| 1 | [Out] Switch Input | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 2 | [Out] Relative Control Input | Dimming control | 4 Bit | 3.7 dimming control | CW |
| 3 | [Out] Absolute Dimming Input | Dimming value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 4 | [Out] Timer Start/Stop Input | 1 = Start, 0 = Stop | 1 Bit | 1.1 switch | CW |
| 5 | [Out] Forced Input | Forced control | 2 Bit | 2.3 enable control | CW |
| 6 | [Out] Scene Number Input | Scene Number control | 1 Byte | 18.1 scene control | CW |
| 7 | [Out] Switch Feedback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 8 | [Out] Actual Dimming Value Feedback | Dimming value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 9 | [Out] Dimming Speed (from 1% to 100%) | 100 msec units | 2 Bytes | 7.4 time (100 ms) | CW |
| 10 | [Out] Load Detected Output | Load type | 1 Byte | 20.610 load type detection | CT |
| 11 | [Out] Dimmer Temperature | Temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 12 | [Out] High Temperature Alarm | 1 = High Temperature | 1 Bit | 1.5 alarm | CT |
| 13 | [Out] Critical Temperature Alarm | 1 = Critical Temperature | 1 Bit | 1.5 alarm | CT |
| 14 | [Out] Block Dimmer Input | 1 = Blocked, 0 = Not blocked | 1 Bit | 1.3 enable | CW |
| 15 | [Out] Dimmer Status Output | Dimmer Status | 2 Bytes | 7.1 pulses | CT |
| 16 | [Aux] Switch On/Off Output Short press | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 16 | [Aux] 1 Byte value Output | 1 Byte Value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 16 | [Aux] Scene Number Output | Scene Number control | 1 Byte | 18.1 scene control | CT |
| 16 | [Aux] 2 Bits value Output | 2 Bits value | 2 Bit | 2.3 enable control | CT |
| 16 | [Aux] 1 Bit value Output | 1 Bit Value | 1 Bit | 1.1 switch | CT |
| 16 | [Aux] 2 Bytes value Output | 2 bytes value | 2 Bytes | 7.1 pulses | CT |
| 16 | [Aux] 4 Bytes value Output | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 17 | [Aux] Dimming Up-Down Output | Dimming control | 4 Bit | 3.7 dimming control | CT |
| 17 | [Aux] 2 Bits value Output Long press | 2 Bits value | 2 Bit | 2.1 switch control | CT |
| 17 | [Aux] 1 Byte value Output Long press | 1 Byte Value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 17 | [Aux] 2 Bytes value Output Long press | 2 bytes value | 2 Bytes | 7.1 pulses | CT |
| 17 | [Aux] 4 Bytes value Output Long press | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 17 | [Aux] Switch On/Off Output Long press | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 17 | [Aux] 1 Bit value Output Long press | 1 Bit Value | 1 Bit | 1.1 switch | CT |
| 18 | [Aux] Switch Feedback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 19 | [Out] Sequential Operation | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 20 | [Out] Sequential Operation Feedback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 21 | GODUMMY1_0 | GODUMMY1_0 | 4 Bytes | 12.1 counter pulses (unsigned) | CWT |
| 22 | GODUMMY2_0 | GODUMMY2_0 | 4 Bytes | 12.1 counter pulses (unsigned) | CWT |
| 23 | GODUMMY3_0 | GODUMMY3_0 | 4 Bytes | 12.1 counter pulses (unsigned) | CWT |
| 24 | GODUMMY4_0 | GODUMMY4_0 | 4 Bytes | 12.1 counter pulses (unsigned) | CWT |
| 25 | GODUMMY5_0 | GODUMMY5_0 | 4 Bytes | 12.1 counter pulses (unsigned) | CWT |
| 26 | GODUMMY6_0 | GODUMMY6_0 | 4 Bytes | 12.1 counter pulses (unsigned) | CWT |
| 27 | GODUMMY7_0 | GODUMMY7_0 | 4 Bytes | 12.1 counter pulses (unsigned) | CWT |
| 28 | GODUMMY8_0 | GODUMMY8_0 | 4 Bytes | 12.1 counter pulses (unsigned) | CWT |
| 29 | GODUMMY9_0 | GODUMMY9_0 | 4 Bytes | 12.1 counter pulses (unsigned) | CWT |
| 30 | GODUMMY10_0 | GODUMMY10_0 | 4 Bytes | 12.1 counter pulses (unsigned) | CWT |
| 40 | [In1] Disable Temperature Functionality | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 40 | [In1] Disable Input | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 41 | [In1] 4 Bytes value on press | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 41 | [In1] Stop / Step | 0 = Step Up, 1 = Step Down | 1 Bit | 1.7 step | CT |
