1 Character String (ISO 8859-1)CT
1Input 1 - {{0:...}}Short, String14 Bytes16.1 Character String (ISO 8859-1)CT
1Input 2 - {{0:...}}Actual temperature, Sensor2 Bytes9.1 temperature (°C)CRT
1Input 2 - {{0:...}}Switch1 Bit1.1 switchCRWTU
1Input 2 - {{0:...}}Close, Switch1 Bit1.1 switchCRWTU
1Input 2 - {{0:...}}Short, Switch1 Bit1.1 switchCRWTU
1Input 2 - {{0:...}}Scene1 Byte18.1 scene controlCT
1Input 2 - {{0:...}}Close, Scene1 Byte18.1 scene controlCT
1Input 2 - {{0:...}}Short, Scene1 Byte18.1 scene controlCT
1Input 2 - {{0:...}}String14 Bytes16.1 Character String (ISO 8859-1)CT
1Input 2 - {{0:...}}Close, String14 Bytes16.1 Character String (ISO 8859-1)CT
1Input 2 - {{0:...}}Short, String14 Bytes16.1 Character String (ISO 8859-1)CT
1Output A-{{0:...}}Switch status1 Bit1.1 switchCRT
1Output A-{{0:...}}Status of contact1 Bit1.1 switchCRT
1Output B-{{0:...}}Switch status1 Bit1.1 switchCRT
1Output B-{{0:...}}Status of contact1 Bit1.1 switchCRT
1Output C-{{0:...}}Switch status1 Bit1.1 switchCRT
1Output C-{{0:...}}Status of contact1 Bit1.1 switchCRT
1Output D-{{0:...}}Switch status1 Bit1.1 switchCRT
1Output D-{{0:...}}Status of contact1 Bit1.1 switchCRT
1Output E-{{0:...}}Switch status1 Bit1.1 switchCRT
1Output E-{{0:...}}Status of contact1 Bit1.1 switchCRT
2GeneralCentral switch1 Bit1.1 switchCW
2Input 1 - {{0:...}}Temperature error report, Sensor1 Bit1.5 alarmCRT
2Input 1 - {{0:...}}Open, Switch1 Bit1.1 switchCRWTU
2Input 1 - {{0:...}}Long, Switch1 Bit1.1 switchCRWTU
2Input 1 - {{0:...}}Open, Scene1 Byte18.1 scene controlCT
2Input 1 - {{0:...}}Long, Scene1 Byte18.1 scene controlCT
2Input 1 - {{0:...}}Open, String14 Bytes16.1 Character String (ISO 8859-1)CT
2Input 1 - {{0:...}}Long, String14 Bytes16.1 Character String (ISO 8859-1)CT
2Input 2 - {{0:...}}Temperature error report, Sensor1 Bit1.5 alarmCRT
2Input 2 - {{0:...}}Open, Switch1 Bit1.1 switchCRWTU
2Input 2 - {{0:...}}Long, Switch1 Bit1.1 switchCRWTU
2Input 2 - {{0:...}}Open, Scene1 Byte18.1 scene controlCT
2Input 2 - {{0:...}}Long, Scene1 Byte18.1 scene controlCT
2Input 2 - {{0:...}}Open, String14 Bytes16.1 Character String (ISO 8859-1)CT
2Input 2 - {{0:...}}Long, String14 Bytes16.1 Character String (ISO 8859-1)CT
2Output A-{{0:...}}Enable time function1 Bit1.3 enableCW
2Output A-{{0:...}}Status of continuous, 1bit1 Bit1.1 switchCRT
2Output B-{{0:...}}Enable time function1 Bit1.3 enableCW
2Output B-{{0:...}}Status of continuous, 1bit1 Bit1.1 switchCRT
2Output C-{{0:...}}Enable time function1 Bit1.3 enableCW
2Output C-{{0:...}}Status of continuous, 1bit1 Bit1.1 switchCRT
2Output D-{{0:...}}Enable time function1 Bit1.3 enableCW
2Output D-{{0:...}}Status of continuous, 1bit1 Bit1.1 switchCRT
2Output E-{{0:...}}Enable time function1 Bit1.3 enableCW
2Output E-{{0:...}}Status of continuous, 1bit1 Bit1.1 switchCRT
3Output A-{{0:...}}Delay function1 Bit1.1 switchCW
3Output A-{{0:...}}Flashing function1 Bit1.1 switchCW
3Output A-{{0:...}}Staircase function1 Bit1.1 switchCW
3Output A-{{0:...}}Control value(Continuous)1 Byte5.1 percentage (0..100%)CW
3Output B-{{0:...}}Delay function1 Bit1.1 switchCW
3Output B-{{0:...}}Flashing function1 Bit1.1 switchCW
3Output B-{{0:...}}Staircase function1 Bit1.1 switchCW
3Output B-{{0:...}}Control value(Continuous)1 Byte5.1 percentage (0..100%)CW
3Output C-{{0:...}}Delay function1 Bit1.1 switchCW
3Output C-{{0:...}}Flashing function1 Bit1.1 switchCW
3Output C-{{0:...}}Staircase function1 Bit1.1 switchCW
3Output C-{{0:...}}Control value(Continuous)1 Byte5.1 percentage (0..100%)CW
3Output D-{{0:...}}Delay function1 Bit1.1 switchCW
3Output D-{{0:...}}Flashing function1 Bit1.1 switchCW
3Output D-{{0:...}}Staircase function1 Bit1.1 switchCW
3Output D-{{0:...}}Control value(Continuous)1 Byte5.1 percentage (0..100%)CW
3Output E-{{0:...}}Delay function1 Bit1.1 switchCW
