KNX Database

KNX-LUNOS-Control4 6500100x

Arcus-eds · Order number 6500100x · KNX-LUNOS-CONTROL4

KNX-LUNOS-Control4

Download .knxprod KNX-LUNOS-Control4 0.3 · 130 KB

Product

ManufacturerArcus-eds
Product nameKNX-LUNOS-Control4
Order number6500100x
HardwareKNX-Lunos-Ex
MediumTwisted Pair
Rail mountedNo
RegistrationRegistered · 2014-02-27
Languagesen-US, de-DE
Catalog entryM-0076_H-6500100x-1_HP-00E5-03-0D67_CI-6500100x-1
Fingerprint0D67
SHA-256e5a8c8bd9e1c9595112818408b858c5f2f3af4de4ef64282bfbc30e2f89a1464
First seen2026-11-25
Markets18 markets

Application program: KNX-LUNOS-Control4 0.3

Application number$00E5
Version0.3
Mask versionMV-0701 (7.1)
KNX Data SecureNo
Minimum ETS version3.0d
Parameters470
Group objects42
Group objects (42)
NoNameFunctionSizeDPTFlags
0Input, Operation ModeHVAC Control1 ByteDPT.5CRWU
1Input, Force Operation ModeHVAC Control1 ByteDPT.5CRWU
2Input, Night ModeHVAC Control1 BitDPT.1CRWU
3Input, Intense VentilationHVAC Control1 BitDPT.1CRWTU
3Input, Force Overwrite 1 ModeHVAC Control1 BitDPT.1CRWTU
4Input, SilenceHVAC Control1 BitDPT.1CRWTU
4Input, Force Overwrite 2 ModeHVAC Control1 BitDPT.1CRWTU
5Input, ComfortHVAC Control1 BitDPT.1CRWTU
5Input, Force Overwrite 3 ModeHVAC Control1 BitDPT.1CRWTU
6IO, Fan StageFAN Control1 Byte5.1 percentage (0..100%)CRWTU
6IO, Fan StageFAN Control1 ByteCRWTU
7IO, Manual OverwriteFAN Control1 BitDPT.1CRWTU
8Input, Fan Stage Up/DownFAN Control1 BitDPT.1CRWU
9Input, Summer ModeFAN Control1 BitDPT.1CRWU
10Input, Temperature InsideLead Temperature2 Bytes9.1 temperature (°C)CRWU
11Input, Temperature OutsideLead Temperature2 Bytes9.1 temperature (°C)CRWU
12Input, Temperature SetpointLead Temperature2 Bytes9.1 temperature (°C)CRWU
13Input, Lead Temperature EnableLead Temperature1 BitDPT.1CRWU
14Input, Humidity InsideLead Humidity2 BytesDPT.9CRWU
15Input, Humidity OutsideLead Humidity2 BytesDPT.9CRWU
16Input, Lead Humidity EnableLead Humidity1 BitDPT.1CRWU
17Input, CO2 InsideLead CO22 BytesDPT.9CRWU
18Input, Lead CO2 EnableLead CO21 BitDPT.1CRWU
19Input, Exhaust RequestExhaust/Supply Control1 Bit1.3 enableCRWU
20Input, Exhaust LockExhaust/Supply Control1 Bit1.3 enableCRWU
21Input, Air Request E²Exhaust/Supply Control1 Bit1.3 enableCRWU
21Input, Air Request EGOExhaust/Supply Control1 Bit1.3 enableCRWU
22Output, Exhaust RequestExhaust/Supply Control1 Bit1.3 enableCRT
23Output, Short PressedDry Contacts1 Bit1.1 switchCRT
23Output, Switch 1Dry Contacts1 Bit1.1 switchCRT
24Output, Long PressedDry Contacts1 Bit1.1 switchCRT
24Output, Switch 2Dry Contacts1 Bit1.1 switchCRT
25Input, System LockSystem1 Bit1.3 enableCRWU
26Output, Master/Slave ModeSystem1 Byte5.1 percentage (0..100%)CRWTU
26Input, Master/Slave ModeSystem1 Byte5.1 percentage (0..100%)CRWTU