| 41 | [In1] Counter direction | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 41 | [In1] 1 Bit value on press | Bit value | 1 Bit | 1.11 state | CT |
| 41 | [In1] Switch | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 41 | [In1] Scene control 8 Bits | Scene Control | 1 Byte | 18.1 scene control | CT |
| 41 | [In1] 2 Bytes signed value on press | 2 Bytes signed value | 2 Bytes | 8.1 pulses difference | CT |
| 41 | [In1] 2 Bytes floating value on press | 2 Bytes floating value | 2 Bytes | 9.1 temperature (°C) | CT |
| 41 | [In1] 1 Byte value on press | Byte value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 41 | [In1] 2 Bits value on press | 2 Bits value | 2 Bit | 2.1 switch control | CT |
| 41 | [In1] Temperature value | Temperature value | 2 Bytes | 9.1 temperature (°C) | CT |
| 41 | [In1] Scene 1 Bit | 0 = Scene 1, 1 = Scene 2 | 1 Bit | 1.22 scene | CT |
| 41 | [In1] 2 Bytes value on press | 2 Bytes value | 2 Bytes | 7.1 pulses | CT |
| 41 | [In1] Dimming Value | Dimming value 0-100% | 1 Byte | 5.1 percentage (0..100%) | CT |
| 41 | [In1] Scene number | Scene Number | 1 Byte | 17.1 scene number | CT |
| 41 | [In1] HVAC mode | HVAC mode | 1 Byte | 20.102 HVAC mode | CT |
| 42 | [In1] 2 Bytes floating value on Long press | 2 Bytes floating value | 2 Bytes | 9.1 temperature (°C) | CT |
| 42 | [In1] Reset Counter | 0 = No action, 1 = Reset | 1 Bit | 1.15 reset | CW |
| 42 | [In1] 4 Bytes value on Long press | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 42 | [In1] Move | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CT |
| 42 | [In1] Dimming Control | Dimming control | 4 Bit | 3.7 dimming control | CT |
| 42 | [In1] 2 Bytes value on Long press | 2 Bytes value | 2 Bytes | 7.1 pulses | CT |
| 42 | [In1] 1 Bit value on Long press | Bit value | 1 Bit | 1.11 state | CT |
| 42 | [In1] Sensor not connected | 0 = Sensor Ok, 1 = Sensor not connected | 1 Bit | 1.11 state | CT |
| 42 | [In1] 2 Bytes signed value on Long press | 2 Bytes signed value | 2 Bytes | 8.1 pulses difference | CT |
| 42 | [In1] Long Switch | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 42 | [In1] Save Scene | 0 = No action, 1 = Save Scene | 1 Bit | 1.3 enable | CW |
| 42 | [In1] Switch 2 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 42 | [In1] 1 Byte value on Long press | Byte value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 42 | [In1] 2 Bits value Long press | 2 Bits value | 2 Bit | 2.1 switch control | CT |
| 42 | [In1] Switch [2] | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 42 | [In1] Dimming Value [2] | Dimming value 0-100% | 1 Byte | 5.1 percentage (0..100%) | CT |
| 42 | [In1] Scene number [2] | Scene Number | 1 Byte | 17.1 scene number | CT |
| 42 | [In1] HVAC mode [2] | HVAC mode | 1 Byte | 20.102 HVAC mode | CT |
| 43 | [In1] Switch Feedback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 43 | [In1] Request Counter | 1 = Trigger | 1 Bit | 1.17 trigger | CW |
| 43 | [In1] Over-Heating Output | 1 = Over-Heating, 0 = No Over-Heating | 1 Bit | 1.5 alarm | CT |
| 43 | [In1] Switch 3 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 44 | [In1] Switch 4 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 44 | [In1] Long Switch Feedback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 44 | [In1] Counter 32 Bits | Counter (0-4.294.967.295) | 4 Bytes | 12.1 counter pulses (unsigned) | CRT |
| 44 | [In1] Over-Cooling Output | 1 = Over-Cooling, 0 = No Over-Cooling | 1 Bit | 1.5 alarm | CT |
| 44 | [In1] Counter 8 Bits | Counter (0-255) | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 44 | [In1] Counter 16 Bits | Counter (0-65535) | 2 Bytes | 7.1 pulses | CRT |
| 44 | [In1] Switch [3] | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 44 | [In1] Dimming value [3] | Dimming value 0-100% | 1 Byte | 5.1 percentage (0..100%) | CT |
| 44 | [In1] Scene number [3] | Scene Number | 1 Byte | 17.1 scene number | CT |
| 44 | [In1] HVAC mode [3] | HVAC mode | 1 Byte | 20.102 HVAC mode | CT |
