KNX Database
Arlight 025670 KNX-113-35-IN

KNX-113-35-IN 025670

Arlight · Order number 025670 · KNX-113-35-IN › KNX-113-35-IN

KNX-113-35-IN

Download .knxprod KNX Temperature Control Panel 3.5" 1.0 · 133 KB

Product

ManufacturerArlight
Product nameKNX-113-35-IN
Order number025670
HardwareKNX-113-35-IN
MediumTwisted Pair
Rail mountedNo
RegistrationCertified
Languagesen-US
Catalog entryM-01C4_H-0UXXXX-16-O0085_HP-0502-10-02CB-O0085_CI-025670-16
Fingerprint02CB
SHA-2565cd2b3f484fb6abef617d8fab2e3b61a037880774012f71d3c657491c6bcc0bb
First seen2026-11-25
MarketsBelarus, Kazakhstan, Russia

Application program: KNX Temperature Control Panel 3.5" 1.0

Application number$0502
Version1.0
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Parameters692
Group objects240
Group objects (240)
NoNameFunctionSizeDPTFlags
0In operationGeneral1 Bit1.1 switchCT
1Day/night modeDay/night switch1 Bit1.1 switchCT
1Day/night modeDay/night switch1 Bit1.1 switchCRW
2Input external temperatureTemperature2 Bytes9.1 temperature (°C)CRW
3Actual temperatureTemperature2 Bytes9.1 temperature (°C)CRT
4rel.humidityHumidity2 BytesCRT
5Operating mode forcing objectSetpoint temperature1 ByteCRW
6Windows statusSetpoint temperature1 Bit1.1 switchCRW
7Presence objectSetpoint temperature1 Bit1.1 switchCRW
8Active comfort modeSetpoint temperature1 Bit1.1 switchCRW
9Active standby modeSetpoint temperature1 Bit1.1 switchCRW
10Active night modeSetpoint temperature1 Bit1.1 switchCRW
11Active frost/heat protection modeSetpoint temperature1 Bit1.1 switchCRW
12Temperature operating mode switchoverSetpoint temperature1 ByteCRWT
13Heating/cooling switchoverTemperature control1 Bit1.1 switchCRT
14Basic comfort temperatureSetpoint temperature2 Bytes9.1 temperature (°C)CRW
14Basic comfort temperature (at heating)Setpoint temperature2 Bytes9.1 temperature (°C)CRW
15Heating setpointSetpoint temperature2 Bytes9.1 temperature (°C)CRWT
16Cooling setpointSetpoint temperature2 Bytes9.1 temperature (°C)CRWT
17Output HVAC statusTemperature control1 ByteCRT
18Output RHCC statusTemperature control2 BytesCRT
19Basic heating/cooling control valueTemperature control1 Byte5.1 percentage (0..100%)CRT
19Basic heating/cooling control valueTemperature control1 Bit1.1 switchCRT
19Basic heating control valueTemperature control1 Bit1.1 switchCRT
19Basic heating control valueTemperature control1 Byte5.1 percentage (0..100%)CRT
20Basic cooling control valueTemperature control1 Byte5.1 percentage (0..100%)CRT
20Basic cooling control valueTemperature control1 Bit1.1 switchCRT
21Automatic fan ON/OFFTemperature control1 Bit1.1 switchCRT
21Manual fan ON/OFFTemperature control1 Bit1.1 switchCRT
22Fan manual stageTemperature control1 Byte5.1 percentage (0..100%)CRT
23Lock temperature controlTemperature control1 Bit1.1 switchCRW
24Additional heating/cooling control valueTemperature control1 Byte5.1 percentage (0..100%)CRT
24Additional heating/cooling control valueTemperature control1 Bit1.1 switchCRT
24Additional heating control valueTemperature control1 Byte5.1 percentage (0..100%)CRT
24Additional heating control valueTemperature control1 Bit1.1 switchCRT
25Additional cooling control valueTemperature control1 Bit1.1 switchCRT
25Additional cooling control valueTemperature control1 Byte5.1 percentage (0..100%)CRT
26Lock additional stageTemperature control1 Bit1.1 switchCRW
27Change temperature threshold value 1Temperature threshold value 12 Bytes9.1 temperature (°C)CRW
281 bit output, temperature Temperature threshold value 11 Bit1.1 switchCRT
291 byte output, temperature Temperature threshold value 11 Byte5.10 counter pulses (0..255)CRT
30Temperature threshold value 1 blockTemperature threshold value 11 Bit1.1 switchCRW