26Output, Master/Slave ModeSystem1 ByteCRWTU
26Input, Master/Slave ModeSystem1 ByteCRWTU
27Output, Master/Slave DirectionSystem1 BitCRWTU
27Input, Master/Slave DirectionSystem1 BitCRWTU
28Output, Filter Change RequestSystem1 BitDPT.1CRWTU
29Input, Filter Change AcknowledgeSystem1 BitDPT.1CRWTU
30IO, Timeout ControlSystem2 BytesDPT.7CRWTU
Parameters (158)
ParameterTypeDefault
ConfigurationlistBasic/Master
Fan TypelistE²
DPT for StagecontrollistFan Scale [0-100%]
TemperaturelistInactive
HumiditylistInactive
IO-SelectlistInactive
CO2listInactive
Dry ContactslistInactive
Debounce Time [ms]unsignedInt 2…10010
rtr_default_modelistStandby
PrioritylistEqual
ovr1_modelistIntense Ventilation
General Overwrite Timeout [min]unsignedInt 0…24030
ovr2_modelistSilence
ovr2_timeoutunsignedInt 0…24030
ovr3_modelistComfort
ovr3_timeoutunsignedInt 0…24030
rtr_mode_0_luefterstufe_paar12unsignedInt 0…32
Summer mode objectlistby Object
Interval ModelistInactive
rtr_mode_1_luefterstufe_paar12unsignedInt 0…31
rtr_mode_2_luefterstufe_paar12unsignedInt 0…31
rtr_mode_3_luefterstufe_paar12unsignedInt 0…31
rtr_mode_4_luefterstufe_paar12unsignedInt 0…33
rtr_mode_5_luefterstufe_paar12unsignedInt 0…33
Summer mode objectlistStatic
rtr_mode_6_luefterstufe_paar12unsignedInt 0…30
ProtectionlistActive
Lead TemperaturelistActive
Lead TemperaturelistInactive
Lead HumiditylistActive
Humidity removallistInactive
Lead HumiditylistInactive
Lead CO2listActive
Lead CO2listInactive
Protection [°C]unsignedInt 5…168
Lock Control BehaviourlistSlave
Difference [°C]unsignedInt 0…100
Variable cycle timelistNo Pairs
var_rev_time_tminsignedInt -10…20-5
var_rev_time_tmaxsignedInt -10…2010
var_rev_time_ct_min1list90 s
var_rev_time_ct_max1list220 s
var_rev_time_ct_min2list70 s
var_rev_time_ct_max2list140 s
var_rev_time_ct_min3list40 s
var_rev_time_ct_max3list70 s
TH 1 [%]unsignedInt 0…9048
TH 2 [%]unsignedInt 0…9053
TH 3 [%]unsignedInt 0…9058
TH 4 [%]unsignedInt 0…9062
Minimum Gap (*0.1) [g/kg] ( Outside/Inside )unsignedInt 0…205
TH 1list800 ppm
TH 2list1000 ppm
TH 3list1500 ppm
TH 4list2000 ppm
Double Presslist500 ms
Long Presslist800 ms
Short FunctionlistSpeed Up/Down
Timeout [min]unsignedInt 0…24030
Long FunctionlistOff
Double FunctionlistIntense Ventilation
Switch Functionlistintern
Function Switch 2 [OFF]listFan Stage 1
Function Switch 2 [ON]listFan Stage 3
OverwritelistBoth Pairs
Reversion_time_1list200 s
Reversion_time_2list140 s
Reversion_time_3list70 s
Reversion_time_summerlist1 h
Hight above sea level [m]unsignedInt 0…200050
Fan 1 [mOhm]unsignedInt 0…20000
Fan 2 [mOhm]unsignedInt 0…20000
Fan 3 [mOhm]unsignedInt 0…20000
Fan 4 [mOhm]unsignedInt 0…20000
Interval period --- Active timelist1 h --- 15 min
flow_rate_stage1unsignedInt 5…1005