3Output E-{{0:...}}Flashing function1 Bit1.1 switchCW
3Output E-{{0:...}}Staircase function1 Bit1.1 switchCW
3Output E-{{0:...}}Control value(Continuous)1 Byte5.1 percentage (0..100%)CW
4Output A-{{0:...}}Operation hours counter4 Bytes13.100 time lag (s)CRWTU
4Output A-{{0:...}}Operation hours counter2 Bytes7.7 time (h)CRWTU
4Output A-{{0:...}}Status of continuous, 1byte1 Byte5.1 percentage (0..100%)CRT
4Output B-{{0:...}}Operation hours counter4 Bytes13.100 time lag (s)CRWTU
4Output B-{{0:...}}Operation hours counter2 Bytes7.7 time (h)CRWTU
4Output B-{{0:...}}Status of continuous, 1byte1 Byte5.1 percentage (0..100%)CRT
4Output C-{{0:...}}Operation hours counter4 Bytes13.100 time lag (s)CRWTU
4Output C-{{0:...}}Operation hours counter2 Bytes7.7 time (h)CRWTU
4Output C-{{0:...}}Status of continuous, 1byte1 Byte5.1 percentage (0..100%)CRT
4Output D-{{0:...}}Operation hours counter4 Bytes13.100 time lag (s)CRWTU
4Output D-{{0:...}}Operation hours counter2 Bytes7.7 time (h)CRWTU
4Output D-{{0:...}}Status of continuous, 1byte1 Byte5.1 percentage (0..100%)CRT
4Output E-{{0:...}}Operation hours counter4 Bytes13.100 time lag (s)CRWTU
4Output E-{{0:...}}Operation hours counter2 Bytes7.7 time (h)CRWTU
4Output E-{{0:...}}Status of continuous, 1byte1 Byte5.1 percentage (0..100%)CRT
5Output A-{{0:...}}Scene1 Byte18.1 scene controlCW
5Output A-{{0:...}}Report fault1 Bit1.5 alarmCRT
5Output B-{{0:...}}Scene1 Byte18.1 scene controlCW
5Output B-{{0:...}}Report fault1 Bit1.5 alarmCRT
5Output C-{{0:...}}Scene1 Byte18.1 scene controlCW
5Output C-{{0:...}}Report fault1 Bit1.5 alarmCRT
5Output D-{{0:...}}Scene1 Byte18.1 scene controlCW
5Output D-{{0:...}}Report fault1 Bit1.5 alarmCRT
5Output E-{{0:...}}Scene1 Byte18.1 scene controlCW
5Output E-{{0:...}}Report fault1 Bit1.5 alarmCRT
6Output A-{{0:...}}Forced output1 Bit1.3 enableCW
6Output A-{{0:...}}Forced output2 Bit2.1 switch controlCW
6Output B-{{0:...}}Forced output1 Bit1.3 enableCW
6Output B-{{0:...}}Forced output2 Bit2.1 switch controlCW
6Output C-{{0:...}}Forced output1 Bit1.3 enableCW
6Output C-{{0:...}}Forced output2 Bit2.1 switch controlCW
6Output D-{{0:...}}Forced output1 Bit1.3 enableCW
6Output D-{{0:...}}Forced output2 Bit2.1 switch controlCW
6Output E-{{0:...}}Forced output1 Bit1.3 enableCW
6Output E-{{0:...}}Forced output2 Bit2.1 switch controlCW
7Output A-{{0:...}}Logic 11 Bit1.2 booleanCW
7Output B-{{0:...}}Logic 11 Bit1.2 booleanCW
7Output C-{{0:...}}Logic 11 Bit1.2 booleanCW
7Output D-{{0:...}}Logic 11 Bit1.2 booleanCW
7Output E-{{0:...}}Logic 11 Bit1.2 booleanCW
8Output A-{{0:...}}Logic 21 Bit1.2 booleanCW
8Output B-{{0:...}}Logic 21 Bit1.2 booleanCW
8Output C-{{0:...}}Logic 21 Bit1.2 booleanCW
8Output D-{{0:...}}Logic 21 Bit1.2 booleanCW
8Output E-{{0:...}}Logic 21 Bit1.2 booleanCW
54Room temperature controllerPower On/Off1 Bit1.1 switchCW
55Room temperature controllerExternal temperature sensor2 Bytes9.1 temperature (°C)CWTU
56Room temperature controllerBase setpoint adjustment2 Bytes9.1 temperature (°C)CW
56Room temperature controllerCurrent setpoint adjustment2 Bytes9.1 temperature (°C)CW
57Room temperature controllerSetpoint offset1 Bit1.7 stepCW
58Room temperature controllerFloat offset value2 Bytes9.2 temperature difference (K)CW
59Room temperature controllerSetpoint offset reset1 Bit1.15 resetCW
60Room temperature controllerHeating/Cooling mode1 Bit1.100 cooling/heatingCW
61Room temperature controllerOperation mode1 Byte20.102 HVAC modeCW
62Room temperature controllerComfort mode1 Bit1.3 enableCW
63Room temperature controllerEconomy mode1 Bit1.3 enableCW
64Room temperature controllerFrost/Heat protection mode1 Bit1.3 enableCW
65Room temperature controllerStandby mode1 Bit1.3 enableCW
66Room temperature controllerExtended comfort mode1 Bit1.16 acknowledgeCW