31Change temperature threshold value 2Temperature threshold value 22 Bytes9.1 temperature (°C)CRW
321 bit output, temperature Temperature threshold value 21 Bit1.1 switchCRT
331 byte output, temperature Temperature threshold value 21 Byte5.10 counter pulses (0..255)CRT
34Temperature threshold value 2 blockTemperature threshold value 21 Bit1.1 switchCRW
35Change humidity threshold value 1Humidity threshold value 12 BytesCRW
361 bit output, humidity Humidity threshold value 11 Bit1.1 switchCRT
371 byte output, humidity Humidity threshold value 11 Byte5.10 counter pulses (0..255)CRT
38Humidity threshold value 1 blockHumidity threshold value 11 Bit1.1 switchCRW
39Change humidity threshold value 2Humidity threshold value 22 BytesCRW
401 bit output, humidity Humidity threshold value 21 Bit1.1 switchCRT
411 byte output, humidity Humidity threshold value 21 Byte5.10 counter pulses (0..255)CRT
42Humidity threshold value 2 blockHumidity threshold value 21 Bit1.1 switchCRW
43Logic input ALogic input1 Bit1.1 switchCRW
44Logic input BLogic input1 Bit1.1 switchCRW
45Logic 1,1 bit outputLogic 11 Bit1.1 switchCRT
46Logic 1,1 byte outputLogic 11 Byte5.10 counter pulses (0..255)CRT
47Logic 1 blockLogic 11 Bit1.1 switchCRW
48Logic 2,1 bit outputLogic 21 Bit1.1 switchCRT
49Logic 2,1 byte outputLogic 21 Byte5.10 counter pulses (0..255)CRT
50Logic 2 blockLogic 21 Bit1.1 switchCRW
51TimeTime3 Bytes10.1 time of dayCRWT
52Disable room temperature timerTime1 Bit1.1 switchCW
53Output shutter UP/DOWNCH A Blind1 Bit1.8 up/downCT
53Output shutter UP/DOWNCH A Blind1 Byte5.1 percentage (0..100%)CT
53Switch 1, input 1CH A Switch1 Bit1.1 switchCWT
53SwitchCH A Switch1 Bit1.1 switchCWT
53Input 1, SceneScene number1 ByteCT
54Output Stop/lamella adjCH A Blind1 BitCT
54Output Stop/lamella adjCH A Blind1 Byte5.1 percentage (0..100%)CT
54Switch 2, input 1CH A switch1 Bit1.1 switchCT
54DimmingCH A Dimming4 Bit3.7 dimming controlCT
55Disable input 1CH A Disable1 Bit1.1 switchCW
56Output shutter UP/DOWNCH B Blind1 Bit1.8 up/downCT
56Output shutter UP/DOWNCH B Blind1 Byte5.1 percentage (0..100%)CT
56Switch 1, input 2CH B Switch1 Bit1.1 switchCWT
56SwitchCH B Switch1 Bit1.1 switchCWT
56Input 2 , SceneScene number1 ByteCT
57Output Stop/lamella adjCH B Blind1 BitCT
57Output Stop/lamella adjCH B Blind1 Byte5.1 percentage (0..100%)CT
57Switch 2, input 2CH B switch1 Bit1.1 switchCT
57DimmingCH B Dimming4 Bit3.7 dimming controlCT
58Disable input 2CH B Disable1 Bit1.1 switchCW
59Output shutter UP/DOWNCH C Blind1 Bit1.8 up/downCT
59Output shutter UP/DOWNCH C Blind1 Byte5.1 percentage (0..100%)CT
59Switch 1, input 3CH C Switch1 Bit1.1 switchCWT
59SwitchCH C Switch1 Bit1.1 switchCWT
59Input 3, SceneScene number1 ByteCT
60Output Stop/lamella adjCH C Blind1 BitCT
60Output Stop/lamella adjCH C Blind1 Byte5.1 percentage (0..100%)CT
60Switch 2, input 3CH C switch1 Bit1.1 switchCT
60DimmingCH C Dimming4 Bit3.7 dimming controlCT
61Disable input 3CH C Disable1 Bit1.1 switchCW
62Floor temperatureCH D Temperature2 Bytes9.1 temperature (°C)CRT
63IR command numberTemperature control1 ByteCT
64Air condition on/offTemperature control1 Bit1.1 switchCT
65Mode heating/coolingTemperature control1 Bit1.1 switchCT
66Switch to high/medium speedTemperature control1 Bit1.1 switchCT
67Switch to low/auto speedTemperature control1 Bit1.1 switchCT
68setpoint for heating 16/17Setpoint temperature1 Bit1.1 switchCT
69setpoint for heating 18/19Setpoint temperature1 Bit1.1 switchCT
70setpoint for heating 20/21Setpoint temperature1 Bit1.1 switchCT
71setpoint for heating 22/23Setpoint temperature1 Bit1.1 switchCT
72setpoint for heating 24/25Setpoint temperature1 Bit1.1 switchCT
73setpoint for heating 26/27Setpoint temperature1 Bit1.1 switchCT
74setpoint for heating 28/29Setpoint temperature1 Bit1.1 switchCT
