KNX-LUNOS-CONTROL4-IW 65001002
Arcus-eds · Order number 65001002 · KNX-LUNOS-CONTROL4
In-wall mounted KNX-LUNOS-CONTROL4 module controls up to 4 decentralized ventilation devices from Lunos.
Download .knxprod KNX-Lunos-Control4 0.5 · 97 KB
Product
| Manufacturer | Arcus-eds |
|---|---|
| Product name | KNX-LUNOS-CONTROL4-IW |
| Order number | 65001002 |
| Hardware | KNX-Lunos-Ex |
| Medium | Twisted Pair |
| Bus current (mA) | 10 |
| Rail mounted | No |
| Registration | Registered · 2022-03-28 |
| Languages | en-US, de-DE |
| Catalog entry | M-0076_H-6500100x-2_HP-00E5-05-15D0_CI-65001002-1 |
| Fingerprint | 15D0 |
| SHA-256 | 2f794c922914821fe6dc77abe24a84cf9de454a28a0ac75fae9586998aba0fe8 |
| First seen | 2026-11-25 |
| Markets | 16 markets |
Application program: KNX-Lunos-Control4 0.5
| Application number | $00E5 |
|---|---|
| Version | 0.5 |
| Mask version | MV-0701 (7.1) |
| KNX Data Secure | No |
| Minimum ETS version | 4.0 |
| Parameters | 202 |
| Group objects | 48 |
Group objects (48)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Input, Operation Mode | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRWU |
| 0 | Input, Ventilation Stage | Ventilation Mode | 1 Byte | DPT.5 | CRWU |
| 1 | Input, Force Operation Mode | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRWU |
| 1 | Input, Force Ventilation Stage | Ventilation Mode | 1 Byte | DPT.5 | CRWU |
| 2 | Input, Night Mode | HVAC Mode | 1 Bit | 1.2 boolean | CRWU |
| 3 | Input, Intense Ventilation | HVAC Mode | 1 Bit | 1.2 boolean | CRWTU |
| 3 | Input, Force Overwrite 1 Mode | HVAC Mode | 1 Bit | 1.2 boolean | CRWTU |
| 3 | Input, Force Stage 3 | Ventilation Mode | 1 Bit | 1.2 boolean | CRWTU |
| 3 | Input, Force Overwrite 1 Mode | Ventilation Mode | 1 Bit | 1.2 boolean | CRWTU |
| 4 | Input, Silence | HVAC Mode | 1 Bit | 1.2 boolean | CRWTU |
| 4 | Input, Force Overwrite 2 Mode | HVAC Mode | 1 Bit | 1.2 boolean | CRWTU |
| 4 | Input, Force Stage Off | Ventilation Mode | 1 Bit | 1.2 boolean | CRWTU |
| 4 | Input, Force Overwrite 2 Mode | Ventilation Mode | 1 Bit | 1.2 boolean | CRWTU |
| 5 | Input, Comfort | HVAC Mode | 1 Bit | 1.2 boolean | CRWTU |
| 5 | Input, Force Overwrite 3 Mode | HVAC Mode | 1 Bit | 1.2 boolean | CRWTU |
| 5 | Input, Force Stage 2 | Ventilation Mode | 1 Bit | 1.2 boolean | CRWTU |
| 5 | Input, Force Overwrite 3 Mode | Ventilation Mode | 1 Bit | 1.2 boolean | CRWTU |
| 6 | IO, Fan Stage | FAN Control | 1 Byte | DPT.5 | CRWTU |
| 7 | IO, Manual Overwrite | FAN Control | 1 Bit | 1.3 enable | CRWTU |
| 8 | Input, Fan Stage Up/Down | FAN Control | 1 Bit | 1.8 up/down | CRWU |
| 9 | Input, Summer Mode | FAN Control | 1 Bit | 1.2 boolean | CRWU |
| 10 | Input, Temperature Inside | Lead Temperature | 2 Bytes | 9.1 temperature (°C) | CRWU |
| 11 | Input, Temperature Outside | Lead Temperature | 2 Bytes | 9.1 temperature (°C) | CRWU |
| 12 | Input, Temperature Setpoint | Lead Temperature | 2 Bytes | 9.1 temperature (°C) | CRWU |
| 13 | Input, Lead Temperature Enable | Lead Temperature | 1 Bit | 1.3 enable | CRWU |
| 14 | Input, Humidity Inside | Lead Humidity | 2 Bytes | 9.7 humidity (%) | CRWU |
| 15 | Input, Humidity Outside | Lead Humidity | 2 Bytes | 9.7 humidity (%) | CRWU |
| 16 | Input, Lead Humidity Enable | Lead Humidity | 1 Bit | 1.3 enable | CRWU |
| 17 | Input, CO2 Inside | Lead CO2 | 2 Bytes | 9.8 parts/million (ppm) | CRWU |