67Room temperature controllerFan automatic operation1 Bit1.3 enableCW
68Room temperature controllerWindow contact1 Bit1.19 window/doorCWTU
69Room temperature controllerPresence detector1 Bit1.18 occupancyCWTU
70Room temperature controllerActual temperature, status2 Bytes9.1 temperature (°C)CRT
71Room temperature controllerBase temperature setpoint, status2 Bytes9.1 temperature (°C)CRT
72Room temperature controllerSetpoint offset, status2 Bytes9.2 temperature difference (K)CRT
73Room temperature controllerCurrent temperature setpoint, status2 Bytes9.1 temperature (°C)CRT
74Room temperature controllerHeating/Cooling mode, status1 Bit1.100 cooling/heatingCRT
75Room temperature controllerOperation mode, status1 Byte20.102 HVAC modeCRT
76Room temperature controllerComfort mode, status1 Bit1.3 enableCRT
77Room temperature controllerEconomy mode, status1 Bit1.3 enableCRT
78Room temperature controllerFrost/Heat protection mode, status1 Bit1.3 enableCRT
79Room temperature controllerStandby mode, status1 Bit1.3 enableCRT
80Room temperature controllerHeating control value1 Bit1.1 switchCRT
80Room temperature controllerHeating control value1 Byte5.1 percentage (0..100%)CRT
80Room temperature controllerHeating/Cooling control value1 Bit1.1 switchCRT
80Room temperature controllerHeating/Cooling control value1 Byte5.1 percentage (0..100%)CRT
81Room temperature controllerCooling control value1 Bit1.1 switchCRT
81Room temperature controllerCooling control value1 Byte5.1 percentage (0..100%)CRT
82Room temperature controllerFan speed1 Byte5.100 fan stage (0..255)CWTU
82Room temperature controllerFan speed1 Byte5.1 percentage (0..100%)CWTU
83Room temperature controllerFan speed low1 Bit1.1 switchCWTU
84Room temperature controllerFan speed medium1 Bit1.1 switchCWTU
85Room temperature controllerFan speed high1 Bit1.1 switchCWTU
86Room temperature controllerFan speed off1 Bit1.1 switchCWTU
87Room temperature controllerAdditional heating control value1 Bit1.1 switchCRT
87Room temperature controllerAdditional heating control value1 Byte5.1 percentage (0..100%)CRT
87Room temperature controllerAdditional heating/cooling control value1 Bit1.1 switchCRT
87Room temperature controllerAdditional heating/cooling control value1 Byte5.1 percentage (0..100%)CRT
88Room temperature controllerAdditional cooling control value1 Bit1.1 switchCRT
88Room temperature controllerAdditional cooling control value1 Byte5.1 percentage (0..100%)CRT
89Room temperature controllerPower On/Off, status1 Bit1.1 switchCRT
90FanFan speed1 Bit1.1 switchCW
90FanFan speed1 Byte5.1 percentage (0..100%)CW
90FanFan speed1 Byte5.100 fan stage (0..255)CW
91FanFan speed 11 Bit1.1 switchCW
92FanFan speed 21 Bit1.1 switchCW
93FanFan speed 31 Bit1.1 switchCW
94FanStatus Fan On/Off1 Bit1.1 switchCRT
95FanStatus Fan speed1 Byte5.1 percentage (0..100%)CRT
95FanStatus Fan speed1 Byte5.100 fan stage (0..255)CRT
96FanStatus Fan speed 11 Bit1.1 switchCRT
97FanStatus Fan speed 21 Bit1.1 switchCRT
98FanStatus Fan speed 31 Bit1.1 switchCRT
99FanAutomatic function1 Bit1.3 enableCW
100FanStatus Automatic1 Bit1.3 enableCRT
101FanForced operation1 Bit1.3 enableCW
102FanControl value1 Byte5.1 percentage (0..100%)CW
102FanControl value 11 Byte5.1 percentage (0..100%)CW
103FanControl value 21 Byte5.1 percentage (0..100%)CW
104FanSwitching control value 1/21 Bit1.1 switchCW
105FanControl value fault1 Bit1.5 alarmCRT
106FanFan Limitation 11 Bit1.3 enableCW
107FanFan Limitation 21 Bit1.3 enableCW
108FanFan Limitation 31 Bit1.3 enableCW
109FanFan Limitation 41 Bit1.3 enableCW
110ValveControl value fault1 Bit1.5 alarmCRT
111ValveDisable,Heat1 Bit1.3 enableCW
111ValveDisable,Heat/Cool1 Bit1.3 enableCW
112ValveControl value, Heat1 Byte5.1 percentage (0..100%)CW
112ValveControl value, Heat1 Bit1.1 switchCW