75setpoint for heating 30/31Setpoint temperature1 Bit1.1 switchCT
76setpoint for cooling 16/17Setpoint temperature1 Bit1.1 switchCT
77setpoint for cooling 18/19Setpoint temperature1 Bit1.1 switchCT
78setpoint for cooling 20/21Setpoint temperature1 Bit1.1 switchCT
79setpoint for cooling 22/23Setpoint temperature1 Bit1.1 switchCT
80setpoint for cooling 24/25Setpoint temperature1 Bit1.1 switchCT
81setpoint for cooling 26/27Setpoint temperature1 Bit1.1 switchCT
82setpoint for cooling 28/29Setpoint temperature1 Bit1.1 switchCT
83setpoint for cooling 30/31Setpoint temperature1 Bit1.1 switchCT
84outdoor temperatureTemperature2 Bytes9.1 temperature (°C)CRW
85Heating standby setpoint Setpoint temperature2 Bytes9.1 temperature (°C)CRW
86Heating night setpoint Setpoint temperature2 Bytes9.1 temperature (°C)CRW
87Setpoint heat protectionSetpoint temperature2 Bytes9.1 temperature (°C)CRW
87Setpoint frost protectionSetpoint temperature2 Bytes9.1 temperature (°C)CRW
88Cooling comfort setpoint Setpoint temperature2 Bytes9.1 temperature (°C)CRW
88Basic comfort temperatureSetpoint temperature2 Bytes9.1 temperature (°C)CRW
89Cooling standby setpoint Setpoint temperature2 Bytes9.1 temperature (°C)CRW
90Cooling night setpoint Setpoint temperature2 Bytes9.1 temperature (°C)CRW
91Setpoint frost protectionSetpoint temperature2 Bytes9.1 temperature (°C)CRW
91Setpoint heat protectionSetpoint temperature2 Bytes9.1 temperature (°C)CRW
924 byte value[0..4294967295]Time 1 value4 Bytes12.1 counter pulses (unsigned)CT
924 bit value[0..15]Time 1 value4 Bit3.7 dimming controlCT
922 bit value[0..3]Time 1 value2 Bit2.2 boolean controlCT
921 bit value[0..1]Time 1 value1 Bit1.1 switchCT
922 byte value[0..65535]Time 1 value2 Bytes7.1 pulsesCT
922 byte value[-32768..32767]Time 1 value2 Bytes8.1 pulses differenceCT
921 byte value[0..255]Time 1 value1 Byte5.10 counter pulses (0..255)CT
934 bit value[0..15]Time 2 value4 Bit3.7 dimming controlCT
931 bit value[0..1]Time 2 value1 Bit1.1 switchCT
931 byte value[0..255]Time 2 value1 Byte5.10 counter pulses (0..255)CT
934 byte value[0..4294967295]Time 2 value4 Bytes12.1 counter pulses (unsigned)CT
932 byte value[0..65535]Time 2 value2 Bytes7.1 pulsesCT
932 bit value[0..3]Time 2 value2 Bit2.2 boolean controlCT
932 byte value[-32768..32767]Time 2 value2 Bytes8.1 pulses differenceCT
942 bit value[0..3]Time 3 value2 Bit2.2 boolean controlCT
942 byte value[0..65535]Time 3 value2 Bytes7.1 pulsesCT
944 byte value[0..4294967295]Time 3 value4 Bytes12.1 counter pulses (unsigned)CT
942 byte value[-32768..32767]Time 3 value2 Bytes8.1 pulses differenceCT
941 bit value[0..1]Time 3 value1 Bit1.1 switchCT
944 bit value[0..15]Time 3 value4 Bit3.7 dimming controlCT
941 byte value[0..255]Time 3 value1 Byte5.10 counter pulses (0..255)CT
954 byte value[0..4294967295]Time 4 value4 Bytes12.1 counter pulses (unsigned)CT
952 byte value[0..65535]Time 4 value2 Bytes7.1 pulsesCT
952 byte value[-32768..32767]Time 4 value2 Bytes8.1 pulses differenceCT
952 bit value[0..3]Time 4 value2 Bit2.2 boolean controlCT
951 bit value[0..1]Time 4 value1 Bit1.1 switchCT
954 bit value[0..15]Time 4 value4 Bit3.7 dimming controlCT
951 byte value[0..255]Time 4 value1 Byte5.10 counter pulses (0..255)CT
964 bit value[0..15]Time 5 value4 Bit3.7 dimming controlCT
962 byte value[-32768..32767]Time 5 value2 Bytes8.1 pulses differenceCT
962 bit value[0..3]Time 5 value2 Bit2.2 boolean controlCT
961 bit value[0..1]Time 5 value1 Bit1.1 switchCT
962 byte value[0..65535]Time 5 value2 Bytes7.1 pulsesCT
961 byte value[0..255]Time 5 value1 Byte5.10 counter pulses (0..255)CT
964 byte value[0..4294967295]Time 5 value4 Bytes12.1 counter pulses (unsigned)CT
974 byte value[0..4294967295]Time 6 value4 Bytes12.1 counter pulses (unsigned)CT