flow_rate_stage2unsignedInt 5…10010
flow_rate_stage3unsignedInt 5…10020
Flow1unsignedInt 5…1005
Exhaust1unsignedInt 0…100004500
Supply1unsignedInt 0…100005500
Flow2unsignedInt 5…10017
Exhaust2unsignedInt 0…100004093
Supply2unsignedInt 0…100006727
Flow3unsignedInt 5…10032
Exhaust3unsignedInt 0…100002373
Supply3unsignedInt 0…100008457
Flow4unsignedInt 5…10038
Exhaust4unsignedInt 0…1000015
Supply4unsignedInt 0…100009759
Pair 1 -- Pair 2listNone -- None
Flow per Fan [m³/h]unsignedInt 5…10032
Balance Supply 1unsignedInt 0…25520
Balance Supply 2unsignedInt 0…25517
Balance Supply 3unsignedInt 0…2557
Balance Supply 4unsignedInt 0…25512
Balance Exhaust 1unsignedInt 0…2553
Balance Exhaust 2unsignedInt 0…25512
Balance Exhaust 3unsignedInt 0…25515
Balance Exhaust 4unsignedInt 0…25510
Flow [m³/h]unsignedInt 5…10032
Lead Timelist2 min
Lag Time [min]unsignedInt 0…6015
Exhaust Fan TypelistSilvento FK
Basic Flow [m³/h]unsignedInt 5…10030
Active Flow [m³/h]unsignedInt 5…10050
Flow [m³/h]unsignedInt 5…1005
Exhaust [mV]unsignedInt 0…100001000
abluft_pnt1_supplyunsignedInt 0…100005500
Flow [m³/h]unsignedInt 5…10030
Exhaust [mV]unsignedInt 0…100005000
abluft_pnt2_supplyunsignedInt 0…100008457
Flow [m³/h]unsignedInt 5…10060
Exhaust [mV]unsignedInt 0…1000010000
abluft_pnt3_supplyunsignedInt 0…100009759
Basic Flow [m³/h]list30 m³/h
Active Flow [m³/h]list50 m³/h
abluft_pnt1_flowunsignedInt 5…1005
abluft_pnt1_exhaustunsignedInt 0…100001000
abluft_pnt2_flowunsignedInt 5…10030
abluft_pnt2_exhaustunsignedInt 0…100005000
abluft_pnt3_flowunsignedInt 5…10060
abluft_pnt3_exhaustunsignedInt 0…1000010000
Basic Flow [m³/h]list15 m³/h
Active Flow [m³/h]list30 m³/h
Basic Flow [m³/h]listStage 1
Active Flow [m³/h]listStage 3
Interval period --- Active timelistStatic
Pair 1listNone
Default ModelistStandby
OW 1 ModelistIntense Ventilation
OW 2 ModelistSilence
OW 3 ModelistComfort
Fan StageunsignedInt 0…32
Humidity RemovallistInactive
Sommer Modelistby Object
Fan StageunsignedInt 0…31
Fan StageunsignedInt 0…33
Sommer ModelistStatic
Fan StageunsignedInt 0…30
Dynamic Cycle Time ( depends on Outside Temperature )listNo Pairs
Minimum [°C]signedInt -10…20-5
Maximum [°C]signedInt -10…2010
Minimumlist90 s
Maximumlist220 s
Minimumlist70 s
Maximumlist140 s
Minimumlist40 s
Maximumlist70 s
Stage 1list200 s
Stage 2list140 s
Stage 3list70 s
Summer Modelist1 h
Fan flow ratelistDefault
Stage 1 [m³/h]unsignedInt 5…1005
Stage 2 [m³/h]unsignedInt 5…10010
Stage 3 [m³/h]unsignedInt 5…10020

Version history

ApplicationApp noFingerprintFirst seenSizeFile
KNX-LUNOS-Control4 0.3 latest$00E50D672026-11-25130 KBDownload

About this file

This is the official ETS product database for the Arcus-eds KNX-LUNOS-Control4 (6500100x), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.