112ValveControl value, Heat/Cool1 Bit1.1 switchCW
112ValveControl value, Heat/Cool1 Byte5.1 percentage (0..100%)CW
113ValveValve status, Heat1 Byte5.1 percentage (0..100%)CRT
113ValveValve status, Heat1 Bit1.1 switchCRT
113ValveValve status, Heat/Cool1 Bit1.1 switchCRT
113ValveValve status, Heat/Cool1 Byte5.1 percentage (0..100%)CRT
114ValveTrigger valve purge, Heat1 Bit1.3 enableCW
114ValveTrigger valve purge, Heat/Cool1 Bit1.3 enableCW
115ValveValve purge status, Heat1 Bit1.3 enableCRT
115ValveValve purge status, Heat/Cool1 Bit1.3 enableCRT
116ValveDisable,Cool1 Bit1.3 enableCW
117ValveControl value, Cool1 Byte5.1 percentage (0..100%)CW
117ValveControl value, Cool1 Bit1.1 switchCW
118ValveValve status, Cool1 Byte5.1 percentage (0..100%)CRT
118ValveValve status, Cool1 Bit1.1 switchCRT
119ValveTrigger valve purge, Cool1 Bit1.3 enableCW
120ValveValve purge status, Cool1 Bit1.3 enableCRT
121SceneScene1 Byte18.1 scene controlCW
122SceneHeating/Cooling mode1 Bit1.100 cooling/heatingCT
123SceneOperation mode1 Byte20.102 HVAC modeCT
Parameters (344)
ParameterTypeDefault
Operation and send delay after bus recovery [5..250]unsignedInt 5…25010
Send cycle of "In operation" telegram [1..240,0=inactive]unsignedInt 0…2400
Manual operationunsignedInt 0…11
Manual to automatic bylistOnly long press
Delay time [10..6000]unsignedInt 10…600010
Central control for switch functionunsignedInt 0…10
Input interfaceunsignedInt 0…10
Input 1listTemperature probe(NTC 10K)
Input 2listDisable
When bus failure,Fan speed islistUnchange
When bus recovery,Fan speed islistUnchange
After downloading,Fan speed islistOff
Forced operation on object valuelist1=Force/0=Cancel
Behaviour on forced operationlistUnchange
Time mode for function OnlistSwitch Delay
Delay time [1..65535]unsignedInt 1…6553510
Minimum time [1..65535]unsignedInt 1…6553510
Time mode for function OfflistSwitch Delay
Fan speeds on 2 limitunsignedInt 0…10
Fan operation modelistChangeover switch
Delay between fan speed switchover [50..5000]unsignedInt 50…5000500
Object datatype of 1byte fan speedlistPercentage (DPT_5.001)
Min.threshold value for Fan speed 1list33
Min.threshold value for Fan speed 2list67
Min.threshold value for Fan speed 3list100
Min.threshold value for Fan speed 1unsignedInt 0…2551
Min.threshold value for Fan speed 2unsignedInt 1…2552
Min.threshold value for Fan speed 3unsignedInt 1…2553
Forced operation functionunsignedInt 0…10
Limitation on forced operationlistUnchange
Auto. operation functionunsignedInt 0…10
Obj. "Switch speed x " 1bit functionunsignedInt 0…10
Delay time for function Off [0..65535]unsignedInt 0…655350
Starting characteristic of fanunsignedInt 0…11
Switch On over fan speedlist1
Minimum time in switch [1..65535]unsignedInt 1…6553510
Auto.operation on object valuelist1=Auto/0=Cancel
State of Auto.operation after startuplistCancel
Automatically enable auto.operationunsignedInt 0…10
Enable auto.operation after[10..6000]unsignedInt 10…6000100
Min.threshold value Off<->speed 1 [0..255]unsignedInt 0…25580
Min.threshold value speed 1<->speed 2 [1..255]unsignedInt 1…255150
Min.threshold value speed 2<->speed 3 [1..255]unsignedInt 1…255200
Hysteresis threshold value in +/-[0..50]unsignedInt 0…5010
Minimum time in fan speed [0..65535]unsignedInt 0…6553510
Controller fromlistExternal controller->1 control value
Select bylistControl value with switching object
Monitoring control valueunsignedInt 0…11
Monitoring period of control value [10..65535]unsignedInt 10…65535120
Reply mode of Obj."Control value fault"listRespond after change
Control value after fault occurs [0..100]unsignedInt 0…1000
Reply mode of Obj. "Status Fan On/Off"(1bit)listRespond after change
Reply mode of Obj. "Status Automatic"(1bit)listRespond after change
Reply mode of Obj. "Status Fan speed x"(1bit)listRespond after change