971 bit value[0..1]Time 6 value1 Bit1.1 switchCT
972 byte value[0..65535]Time 6 value2 Bytes7.1 pulsesCT
972 bit value[0..3]Time 6 value2 Bit2.2 boolean controlCT
972 byte value[-32768..32767]Time 6 value2 Bytes8.1 pulses differenceCT
974 bit value[0..15]Time 6 value4 Bit3.7 dimming controlCT
971 byte value[0..255]Time 6 value1 Byte5.10 counter pulses (0..255)CT
984 byte value[0..4294967295]Time 7 value4 Bytes12.1 counter pulses (unsigned)CT
981 byte value[0..255]Time 7 value1 Byte5.10 counter pulses (0..255)CT
982 byte value[-32768..32767]Time 7 value2 Bytes8.1 pulses differenceCT
982 byte value[0..65535]Time 7 value2 Bytes7.1 pulsesCT
981 bit value[0..1]Time 7 value1 Bit1.1 switchCT
982 bit value[0..3]Time 7 value2 Bit2.2 boolean controlCT
984 bit value[0..15]Time 7 value4 Bit3.7 dimming controlCT
991 bit value[0..1]Time 8 value1 Bit1.1 switchCT
992 byte value[0..65535]Time 8 value2 Bytes7.1 pulsesCT
992 byte value[-32768..32767]Time 8 value2 Bytes8.1 pulses differenceCT
991 byte value[0..255]Time 8 value1 Byte5.10 counter pulses (0..255)CT
994 byte value[0..4294967295]Time 8 value4 Bytes12.1 counter pulses (unsigned)CT
992 bit value[0..3]Time 8 value2 Bit2.2 boolean controlCT
994 bit value[0..15]Time 8 value4 Bit3.7 dimming controlCT
1004 byte value[0..4294967295]Time 9 value4 Bytes12.1 counter pulses (unsigned)CT
1004 bit value[0..15]Time 9 value4 Bit3.7 dimming controlCT
1001 byte value[0..255]Time 9 value1 Byte5.10 counter pulses (0..255)CT
1002 byte value[-32768..32767]Time 9 value2 Bytes8.1 pulses differenceCT
1002 byte value[0..65535]Time 9 value2 Bytes7.1 pulsesCT
1001 bit value[0..1]Time 9 value1 Bit1.1 switchCT
1002 bit value[0..3]Time 9 value2 Bit2.2 boolean controlCT
1014 byte value[0..4294967295]Time 10 value4 Bytes12.1 counter pulses (unsigned)CT
1014 bit value[0..15]Time 10 value4 Bit3.7 dimming controlCT
1012 bit value[0..3]Time 10 value2 Bit2.2 boolean controlCT
1011 bit value[0..1]Time 10 value1 Bit1.1 switchCT
1012 byte value[0..65535]Time 10 value2 Bytes7.1 pulsesCT
1012 byte value[-32768..32767]Time 10 value2 Bytes8.1 pulses differenceCT
1011 byte value[0..255]Time 10 value1 Byte5.10 counter pulses (0..255)CT
1024 byte value[0..4294967295]Time 11 value4 Bytes12.1 counter pulses (unsigned)CT
1021 bit value[0..1]Time 11 value1 Bit1.1 switchCT
1024 bit value[0..15]Time 11 value4 Bit3.7 dimming controlCT
1022 byte value[0..65535]Time 11 value2 Bytes7.1 pulsesCT
1022 byte value[-32768..32767]Time 11 value2 Bytes8.1 pulses differenceCT
1021 byte value[0..255]Time 11 value1 Byte5.10 counter pulses (0..255)CT
1022 bit value[0..3]Time 11 value2 Bit2.2 boolean controlCT
1031 byte value[0..255]Time 12 value1 Byte5.10 counter pulses (0..255)CT
1032 bit value[0..3]Time 12 value2 Bit2.2 boolean controlCT
1031 bit value[0..1]Time 12 value1 Bit1.1 switchCT
1034 bit value[0..15]Time 12 value4 Bit3.7 dimming controlCT
1032 byte value[0..65535]Time 12 value2 Bytes7.1 pulsesCT
1032 byte value[-32768..32767]Time 12 value2 Bytes8.1 pulses differenceCT
1034 byte value[0..4294967295]Time 12 value4 Bytes12.1 counter pulses (unsigned)CT
1042 byte value[0..65535]Time 13 value2 Bytes7.1 pulsesCT
1044 byte value[0..4294967295]Time 13 value4 Bytes12.1 counter pulses (unsigned)CT
1041 bit value[0..1]Time 13 value1 Bit1.1 switchCT
1041 byte value[0..255]Time 13 value1 Byte5.10 counter pulses (0..255)CT
1044 bit value[0..15]Time 13 value4 Bit3.7 dimming controlCT
1042 bit value[0..3]Time 13 value2 Bit2.2 boolean controlCT
1042 byte value[-32768..32767]Time 13 value2 Bytes8.1 pulses differenceCT
1052 byte value[0..65535]Time 14 value2 Bytes7.1 pulsesCT
1054 byte value[0..4294967295]Time 14 value4 Bytes12.1 counter pulses (unsigned)CT