| 18 | Input, Lead CO2 Enable | Lead CO2 | 1 Bit | 1.3 enable | CRWU |
| 19 | Input, Exhaust Request | Exhaust/Supply Control | 1 Bit | 1.2 boolean | CRWU |
| 20 | Input, Exhaust Lock | Exhaust/Supply Control | 1 Bit | 1.2 boolean | CRWU |
| 21 | Input, Air Request {{117}} | Exhaust/Supply Control | 1 Bit | 1.2 boolean | CRWU |
| 22 | Output, Exhaust Request | Exhaust/Supply Control | 1 Bit | 1.2 boolean | CRT |
| 23 | Output, Short Pressed | Dry Contacts | 1 Bit | 1.1 switch | CRT |
| 23 | Output, Switch 1 | Dry Contacts | 1 Bit | 1.1 switch | CRT |
| 24 | Output, Switch 2 | Dry Contacts | 1 Bit | 1.1 switch | CRT |
| 24 | Output, Long Pressed | Dry Contacts | 1 Bit | 1.1 switch | CRT |
| 25 | Input, System Lock | System | 1 Bit | 1.2 boolean | CRWU |
| 26 | Output, Master/Slave Mode | System | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 26 | Input, Master/Slave Mode | System | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 26 | Input, Master/Slave Mode | System | 1 Byte | DPT.5 | CRWTU |
| 26 | Output, Master/Slave Mode | System | 1 Byte | DPT.5 | CRWTU |
| 27 | Output, Master/Slave Direction | System | 1 Bit | 1.2 boolean | CRWTU |
| 27 | Input, Master/Slave Direction | System | 1 Bit | 1.2 boolean | CRWTU |
| 28 | Output, Filter Change Request | System | 1 Bit | 1.5 alarm | CRWTU |
| 29 | Input, Filter Change Acknowledge | System | 1 Bit | 1.16 acknowledge | CRWTU |
| 30 | IO, Timeout Control | System | 2 Bytes | 7.5 time (s) | CRWTU |
Parameters (135)
| Parameter | Type | Default |
|---|---|---|
| Temperature | list | Inactive |
| Selection | list | Inactive |
| Humidity | list | Inactive |
| CO2 | list | Inactive |
| Fan Stage | list | Stage 2 |
| Fan Stage | list | Stage 1 |
| Fan Stage | list | Stage 3 |
| Fan Stage | list | Off |
| Balance Supply 1 [*10 mV] | signedInt -128…127 | 0 |
| Balance Supply 2 [*10 mV] | signedInt -128…127 | 0 |
| Balance Supply 3 [*10 mV] | signedInt -128…127 | 0 |
| Balance Supply 4 [*10 mV] | signedInt -128…127 | 0 |
| Balance Exhaust 1 [*10 mV] | signedInt -128…127 | 0 |
| Balance Exhaust 2 [*10 mV] | signedInt -128…127 | 0 |
| Balance Exhaust 3 [*10 mV] | signedInt -128…127 | 0 |
| Balance Exhaust 4 [*10 mV] | signedInt -128…127 | 0 |
| Protection | list | Active |
| Lead CO2 | list | Active |
| Humidity Removal | list | Inactive |
| Interval Mode | list | Inactive |
| Lead Humidity | list | Active |
| Lead Temperature | list | Active |
| Sommer Mode | list | by Object |
| Lead Temperature | list | Inactive |
| Lead CO2 | list | Inactive |
| Lead Humidity | list | Inactive |
| Sommer Mode | list | Static |
| Settings | list | 1 h --- 15 min |
| Selection | list | Silvento FK |
| Priority | list | Equal |
| DPT for Stagecontrol | list | Fan Scale [0-100%] |
| Interval period --- Active time | list | Static |
| Timeout [min] | unsignedInt 0…240 | 30 |
| Pair 1 -- Pair 2 | list | None -- None |
| Pair 1 | list | None |
| Overwrite | list | Both Pairs |
| Protection [°C] | unsignedInt 5…16 | 8 |
| Lock Control Behaviour | list | Slave |
| Gap [°C] | unsignedInt 0…10 | 0 |
| TH 1 [%] | unsignedInt 0…90 | 48 |
| TH 2 [%] | unsignedInt 0…90 | 53 |
| TH 3 [%] | unsignedInt 0…90 | 58 |
| TH 4 [%] | unsignedInt 0…90 | 62 |
| Minimum Gap (*0.1) [g/kg] ( Outside/Inside ) | unsignedInt 0…20 | 5 |
| TH 1 | list | 800 ppm |
| TH 2 | list | 1000 ppm |
| TH 3 | list | 1500 ppm |