Reply mode of Obj. "Status Fan speed"(1byte)listRespond after change
Status value for Fan speed 1list33
Status value for Fan speed 2list67
Status value for Fan speed 3list100
Status value for Fan speed 1unsignedInt 1…2551
Status value for Fan speed 2unsignedInt 1…2552
Status value for Fan speed 3unsignedInt 1…2553
HVAC control modelistHeating and Cooling
Valve mode and drive interfacelistDisable
Observe reversing timelist400ms
If bus failure, valve positionlistUnchange
If bus recovery, valve positionlistUnchange
Valve control time 0%->100% [50..6000]unsignedInt 50…6000100
Automatic adjust valve positionunsignedInt 0…10
Number of valve control up to adjust [1..65535]unsignedInt 1…65535200
Correct Valve characteristic curveunsignedInt 0…10
Min. controller value for closed valve [0..100]unsignedInt 0…1000
Max. controller value for fully opened valve [0..100]unsignedInt 0…100100
Lower valve position for opening [0..100]unsignedInt 0…1000
Upper valve position for opening [0..100]unsignedInt 0…100100
Reply mode for valve statuslistRespond after change
Object type of valve statuslist1byte
Object value with valve position >0list1
Valve typelistNormal(de-energised closed)
PWM cycle time [10..6000]unsignedInt 10…6000120
Valve purge functionunsignedInt 0…10
Duration of valve purge time [1..255]unsignedInt 1…25510
Automatic valve purgeunsignedInt 0…10
Purge Cycle in weeks [1..12]unsignedInt 1…121
Reply mode for valve purge status(1bit)listRespond after change
"Disable heating" object functionunsignedInt 0…10
Trigger object valuelist0=Disable/1=Enable
"Disable cooling" object functionunsignedInt 0…10
HVAC Systemlist4 pipes system
"Disable heating/cooling" object functionunsignedInt 0…10
Number of control valuelist2 control value
Monitoring period of control value [10..65535]unsignedInt 10…6553560
Fan type and drive interfacelistOne level->Relay control(CH A)
Output voltage for fan speed 1 [1..20]unsignedInt 1…205
Output voltage for fan speed 2 [1..20]unsignedInt 1…2010
Output voltage for fan speed 3 [1..20]unsignedInt 1…2015
Output voltage for fan speed [1..20]unsignedInt 1…205
If fan drive interface does not use output A,B&C, they serve as switch outputslist
If fan drive interface does not use output B&C, they serve as switch outputslist
If fan drive interface does not use output C, it serves as switch outputlist
Behavior from fan off to on when the valve is starting from fully close to openlistSwitch on immediately
Delay time [30..450]unsignedInt 3…45030
Limitation functionunsignedInt 0…10
Fan with limitation 1listDisable
Fan with limitation 2listDisable
Fan with limitation 3listDisable
Fan with limitation 4listDisable
Min. output voltage for fan speedlist0
Max. output voltage for fan speedlist10.0
Switch On over fan speedunsignedInt 1…10030
Fan speed for function OnunsignedInt 1…10030
Room temperature controllerunsignedInt 0…10
Room temperature reference fromlistLocal sensor(Input 1)
Period for request external sensor [0...255,0=inactive]unsignedInt 0…25510
Combination ratiolist50% Local to 50% External
Send temperature when the result change bylist1.0
Cyclically send temperature [0...255,0=inactive]unsignedInt 0…2550
Control value after temp. error[0..100] (if 2-point control, set value '0'=0, set value '>0'=1)unsignedInt 0…1000
Room temperature control modelistHeating
Heating/Cooling switchoverlistVia object
Heating/Cooling status after downloadlistHeating
Heating/Cooling status after voltage recoverylistAs before voltage failure
Room temperature control systemlist4 pipes system
Operation modeunsignedInt 0…10
Initial setpoint temperaturelist20.0
Temperature error tip_setpoint/MaxunsignedInt 0…10
Temperature error tip_setpoint/MinunsignedInt 0…10
Upper dead zonelist2.0
Lower dead zonelist2.0