1052 byte value[-32768..32767]Time 14 value2 Bytes8.1 pulses differenceCT
1051 bit value[0..1]Time 14 value1 Bit1.1 switchCT
1052 bit value[0..3]Time 14 value2 Bit2.2 boolean controlCT
1051 byte value[0..255]Time 14 value1 Byte5.10 counter pulses (0..255)CT
1054 bit value[0..15]Time 14 value4 Bit3.7 dimming controlCT
1062 byte value[-32768..32767]Time 15 value2 Bytes8.1 pulses differenceCT
1062 byte value[0..65535]Time 15 value2 Bytes7.1 pulsesCT
1064 byte value[0..4294967295]Time 15 value4 Bytes12.1 counter pulses (unsigned)CT
1062 bit value[0..3]Time 15 value2 Bit2.2 boolean controlCT
1061 bit value[0..1]Time 15 value1 Bit1.1 switchCT
1064 bit value[0..15]Time 15 value4 Bit3.7 dimming controlCT
1061 byte value[0..255]Time 15 value1 Byte5.10 counter pulses (0..255)CT
1072 byte value[-32768..32767]Time 16 value2 Bytes8.1 pulses differenceCT
1072 byte value[0..65535]Time 16 value2 Bytes7.1 pulsesCT
1074 byte value[0..4294967295]Time 16 value4 Bytes12.1 counter pulses (unsigned)CT
1071 byte value[0..255]Time 16 value1 Byte5.1 percentage (0..100%)CT
1071 bit value[0..1]Time 16 value1 Bit1.1 switchCT
1072 bit value[0..3]Time 16 value2 Bit2.2 boolean controlCT
1074 bit value[0..15]Time 16 value4 Bit3.7 dimming controlCT
108Unit on/offUnit on/off1 Bit1.1 switchCRWT
Parameters (265)
ParameterTypeDefault
Send In operation objectlistno
Transmission period of In operation objectlist5 min
Temperature displaylistCelsius(C)
Backlight in no operation in day (%)unsignedInt 0…10060
Backlight in operation in day (%)unsignedInt 0…100100
Backlight in no operation at night (%)unsignedInt 0…10050
Backlight in operation at night (%)unsignedInt 0…10090
Time of backlight delay(s)unsignedInt 5…505
Switch day/night mode automaticallylistno
Time of switching to day at:HourunsignedInt 0…236
Time of switching to day at:MiniuteunsignedInt 0…590
Time of switching to night at:HourunsignedInt 0…2318
Time of switching to night at:MinitueunsignedInt 0…590
Time modelist24H
Send current timelistDo not send
Warning tonelistdisable
Control devicelistHVAC
Controller action when display offlistProtect mode
Temperature control systemlistcooling
Heating and cooling share objectlistno
Temperature sensorlistinternal sensor
Internal temperature correction in 0.1CelsiussignedInt -128…1270
External temperature correction in 0.1CelsiussignedInt -128…1270
Weighting interior/exteriorlist50% / 50%
Monitoring time of external sensor in min (0 = inactive)unsignedInt 0…25510
Send temperature at variation of (Celsius)list0.3
Period of sending temperaturelist2 min
Enalbe display outdoor tempraturelistdisable
Indoor and outdoor temperature switch time (second)unsignedInt 0…25510
Humidity correction in %signedInt -15…150
Send rel. humidity at variation of (%)list1
Period of sending humiditylist2 min
Operating mode after resetlistcomfort mode
Object type for operating mode switchoverlist1 byte
Send setpointliston change
Period of sending setpointlist10 min
Switchover between heating and coolinglistautomatic switchover by dead zone
Control option after resetlistheating
Automatic transmission heating/cooling switchoverlistwhen control option changes
Cyclic transmission of heating/cooling switchover in min (0 = inactive)unsignedInt 0…2550
automatic transmission heating/cooling switchoverlistwhen control option changes
Period of sending HVAC statuslist5 min
Period of sending HVAC and RHCC statuslist5 min
Setpoint adjustmentlistrelative adjustment
Basic comfort setpoint at cooling in 0.1CelsiusunsignedInt 0…500230
Basic comfort setpoint at heating in 0.1CelsiusunsignedInt 0…500210
Setpoint decrease for standby mode at heating in 0.1CelsiusunsignedInt 0…10020
Setpoint decrease for night mode at heating in 0.1CelsiusunsignedInt 0…10040