| 45 | [In1] Switch 5 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 46 | [In1] Increase/Decrease | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 46 | [In1] Save Scene | 0 = Scene 1, 1 = Scene 2 | 1 Bit | 1.3 enable | CT |
| 47 | [In2] Disable Input | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 47 | [In2] Disable Temperature Functionality | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 48 | [In2] 2 Bytes signed value on press | 2 Bytes signed value | 2 Bytes | 8.1 pulses difference | CT |
| 48 | [In2] Temperature value | Temperature value | 2 Bytes | 9.1 temperature (°C) | CT |
| 48 | [In2] 1 Bit value on press | Bit value | 1 Bit | 1.11 state | CT |
| 48 | [In2] 2 Bytes value on press | 2 Bytes value | 2 Bytes | 7.1 pulses | CT |
| 48 | [In2] 1 Byte value on press | Byte value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 48 | [In2] Switch | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 48 | [In2] 2 Bytes floating value on press | 2 Bytes floating value | 2 Bytes | 9.1 temperature (°C) | CT |
| 48 | [In2] Counter direction | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 48 | [In2] Scene 1 Bit | 0 = Scene 1, 1 = Scene 2 | 1 Bit | 1.22 scene | CT |
| 48 | [In2] 2 Bits value on press | 2 Bits value | 2 Bit | 2.1 switch control | CT |
| 48 | [In2] Stop / Step | 0 = Step Up, 1 = Step Down | 1 Bit | 1.7 step | CT |
| 48 | [In2] 4 Bytes value on press | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 48 | [In2] Scene control 8 Bits | Scene Control | 1 Byte | 18.1 scene control | CT |
| 48 | [In2] Dimming Value | Dimming value 0-100% | 1 Byte | 5.1 percentage (0..100%) | CT |
| 48 | [In2] Scene number | Scene Number | 1 Byte | 17.1 scene number | CT |
| 48 | [In2] HVAC mode | HVAC mode | 1 Byte | 20.102 HVAC mode | CT |
| 49 | [In2] 1 Byte value on Long press | Byte value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 49 | [In2] Dimming Control | Dimming control | 4 Bit | 3.7 dimming control | CT |
| 49 | [In2] Long Switch | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 49 | [In2] Save Scene | 0 = No action, 1 = Save Scene | 1 Bit | 1.3 enable | CW |
| 49 | [In2] Switch 2 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 49 | [In2] 1 Bit value on Long press | Bit value | 1 Bit | 1.11 state | CT |
| 49 | [In2] Reset Counter | 0 = No action, 1 = Reset | 1 Bit | 1.15 reset | CW |
| 49 | [In2] Move | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CT |
| 49 | [In2] 2 Bytes floating value on Long press | 2 Bytes floating value | 2 Bytes | 9.1 temperature (°C) | CT |
| 49 | [In2] 2 Bytes value on Long press | 2 Bytes value | 2 Bytes | 7.1 pulses | CT |
| 49 | [In2] 2 Bytes signed value on Long press | 2 Bytes signed value | 2 Bytes | 8.1 pulses difference | CT |
| 49 | [In2] 4 Bytes value on Long press | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 49 | [In2] Sensor not connected | 0 = Sensor Ok, 1 = Sensor not connected | 1 Bit | 1.11 state | CT |
| 49 | [In2] 2 Bits value on Long press | 2 Bits value | 2 Bit | 2.1 switch control | CT |
| 49 | [In2] Switch [2] | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 49 | [In2] Dimming Value [2] | Dimming value 0-100% | 1 Byte | 5.1 percentage (0..100%) | CT |
| 49 | [In2] Scene number [2] | Scene Number | 1 Byte | 17.1 scene number | CT |
| 49 | [In2] HVAC mode [2] | HVAC mode | 1 Byte | 20.102 HVAC mode | CT |
| 50 | [In2] Request Counter | 1 = Trigger | 1 Bit | 1.17 trigger | CW |
| 50 | [In2] Over-Heating Output | 1 = Over-Heating, 0 = No Over-Heating | 1 Bit | 1.5 alarm | CT |
| 50 | [In2] Switch Feedback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 50 | [In2] Switch 3 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 51 | [In2] Switch 4 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 51 | [In2] Counter 32 Bits | Counter (0-4.294.967.295) | 4 Bytes | 12.1 counter pulses (unsigned) | CRT |
| 51 | [In2] Over-Cooling Output | 1 = Over-Cooling, 0 = No Over-Cooling | 1 Bit | 1.5 alarm | CT |
| 51 | [In2] Counter 8 Bits | Counter (0-255) | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 51 | [In2] Counter 16 Bits | Counter (0-65535) | 2 Bytes | 7.1 pulses | CRT |