Controller status after downloadlistComfort mode
Controller status after voltage recoverylistAs before voltage failure
Extended comfort mode [0..255,0=inactive]unsignedInt 0…2550
1 bit object function for operation modeunsignedInt 0…10
1 bit object for standby modeunsignedInt 0…11
Fan speed auto.control functionunsignedInt 0…10
Window contact input functionunsignedInt 0…10
Delay for window contact [0..65535]unsignedInt 0…6553515
Controller mode for open windowlistFrost/heat protection
Bus presence detector functionunsignedInt 0…10
Setpoint method for operating modelistAbsolute
Base setpoint temperaturelist20.0
Additional setpoint offset for setpoint adjustmentunsignedInt 0…10
Step of setpoint offsetlist0.5K
Min. setpoint offset [-10..0]signedInt -10…0-5
Max. setpoint offset [0..10]unsignedInt 0…105
Reduced heating in standby mode [0..10]list2
Reduced heating in economy mode [0..10]list4
Setpoint temperature in frost protection mode [5..10]list7
Increased cooling in standby mode [0..10]list2
Increased cooling in economy mode [0..10]list4
Setpoint temperature in heat protection mode [30..37]list35
Min. setpoint temperature [5..37]list10
Max. setpoint temperature [5..37]list32
Setpoint temperature in comfort mode [5..37]list21
Setpoint temperature in standby mode [5..37]list19
Setpoint temperature in economy mode [5..37]list17
Setpoint temperature in comfort mode [5..37]list23
Setpoint temperature in standby mode [5..37]list25
Setpoint temperature in economy mode [5..37]list27
Minimum zone between heating and cooling setpointlist2.0
Type of heating controllistSwitching On/Off(use 2-point control)
Invert control valueunsignedInt 0…10
Lower Hysteresis [0..200]unsignedInt 0…20010
Upper Hysteresis [0..200]unsignedInt 0…20010
PWM cycle time [1..255]unsignedInt 1…25515
Heating speedlistHot water heating(5K/150min)
Proportional range [10..100]unsignedInt 0…10040
Reset time [0..255]unsignedInt 0…255150
Send control value on change by [0..100,0=inactive]unsignedInt 0…1005
Cyclically send control value [0..255]unsignedInt 0…25510
Additional heatingunsignedInt 0…10
Control typelist1bit
Temperature difference to switch on additional heating [-100..-5]signedInt -100…-5-25
Hysteresis to switch off additional heating [-20..-1]signedInt -20…-1-5
Cyclically send control value [0..255]unsignedInt 0…2550
Type of cooling controllistSwitching On/Off(use 2-point control)
Cooling speedlistCooling ceiling (5K/240min)
Proportional range [10..100]unsignedInt 10…10040
Additional coolingunsignedInt 0…10
Temperature difference to switch on additional cooling [5..100]unsignedInt 5…10025
Hysteresis to switch off additional cooling [1..20]unsignedInt 1…205
Type of heating/cooling controllistSwitching On/Off(use 2-point control)
Additional heating/coolingunsignedInt 0…10
Auto. operation on object valuelistAuto=1/Man.=0
Output value for fan speed lowunsignedInt 1…2551
Output value for fan speed mediumunsignedInt 1…2552
Output value for fan speed highunsignedInt 1…2553
Output value for fan speed lowunsignedInt 1…10033
Output value for fan speed mediumunsignedInt 1…10067
Output value for fan speed highunsignedInt 1…100100
1 bit object function for fan speedunsignedInt 0…10
1 bit object for fan speed offunsignedInt 0…10
Threshold value speed OFF<-->low [0..255]unsignedInt 0…25580
Threshold value speed low<-->medium [1..255]unsignedInt 1…255150
Threshold value speed medium<-->high [1..255]unsignedInt 1…255200
Temperature difference speed OFF<-->low [0..200]unsignedInt 0…20020
Temperature difference speed low<-->medium [1..200]unsignedInt 1…20030
Temperature difference speed medium<-->high [1..200]unsignedInt 1…20040
Hysteresis temperature difference in [0..50]unsignedInt 0…5010
Minimum time in fan speed [0..65535]unsignedInt 0…6553560
Room temperature reference fromlistLocal sensor(Input 2)