Setpoint frost protection at heating in 0.1CelsiusunsignedInt 0…25570
Positive dead zone between heating and cooling in 0.1CelsiusunsignedInt 0…10020
Setpoint increase for standby mode at cooling in 0.1CelsiusunsignedInt 0…10020
Setpoint increase for night mode at cooling in 0.1CelsiusunsignedInt 0…10040
Setpoint heat protection at cooling in 0.1CelsiusunsignedInt 0…500350
Heating comfort setpoint in 0.1CelsiusunsignedInt 0…500210
Heating standby setpoint in 0.1 CelsiusunsignedInt 0…500190
Heating night setpoint in 0.1CelsiusunsignedInt 0…500170
Cooling comfort setpoint in 0.1CelsiusunsignedInt 0…500230
Cooling standby setpoint in 0.1CelsiusunsignedInt 0…500250
Cooling night setpoint in 0.1CelsiusunsignedInt 0…500270
Minimum distance between heating setpoint and cooling setpointunsignedInt 0…10020
Control typelistfan coil control
Invert control valuelistno
Control parameter of heating systemlisthot water heating (5 K / 150 min)
Send control value at variation of (%) (0 = inactive)unsignedInt 0…154
Proportional range in 0.1 CelsiusunsignedInt 10…10040
Period of sending control value in min (0 = inactive)unsignedInt 0…25510
Reset time in minunsignedInt 0…255150
Minimum control value in % at heatingunsignedInt 0…300
Minimum control value in %unsignedInt 0…300
Maximum control value in % at heatingunsignedInt 70…100100
Maximum control value in %unsignedInt 70…100100
Maximum control value in % at heatingunsignedInt 70…100100
PWM cycle time in minunsignedInt 1…25510
Proportional range in 0.1 CelsiusunsignedInt 10…10040
Symmetrical hysteresis temperature in 0.1 Celsius at heatingunsignedInt 5…5020
Symmetrical hysteresis temperature in 0.1 CelsiusunsignedInt 5…5020
Symmetrical hysteresis temperature in 0.1 Celsius at coolingunsignedInt 5…5020
Symmetrical hysteresis temperature in 0.1 Celsius at coolingunsignedInt 5…5020
Control value typelist1 bit (ON/OFF)
Control parameter of cooling systemlistcooling ceiling (5 K / 240 min)
Minimum control value in % at coolingunsignedInt 0…300
Maximum control value in % at coolingunsignedInt 70…100100
Automatic return from manual adjustment (0 =inactive, min)unsignedInt 0…2550
Threshold value in % for fan speed 1 at heatingunsignedInt 0…10020
Threshold value in % for fan speed 2 at heatingunsignedInt 0…10040
Threshold value in % for fan speed 3 at heatingunsignedInt 0…10080
Fan speed for switching to comfort mode at heatinglistno change
Fan speed for switching to standby mode at heatinglistno change
Fan speed for switching to night mode at heatinglistno change
Fan speed for switching to frost/heat protection mode at heatinglistno change
Minimum control value in % at coolingunsignedInt 0…300
Threshold value in % for fan speed 1 at coolingunsignedInt 0…10020
Threshold value in % for fan speed 2 at coolingunsignedInt 0…10040
Threshold value in % for fan speed 3 at coolingunsignedInt 0…10080
Fan speed for switching to comfort mode at coolinglistno change
Fan speed for switching to standby mode at coolinglistno change
Fan speed for switching to night mode at coolinglistno change
Fan speed for switching to frost/heat protection mode at coolinglistno change
Setpoint between basic and additional heating in 1CunsignedInt 0…152
Control typelistcontinuous PI control
Symmetrical hysteresis temperature in 0.1 Celsius at heatingunsignedInt 5…5020
Symmetrical hysteresis temperature in 0.1 CelsiusunsignedInt 5…5020
Setpoint between basic and additional cooling in 1CunsignedInt 0…152
Number of fan levelslist3 levels
Switchover fan between auto and manuallistobject Automatic ON/OFF"
Temperature threshold value 1listdisable
Temperature threshold value 2listdisable
Humidity threshold value 1listdisable
Humidity threshold value 2listdisable