| 51 | [In2] Long Switch Feedback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 51 | [In2] Switch [3] | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 51 | [In2] Dimming Value [3] | Dimming value 0-100% | 1 Byte | 5.1 percentage (0..100%) | CT |
| 51 | [In2] Scene number [3] | Scene Number | 1 Byte | 17.1 scene number | CT |
| 51 | [In2] HVAC mode [3] | HVAC mode | 1 Byte | 20.102 HVAC mode | CT |
| 52 | [In2] Switch 5 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 53 | [In2] Save Scene | 0 = Scene 1, 1 = Scene 2 | 1 Bit | 1.3 enable | CT |
| 53 | [In2] Increase/Decrease | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 54 | [In3] Disable Temperature Functionality | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 54 | [In3] Disable Input | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 55 | [In3] Scene control 8 Bits | Scene Control | 1 Byte | 18.1 scene control | CT |
| 55 | [In3] Switch | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 55 | [In3] 1 Bit value on press | Bit value | 1 Bit | 1.11 state | CT |
| 55 | [In3] 1 Byte value on press | Byte value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 55 | [In3] 2 Bytes value on press | 2 Bytes value | 2 Bytes | 7.1 pulses | CT |
| 55 | [In3] 2 Bits value on press | 2 Bits value | 2 Bit | 2.1 switch control | CT |
| 55 | [In3] Stop / Step | 0 = Step Up, 1 = Step Down | 1 Bit | 1.7 step | CT |
| 55 | [In3] 2 Bytes signed value on press | 2 Bytes signed value | 2 Bytes | 8.1 pulses difference | CT |
| 55 | [In3] Scene 1 Bit | 0 = Scene 1, 1 = Scene 2 | 1 Bit | 1.22 scene | CT |
| 55 | [In3] Counter direction | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 55 | [In3] 4 Bytes value on press | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 55 | [In3] Temperature value | Temperature value | 2 Bytes | 9.1 temperature (°C) | CT |
| 55 | [In3] 2 Bytes floating value on press | 2 Bytes floating value | 2 Bytes | 9.1 temperature (°C) | CT |
| 55 | [In3] Dimming Value | Dimming value 0-100% | 1 Byte | 5.1 percentage (0..100%) | CT |
| 55 | [In3] Scene number | Scene Number | 1 Byte | 17.1 scene number | CT |
| 55 | [In3] HVAC mode | HVAC mode | 1 Byte | 20.102 HVAC mode | CT |
| 56 | [In3] 2 Bytes signed value on Long press | 2 Bytes signed value | 2 Bytes | 8.1 pulses difference | CT |
| 56 | [In3] Reset Counter | 0 = No action, 1 = Reset | 1 Bit | 1.15 reset | CW |
| 56 | [In3] 2 Bits value on Long press | 2 Bits value | 2 Bit | 2.1 switch control | CT |
| 56 | [In3] Save Scene | 0 = No action, 1 = Save Scene | 1 Bit | 1.3 enable | CW |
| 56 | [In3] Long Switch | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 56 | [In3] 1 Byte value on Long press | Byte value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 56 | [In3] 2 Bytes value on Long press | 2 Bytes value | 2 Bytes | 7.1 pulses | CT |
| 56 | [In3] Dimming Control | Dimming control | 4 Bit | 3.7 dimming control | CT |
| 56 | [In3] 1 Bit value on Long press | Bit value | 1 Bit | 1.11 state | CT |
| 56 | [In3] 4 Bytes value on Long press | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 56 | [In3] 2 Bytes floating value on Long press | 2 Bytes floating value | 2 Bytes | 9.1 temperature (°C) | CT |
| 56 | [In3] Switch 2 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 56 | [In3] Sensor not connected | 0 = Sensor Ok, 1 = Sensor not connected | 1 Bit | 1.11 state | CT |
| 56 | [In3] Move | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CT |
| 56 | [In3] Switch [2] | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 56 | [In3] Dimming Value [2] | Dimming value 0-100% | 1 Byte | 5.1 percentage (0..100%) | CT |
| 56 | [In3] Scene number [2] | Scene Number | 1 Byte | 17.1 scene number | CT |
| 56 | [In3] HVAC mode [2] | HVAC mode | 1 Byte | 20.102 HVAC mode | CT |
| 57 | [In3] Switch 3 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 57 | [In3] Request Counter | 1 = Trigger | 1 Bit | 1.17 trigger | CW |
| 57 | [In3] Switch Feedback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 57 | [In3] Over-Heating Output | 1 = Over-Heating, 0 = No Over-Heating | 1 Bit | 1.5 alarm | CT |