Min.threshold value 1 [0..255]unsignedInt 0…25580
Min.threshold value 2 [1..255]unsignedInt 1…255150
Min.threshold value 3 [1..255]unsignedInt 1…255200
Fan speed for min. threshold value 1 [1..100]unsignedInt 1…10030
Fan speed for min. threshold value 2 [1..100]unsignedInt 1…10060
Fan speed for min. threshold value 3 [1..100]unsignedInt 1…10080
Limitation 1 lower limitunsignedInt 0…1000
Limitation 2 lower limitunsignedInt 0…1000
Limitation 3 lower limitunsignedInt 0…1000
Limitation 4 lower limitunsignedInt 0…1000
Controller fromlistDisable
If valve drive interface does not use output D, they serve as switch outputslist
If valve drive interface does not use output E, they serve as switch outputslist
If valve drive interface does not use output D&E, they serve as switch outputslist
Scene functionunsignedInt 0…10
Overwrite scene stored values during downloadunsignedInt 0…10
1>Assignment scene number (1-64 is active,0 is no assignment)unsignedInt 0…640
Operation modelistComfort mode
Fan speedlistUnchange
Heating/CoolinglistUnchange
2>Assignment scene number (1-64 is active,0 is no assignment)unsignedInt 0…640
3>Assignment scene number (1-64 is active,0 is no assignment)unsignedInt 0…640
4>Assignment scene number (1-64 is active,0 is no assignment)unsignedInt 0…640
5>Assignment scene number (1-64 is active,0 is no assignment)unsignedInt 0…640
6>Assignment scene number (1-64 is active,0 is no assignment)unsignedInt 0…640
7>Assignment scene number (1-64 is active,0 is no assignment)unsignedInt 0…640
8>Assignment scene number (1-64 is active,0 is no assignment)unsignedInt 0…640
When bus failure,Fan speed islistOff
When bus recovery,Fan speed islistOff
TemperaturelistUnchange
If bus failure, valve positionlist
Min.temperature difference Off<->speed 1 [0..200]unsignedInt 0…20020
Min.temperature difference speed 1<->speed 2 [1..200]unsignedInt 1…20030
Min.temperature difference speed 2<->speed 3 [1..200]unsignedInt 1…20040
Min.temperature difference 1 [0..200]unsignedInt 0…20020
Min.temperature difference 2 [1..200]unsignedInt 1…20030
Min.temperature difference 3 [1..200]unsignedInt 1…20040
Fan speed for min. temperature difference 1 [1..100]unsignedInt 1…10030
Fan speed for min. temperature difference 2 [1..100]unsignedInt 1…10060
Fan speed for min. temperature difference 3 [1..100]unsignedInt 1…10080
Min.threshold value Off<->On[1..255]unsignedInt 1…25580
Min.temperature difference Off<->On[1..200]unsignedInt 1…20020
Fan speed control methodlistThree level according to control value
Limitation 1 upper limitunsignedInt 0…100100
Limitation 2 upper limitunsignedInt 0…100100
Limitation 3 upper limitunsignedInt 0…100100
Limitation 4 upper limitunsignedInt 0…100100
FunctionlistBI: Switch sensor
Description (max 30char.)text
B value of temperature sensor (must refer to the characteristic of component)list3950
Temperature calibrationlist0.0
Cyclically send temperature [0...255]unsignedInt 0…2550
Reply error of sensor measurementlistNo respond
Object value of errorlist0=no error/1=error
Lower threshold value for error reportlist0
Upper threshold value for error reportlist60
Distinction between short and long operationunsignedInt 0…10
Reaction on close the contactlistTOGGLE
Reaction on open the contactlistNo reaction
Send object value after voltage recovery (valid if reaction is not toggle)unsignedInt 0…10
Number of objectslist1
Long operation after [3..25]unsignedInt 3…255
Connected contact typelistNormally open
Reaction on short operationlistTOGGLE
Reaction on long operationlistNo reaction
Disable functionlistDisable
Reaction on close the contactlistRecall scene
8 bit scene numberlistScene No.2
Reaction on short operationlistRecall scene
Reaction on close the contactlistSend Value
String (14byte) valuetextHello, world !