Temperature threshold value in 0.1 CelsiusunsignedInt 0…500250
Negative hysteresis temperature in 0.1 CelsiusunsignedInt 5…5010
If temperature is lower than threshold valuelistsend following telegram once
Logic 1bit telegram value[0..1]list0'
1byte telegram value[0..255]unsignedInt 0…2550
If temperature is upper than threshold valuelistsend following telegram once
Logic 1bit telegram value[0..1]list1'
1byte telegram value[0..255]unsignedInt 0…255255
Cycle time for temperature threshold value in min(if used)unsignedInt 1…25510
Use block of the temperature threshold outputlistno
Behaviour when setting the locklistsend the same telegram as upper threshold
Behaviour when releasing the locklistupdate
Negative hysteresis temperature in 0.1 CelsiusunsignedInt 5…5020
Behaviour when setting the locklistsend the same telegram as lower threshold
humidity threshold value in %unsignedInt 0…10060
Negative hysteresis humidity in %unsignedInt 1…102
If humidity is lower than threshold valuelistsend following telegram once
If humidity is upper than threshold valuelistsend following telegram once
Cycle time for humidity threshold value in min(if used)unsignedInt 1…25510
Use block of the humidity threshold outputlistno
Active logic functionlistdisable
Logic 1listdisable
Logic 2listdisable
The value of communication object input A after bus voltage recoverylist0'
The value of communication object input B after bus voltage recoverylist0'
input 1listdo not use
input 2listdo not use
input 3listdo not use
The logic function type between input 1 and input 2listAND
The logic function type between input 3 and result of input 1/2listAND
If logic result = '0'listsend following telegram once
1bit telegram value[0..1]list0'
If logic result = '1'listsend following telegram once
1bit telegram value[0..1]list1'
Cycle time for logic in min(if used)unsignedInt 1…25510
Use block of the logic 1 outputlistno
Behaviour when setting the locklistthe same as logic result = '0'
input 4listdo not use
input 5listdo not use
input 6listdo not use
The logic function type between input 4 and input 5listAND
The logic function type between input 6 and result of input 4/5listAND
Use block of the logic 2 outputlistno
Time 1listdisable
WeeklistMonday
HourunsignedInt 0…238
MinuteunsignedInt 0…590
Operating modelistunchange
Reaction at regular timelistNo reaction
Output valueunsignedInt 0…10
Output valueunsignedInt 0…30
Output valueunsignedInt 0…150
Output valueunsignedInt 0…2550
Output valuesignedInt -32768…327670
Output valueunsignedInt 0…655350
Output valueunsignedInt 0…42949672950
Time 2listdisable
Time 3listdisable
Time 4listdisable
Time 5listdisable
Time 6listdisable
Time 7listdisable
Operating modelistfrost/heat protection
Time 8listdisable
Time 9listdisable
Time 10listdisable
Time 11listdisable
Time 12listdisable
Time 13listdisable
Time 14listdisable
Time 15listdisable
Time 16listdisable
Pushbutton Interface Functionlistdisable
Delay time after power on[1..255s]unsignedInt 1…2551
Debounce timelist50ms
Limit number of Tele.listYes
Telegrams per 17 sencondslist127
Function of input 1listNo Function
Reaction on closing the contact (Rising edge) switch 1listOFF
Reaction on opening the contact (Falling edge) switch 1listno action
Reaction on closing the contact (Rising edge) switch 2listOFF
Reaction on opening the contact (Falling edge) switch 2listno action
Send object value after voltage recovery ( if YES not equal TOGGLE)listNo
Cyclic send Tele.Tele.switch"listalways
Interval of Tele.cyclic send: Base 1list20s
Interval of Tele.cyclic send: Base 2list20s
Factor[1..255]unsignedInt 1…25510
Long operation after (Entry * 0.1s)unsignedInt 3…25010
Reaction on short operationlistNo action
Reaction on long operationlistbrighter/darker