| 58 | [In3] Over-Cooling Output | 1 = Over-Cooling, 0 = No Over-Cooling | 1 Bit | 1.5 alarm | CT |
| 58 | [In3] Long Switch Feedback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 58 | [In3] Counter 16 Bits | Counter (0-65535) | 2 Bytes | 7.1 pulses | CRT |
| 58 | [In3] Switch 4 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 58 | [In3] Counter 8 Bits | Counter (0-255) | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 58 | [In3] Counter 32 Bits | Counter (0-4.294.967.295) | 4 Bytes | 12.1 counter pulses (unsigned) | CRT |
| 58 | [In3] Switch [3] | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 58 | [In3] Dimming Value [3] | Dimming value 0-100% | 1 Byte | 5.1 percentage (0..100%) | CT |
| 58 | [In3] Scene number [3] | Scene Number | 1 Byte | 17.1 scene number | CT |
| 58 | [In3] HVAC mode [3] | HVAC mode | 1 Byte | 20.102 HVAC mode | CT |
| 59 | [In3] Switch 5 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 60 | [In3] Save Scene | 0 = Scene 1, 1 = Scene 2 | 1 Bit | 1.3 enable | CT |
| 60 | [In3] Increase/Decrease | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 61 | [In4] Disable Temperature Functionality | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 61 | [In4] Disable Input | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 62 | [In4] 1 Bit value on press | Bit value | 1 Bit | 1.11 state | CT |
| 62 | [In4] 2 Bits value on press | 2 Bits value | 2 Bit | 2.1 switch control | CT |
| 62 | [In4] 2 Bytes value on press | 2 Bytes value | 2 Bytes | 7.1 pulses | CT |
| 62 | [In4] 1 Byte value on press | Byte value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 62 | [In4] 2 Bytes floating value on press | 2 Bytes floating value | 2 Bytes | 9.1 temperature (°C) | CT |
| 62 | [In4] Stop / Step | 0 = Step Up, 1 = Step Down | 1 Bit | 1.7 step | CT |
| 62 | [In4] Scene 1 Bit | 0 = Scene 1, 1 = Scene 2 | 1 Bit | 1.22 scene | CT |
| 62 | [In4] Counter direction | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 62 | [In4] 4 Bytes value on press | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 62 | [In4] Temperature value | Temperature value | 2 Bytes | 9.1 temperature (°C) | CT |
| 62 | [In4] Scene control 8 Bits | Scene Control | 1 Byte | 18.1 scene control | CT |
| 62 | [In4] Switch | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 62 | [In4] 2 Bytes signed value on press | 2 Bytes signed value | 2 Bytes | 8.1 pulses difference | CT |
| 62 | [In4] Dimming Value | Dimming value 0-100% | 1 Byte | 5.1 percentage (0..100%) | CT |
| 62 | [In4] Scene number | Scene Number | 1 Byte | 17.1 scene number | CT |
| 62 | [In4] HVAC mode | HVAC mode | 1 Byte | 20.102 HVAC mode | CT |
| 63 | [In4] Save Scene | 0 = No action, 1 = Save Scene | 1 Bit | 1.3 enable | CW |
| 63 | [In4] 2 Bytes signed value on Long press | 2 Bytes signed value | 2 Bytes | 8.1 pulses difference | CT |
| 63 | [In4] Move | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CT |
| 63 | [In4] 4 Bytes value on Long press | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 63 | [In4] 2 Bits value on Long press | 2 Bits value | 2 Bit | 2.1 switch control | CT |
| 63 | [In4] 2 Bytes floating value on Long press | 2 Bytes floating value | 2 Bytes | 9.1 temperature (°C) | CT |
| 63 | [In4] 2 Bytes value on Long press | 2 Bytes value | 2 Bytes | 7.1 pulses | CT |
| 63 | [In4] Sensor not connected | 0 = Sensor Ok, 1 = Sensor not connected | 1 Bit | 1.11 state | CT |
| 63 | [In4] Reset Counter | 0 = No action, 1 = Reset | 1 Bit | 1.15 reset | CW |
| 63 | [In4] 1 Byte value on Long press | Byte value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 63 | [In4] Dimming Control | Dimming control | 4 Bit | 3.7 dimming control | CT |
| 63 | [In4] Long Switch | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 63 | [In4] 1 Bit value on Long press | Bit value | 1 Bit | 1.11 state | CT |
| 63 | [In4] Switch 2 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 63 | [In4] Switch [2] | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 63 | [In4] Dimming Value [2] | Dimming value 0-100% | 1 Byte | 5.1 percentage (0..100%) | CT |