Send object value after voltage recoveryunsignedInt 0…10
Reaction on short operationlistSend Value
Interval of tele. cyclic send [0..60000] (0=send once)unsignedInt 0…600000
Behaviour from disable to enable (valid if reaction is not toggle)listNo reaction
Work mode of the channel islistSwitch actuator
Central function of channelunsignedInt 0…10
If bus recovery, output status islistUnchange
If bus failure, output status islistUnchange
After downloading,output status islistContact open
Object value of "switch" after bus recoverylist0
Set the reply mode of switch statuslistRespond after change
Object value of switch statuslist1=contact close;0=contact open
Output status for the telegram "1" (telegram "0" is opposite of selection)listContact close
Extension functionunsignedInt 0…10
Function of "Time"unsignedInt 0…10
Function of "Logic"unsignedInt 0…10
Function of "Scene"unsignedInt 0…10
Function of "Forced"unsignedInt 0…10
Force operation typelist1Bit
Output status if forced operationlistUnchange
Function of "Operation hours counter"unsignedInt 0…10
Object datatype of "Operation hours counter"list4 byte Value in s(DPT13.100)
Cyclically send counter value in [0...100] (0 = not send,only for reading)unsignedInt 0…1000
Type of time functionlistDelay
Delay for switch on(contact close) --(0...240)unsignedInt 0…2400
--(0...59)unsignedInt 0…590
Delay for switch off(contact open) --(0...240)unsignedInt 0…2400
Duration of staircase lighting --(0...1000)unsignedInt 0…10001
Control mode of staircase lightinglistStart with "1",Stop with"0"
During the lighting time,if receive the "start" telegramlistRestart duration of staircase lighting
Modify the duration via object [0...60059]unsignedInt 0…10
Duration of switch on(contact close) --(0...240)unsignedInt 0…2400
Duration of switch off(contact open) --(0...240)unsignedInt 0…2400
Number of ON-implused [1...255,0=no limited]unsignedInt 0…2550
Output status after flashinglistUnchange
Control mode of flashinglistStart with "1",Stop with"0"
Enable input 0unsignedInt 0…10
Input 0 reverseunsignedInt 0…10
The input 1 of logicunsignedInt 0…10
Logic function typelistAND
Input 1 reverseunsignedInt 0…10
Invert result(if no,1=contact close,0=contact open;while yes is opposite)unsignedInt 0…10
Value of input1 after bus recoverylist0
The input 2 of logicunsignedInt 0…10
Input 2 reverseunsignedInt 0…10
Value of input2 after bus recoverylist0
Overwrite scene stored values during downloadunsignedInt 0…11
1> channel is assigned to (1...64,0=no assignment)unsignedInt 0…640
Output status islistContact open
2> channel is assigned to (1...64,0=no assignment)unsignedInt 0…640
3> channel is assigned to (1...64,0=no assignment)unsignedInt 0…640
4> channel is assigned to (1...64,0=no assignment)unsignedInt 0…640
5> channel is assigned to (1...64,0=no assignment)unsignedInt 0…640
6> channel is assigned to (1...64,0=no assignment)unsignedInt 0…640
7> channel is assigned to (1...64,0=no assignment)unsignedInt 0…640
8> channel is assigned to (1...64,0=no assignment)unsignedInt 0…640
Valve typelistNormal (de-energised closed)
If bus recovery, valve positionlist0%[Closed]
PWM cycle time for continuous [60...65535]unsignedInt 60…65535120
Control typelist1bit (on-off control or PWM)
Reply the status for continuous controllistNo reply
Reply the status of contact statelistYes, 1=contact close; 0=contact open
Function of monitoringunsignedInt 0…11
Cyclic monitoring control value [0…65535]unsignedInt 0…65535120
Valve position during faultlistUnchange
Report fault statusunsignedInt 0…11
Function of forced operationunsignedInt 0…10
Valve position during forced operationlistUnchange
Output A SwitchunsignedInt 0…10
Output B SwitchunsignedInt 0…10
Output C SwitchunsignedInt 0…10
Output D SwitchunsignedInt 0…10
Output E SwitchunsignedInt 0…10

Version history

ApplicationApp noFingerprintFirst seenSizeFile
0-10V Fan Coil Actuator with Secure/00E4 2.0 2.0 latest$00E4A3212026-11-25230 KBDownload

About this file

This is the official ETS product database for the GVS 0-10V Fan Coil Actuator with Secure (AFVFT-07/10.S), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.