Step size for dimminglist1.56%
Transmission dimming stop telegramlistyes
Cyclical transmission of dimming telegramslistdisable
Time between two dimming telegramsunsignedInt 3…25010
Long operation afterunsignedInt 3…25010
Function switchover blinds/roller shuttelistShutter
Objet typelist1 BIT
Cyclical transmission tele.repetition (Entry * 0.1s)unsignedInt 3…25030
Value for position down(%)unsignedInt 0…10050
Value for position up(%)unsignedInt 0…1000
Value for slats position down(%)unsignedInt 0…10050
Value for slats position up(%)unsignedInt 0…1000
Number of sceneunsignedInt 1…641
Storage function light sceneslistdisable
Long operation afterunsignedInt 3…25030
Function of input 2listNo Function
Function of input 3listNo Function
Function of input 4listno function
Resistor of external temperature sensorlist33K
B value of external temperature sensorlist3950
Limit temperature in 1CelsiusunsignedInt 1…5035
Negative hysteresis temperature (0.1 Celsius)unsignedInt 5…505
Acting onlistbasic heating
SetpointunsignedInt 16…3225
Object type for controlling air conditionlist1 bit
Command for air condition onunsignedInt 1…641
Command for air condition offunsignedInt 1…642
Command for heating modeunsignedInt 1…643
Command for cooling modeunsignedInt 1…644
Command for fan speed highunsignedInt 1…645
Command for fan speed mediumunsignedInt 1…646
Command for fan speed lowunsignedInt 1…647
Command for fan speed auto/stopunsignedInt 1…648
Command for setpoint 16 Celsius for coolingunsignedInt 1…649
Command for setpoint 17 Celsius for coolingunsignedInt 1…6410
Command for setpoint 18 Celsius for coolingunsignedInt 1…6411
Command for setpoint 19 Celsius for coolingunsignedInt 1…6412
Command for setpoint 20 Celsius for coolingunsignedInt 1…6413
Command for setpoint 21 Celsius for coolingunsignedInt 1…6414
Command for setpoint 22 Celsius for coolingunsignedInt 1…6415
Command for setpoint 23 Celsius for coolingunsignedInt 1…6416
Command for setpoint 24 Celsius for coolingunsignedInt 1…6417
Command for setpoint 25 Celsius for coolingunsignedInt 1…6418
Command for setpoint 26 Celsius for coolingunsignedInt 1…6419
Command for setpoint 27 Celsius for coolingunsignedInt 1…6420
Command for setpoint 28 Celsius for coolingunsignedInt 1…6421
Command for setpoint 29 Celsius for coolingunsignedInt 1…6422
Command for setpoint 30 Celsius for coolingunsignedInt 1…6423
Command for setpoint 31 Celsius for coolingunsignedInt 1…6424
Command for setpoint 16 Celsius for heatingunsignedInt 1…6425
Command for setpoint 17 Celsius for heatingunsignedInt 1…6426
Command for setpoint 18 Celsius for heatingunsignedInt 1…6427
Command for setpoint 19 Celsius for heatingunsignedInt 1…6428
Command for setpoint 20 Celsius for heatingunsignedInt 1…6429
Command for setpoint 21 Celsius for heatingunsignedInt 1…6430
Command for setpoint 22 Celsius for heatingunsignedInt 1…6431
Command for setpoint 23 Celsius for heatingunsignedInt 1…6432
Command for setpoint 24 Celsius for heatingunsignedInt 1…6433
Command for setpoint 25 Celsius for heatingunsignedInt 1…6434
Command for setpoint 26 Celsius for heatingunsignedInt 1…6435
Command for setpoint 27 Celsius for heatingunsignedInt 1…6436
Command for setpoint 28 Celsius for heatingunsignedInt 1…6437
Command for setpoint 29 Celsius for heatingunsignedInt 1…6438
Command for setpoint 30 Celsius for heatingunsignedInt 1…6439
Command for setpoint 31 Celsius for heatingunsignedInt 1…6440
HourunsignedInt 0…230

Version history

ApplicationApp noFingerprintFirst seenSizeFile
KNX Temperature Control Panel 3.5" 1.0 latest$050202CB2026-11-25133 KBDownload

About this file

This is the official ETS product database for the Arlight KNX-113-35-IN (025670), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.