| 63 | [In4] Scene number [2] | Scene Number | 1 Byte | 17.1 scene number | CT |
| 63 | [In4] HVAC mode [2] | HVAC mode | 1 Byte | 20.102 HVAC mode | CT |
| 64 | [In4] Over-Heating Output | 1 = Over-Heating, 0 = No Over-Heating | 1 Bit | 1.5 alarm | CT |
| 64 | [In4] Switch 3 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 64 | [In4] Request Counter | 1 = Trigger | 1 Bit | 1.17 trigger | CW |
| 64 | [In4] Switch Feedback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 65 | [In4] Counter 16 Bits | Counter (0-65535) | 2 Bytes | 7.1 pulses | CRT |
| 65 | [In4] Counter 32 Bits | Counter (0-4.294.967.295) | 4 Bytes | 12.1 counter pulses (unsigned) | CRT |
| 65 | [In4] Over-Cooling Output | 1 = Over-Cooling, 0 = No Over-Cooling | 1 Bit | 1.5 alarm | CT |
| 65 | [In4] Counter 8 Bits | Counter (0-255) | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 65 | [In4] Switch 4 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 65 | [In4] Long Switch Feedback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 65 | [In4] Switch [3] | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 65 | [In4] Dimming Value [3] | Dimming value 0-100% | 1 Byte | 5.1 percentage (0..100%) | CT |
| 65 | [In4] Scene number [3] | Scene Number | 1 Byte | 17.1 scene number | CT |
| 65 | [In4] HVAC mode [3] | HVAC mode | 1 Byte | 20.102 HVAC mode | CT |
| 66 | [In4] Switch 5 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 67 | [In4] Increase/Decrease | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 67 | [In4] Save Scene | 0 = Scene 1, 1 = Scene 2 | 1 Bit | 1.3 enable | CT |
| 70 | [T1] On/Off Feedback | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CT |
| 71 | [T1] On/Off Input | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CW |
| 72 | [T1] Set-point Information | Current Set-point | 2 Bytes | 9.1 temperature (°C) | CT |
| 73 | [T1] Set-point Input | Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 73 | [T1] Comfort Set-point Input | Comfort Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 74 | [T1] Output | Output (2-point with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 74 | [T1] Output Heating | Output (2-point with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 74 | [T1] Output Heating | Output (% Proportional - Integral) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 74 | [T1] Output | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 74 | [T1] Output Heating | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 74 | [T1] Output | Output (% Proportional - Integral) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 75 | [T1] Output Cooling | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 75 | [T1] Output Cooling | Output (% Proportional - Integral) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 75 | [T1] Output Cooling | Output (2-point with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 76 | [T1] Temperature Sensor 1 | Input Temperature Sensor 1 | 2 Bytes | 9.1 temperature (°C) | CW |
| 77 | [T1] Temperature Sensor 2 | Input Temperature Sensor 2 | 2 Bytes | 9.1 temperature (°C) | CW |
| 78 | [T1] Special mode Feedback | 2 Bytes mode Feedback | 2 Bytes | 22.101 RHCC status | CT |
| 79 | [T1] 1 Byte Special mode Input | 1 Byte mode HVAC | 1 Byte | 20.102 HVAC mode | CW |
| 80 | [T1] Special mode Economy | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 81 | [T1] Special mode Stand-by | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 82 | [T1] Special mode Protection | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 83 | [T1] Special mode Comfort | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 84 | [T1] Heating or Cooling mode Status | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CT |
| 85 | [T1] Heating or Cooling mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CW |
| 86 | [T1] Window Alarm 1 | 0 = No alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CW |
| 87 | [T1] Window Alarm 2 | 0 = No alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CW |
| 88 | [T1] Window Alarm 3 | 0 = No alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CW |
| 89 | [T1] Window Alarm 4 | 0 = No alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CW |
| 90 | [T2] On/Off Feedback | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CT |
| 91 | [T2] On/Off Input | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CW |
| 92 | [T2] Set-point Feedback | Current Set-point | 2 Bytes | 9.1 temperature (°C) | CT |
| 93 | [T2] Comfort Set-point Input | Comfort Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 93 | [T2] Set-point Input | Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 94 | [T2] Output Heating | Output (2-point with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 94 | [T2] Output Heating | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 94 | [T2] Output Heating | Output (% Proportional - Integral) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 94 | [T2] Output | Output (% Proportional - Integral) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 94 | [T2] Output | Output (2-point with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 94 | [T2] Output | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 95 | [T2] Output Cooling | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 95 | [T2] Output Cooling | Output (2-point with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 95 | [T2] Output Cooling | Output (% Proportional - Integral) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 96 | [T2] Temperature Sensor 1 | Input Temperature Sensor 1 | 2 Bytes | 9.1 temperature (°C) | CW |
| 97 | [T2] Temperature Sensor 2 | Input Temperature Sensor 2 | 2 Bytes | 9.1 temperature (°C) | CW |
| 98 | [T2] Special mode Feedback | 2 Bytes mode Feedback | 2 Bytes | 22.101 RHCC status | CT |
| 99 | [T2] 1 Byte Special mode Input | 1 Byte mode HVAC | 1 Byte | 20.102 HVAC mode | CW |
| 100 | [T2] Special mode Economy | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 101 | [T2] Special mode Stand-by | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 102 | [T2] Special mode Protection | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 103 | [T2] Special mode Comfort | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 104 | [T2] Heating or Cooling mode Status | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CT |
| 105 | [T2] Heating or Cooling mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CW |
| 106 | [T2] Window Alarm 1 | 0 = No alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CW |
| 107 | [T2] Window Alarm 2 | 0 = No alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CW |
| 108 | [T2] Window Alarm 3 | 0 = No alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CW |
| 109 | [T2] Window Alarm 4 | 0 = No alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CW |
| 110 | [T3] On/Off Feedback | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CT |
| 111 | [T3] On/Off Input | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CW |
| 112 | [T3] Set-point Information | Current Set-point | 2 Bytes | 9.1 temperature (°C) | CT |
| 113 | [T3] Set-point Input | Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 113 | [T3] Comfort Set-point Input | Comfort Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 114 | [T3] Output Heating | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 114 | [T3] Output Heating | Output (% Proportional - Integral) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 114 | [T3] Output | Output (% Proportional - Integral) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 114 | [T3] Output | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 114 | [T3] Output | Output (2-point with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 114 | [T3] Output Heating | Output (2-point with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 115 | [T3] Output Cooling | Output (% Proportional - Integral) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 115 | [T3] Output Cooling | Output (2-point with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 115 | [T3] Output Cooling | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 116 | [T3] Temperature Sensor 1 | Input Temperature Sensor 1 | 2 Bytes | 9.1 temperature (°C) | CW |
| 117 | [T3] Temperature Sensor 2 | Input Temperature Sensor 2 | 2 Bytes | 9.1 temperature (°C) | CW |
| 118 | [T3] Special mode Feedback | 2 Bytes mode Feedback | 2 Bytes | 22.101 RHCC status | CT |
| 119 | [T3] 1 Byte Special mode Input | 1 Byte mode HVAC | 1 Byte | 20.102 HVAC mode | CW |
| 120 | [T3] Special mode Economy | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 121 | [T3] Special mode Stand-by | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 122 | [T3] Special mode Protection | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 123 | [T3] Special mode Comfort | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 124 | [T3] Heating or Cooling mode Status | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CT |
| 125 | [T3] Heating or Cooling mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CW |
| 126 | [T3] Window Alarm 1 | 0 = No alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CW |
| 127 | [T3] Window Alarm 2 | 0 = No alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CW |
| 128 | [T3] Window Alarm 3 | 0 = No alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CW |
| 129 | [T3] Window Alarm 4 | 0 = No alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CW |
| 130 | [T4] On/Off Feedback | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CT |
| 131 | [T4] On/Off Input | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CW |
| 132 | [T4] Set-point Feedback | Current Set-point | 2 Bytes | 9.1 temperature (°C) | CT |
| 133 | [T4] Comfort Set-point Input | Comfort Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 133 | [T4] Set-point Input | Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 134 | [T4] Output | Output (2-point with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 134 | [T4] Output Heating | Output (2-point with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 134 | [T4] Output Heating | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 134 | [T4] Output Heating | Output (% Proportional - Integral) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 134 | [T4] Output | Output (% Proportional - Integral) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 134 | [T4] Output | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 135 | [T4] Output Cooling | Output (% Proportional - Integral) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 135 | [T4] Output Cooling | Output (2-point with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 135 | [T4] Output Cooling | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 136 | [T4] Temperature Sensor 1 | Input Temperature Sensor 1 | 2 Bytes | 9.1 temperature (°C) | CW |
| 137 | [T4] Temperature Sensor 2 | Input Temperature Sensor 2 | 2 Bytes | 9.1 temperature (°C) | CW |
| 138 | [T4] Special mode Feedback | 2 Bytes mode Feedback | 2 Bytes | 22.101 RHCC status | CT |
| 139 | [T4] 1 Byte Special mode Input | 1 Byte mode HVAC | 1 Byte | 20.102 HVAC mode | CW |
| 140 | [T4] Special mode Economy | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 141 | [T4] Special mode Stand-by | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 142 | [T4] Special mode Protection | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 143 | [T4] Special mode Comfort | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 144 | [T4] Heating or Cooling mode Status | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CT |
| 145 | [T4] Heating or Cooling mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CW |
| 146 | [T4] Window Alarm 1 | 0 = No alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CW |
| 147 | [T4] Window Alarm 2 | 0 = No alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CW |
| 148 | [T4] Window Alarm 3 | 0 = No alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CW |
| 149 | [T4] Window Alarm 4 | 0 = No alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CW |