| TH 4 | list | 2000 ppm |
| Lag Time [min] | unsignedInt 0…60 | 15 |
| Lead Time | list | 2 min |
| Basic Flow [%] | unsignedInt 0…100 | 30 |
| Basic Flow [m³/h] | list | 30 m³/h |
| Basic Flow [m³/h] | list | 15 m³/h |
| Basic Flow [m³/h] | list | 0 m³/h |
| Configuration | list | Basic/Master |
| Fan 1 [mOhm] | unsignedInt 0…2000 | 0 |
| Fan 2 [mOhm] | unsignedInt 0…2000 | 0 |
| Fan 3 [mOhm] | unsignedInt 0…2000 | 0 |
| Fan 4 [mOhm] | unsignedInt 0…2000 | 0 |
| Flow 1 [m³/h] | unsignedInt 0…100 | 5 |
| Exhaust 1 [mV] | unsignedInt 0…10000 | 4500 |
| Supply 1 [mV] | unsignedInt 0…10000 | 5500 |
| Flow 2 [m³/h] | unsignedInt 0…100 | 17 |
| Exhaust 2 [mV] | unsignedInt 0…10000 | 4093 |
| Supply 2 [mV] | unsignedInt 0…10000 | 6727 |
| Flow 3 [m³/h] | unsignedInt 0…100 | 32 |
| Exhaust 3 [mV] | unsignedInt 0…10000 | 2373 |
| Supply 3 [mV] | unsignedInt 0…10000 | 8457 |
| Flow 4 [m³/h] | unsignedInt 0…100 | 38 |
| Exhaust 4 [mV] | unsignedInt 0…10000 | 15 |
| Supply 4 [mV] | unsignedInt 0…10000 | 9759 |
| Flow [m³/h] | unsignedInt 0…100 | 15 |
| Exhaust [mV] | unsignedInt 0…10000 | 1570 |
| Supply [mV] | unsignedInt 0…10000 | 0 |
| Flow [m³/h] | unsignedInt 0…100 | 30 |
| Exhaust [mV] | unsignedInt 0…10000 | 3560 |
| Flow [m³/h] | unsignedInt 0…100 | 60 |
| Exhaust [mV] | unsignedInt 0…10000 | 8150 |
| Double Press | list | 500 ms |
| Long Press | list | 800 ms |
| Switch Function | list | intern |
| Short Function | list | Speed Up/Down |
| Long Function | list | Off |
| Function Switch 2 [OFF] | list | Fan Stage 1 |
| Double Function | list | Intense Ventilation |
| Function Switch 2 [ON] | list | Fan Stage 3 |
| Debounce Time [ms] | unsignedInt 2…100 | 10 |
| Hight above sea level [m] | unsignedInt 0…2000 | 50 |
| Fan Type | list | E² |
| Operation Setup | list | HVAC Mode |
| ShowRuler_V | list | No |
| Stage 1 | list | 70 s |
| Stage 1 | list | 60 s |
| Stage 1 | list | 50 s |
| Stage 2 | list | 70 s |
| Stage 2 | list | 60 s |
| Stage 2 | list | 50 s |
| Stage 3 | list | 70 s |
| Stage 3 | list | 60 s |
| Stage 3 | list | 50 s |
| Summer Mode | list | 1 h |
| Summer Mode Nexxt | signedInt 0…0 | 0 |
| OW 2 Mode | list | Silence |
| OW 2 Mode | list | Off |
| OW 1 Mode | list | Intense Ventilation |
| OW 1 Mode | list | Stage 3 |
| OW 3 Mode | list | Comfort |
| OW 3 Mode | list | Stage 2 |
| Default Mode | list | Standby |
| Default Mode | list | Stage 1 |
| Active Flow [%] | unsignedInt 0…100 | 50 |
| Active Flow [m³/h] | list | 60 m³/h |
| Active Flow [m³/h] | list | 100 m³/h |
| ShowInterval_V | list | No |
| Stage 1 | list | 15 m³/h |
| Stage 1 | list | 5 m³/h |
| Stage 1 | list | 17 m³/h |
| Stage 1 | list | Speed 1 |
| Stage 2 | list | 25 m³/h |
| Stage 2 | list | 15 m³/h |
| Stage 2 | list | 20 m³/h |
| Stage 2 | list | 26 m³/h |
| Stage 2 | list | Speed 5 |
| Stage 3 | list | 38 m³/h |
| Stage 3 | list | 20 m³/h |
| Stage 3 | list | Speed 8 |
| ShowLead_V | list | No |
| ShowRequestCom_V | list | No |
| COM_Request_Rename_V | text | |
| Flow per Fan | list | 38 m³/h |
| Flow per Fan | list | 20 m³/h |
| Flow per Fan | list | Speed 8 |
| Stage 2 | list | 40 m³/h |
| Stage 3 | list | 60 m³/h |
| Flow per Fan | list | 60 m³/h |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| KNX-Lunos-Control4 0.5 latest | $00E5 | 15D0 | 2026-11-25 | 97 KB | Download |
About this file
This is the official ETS product database for the Arcus-eds KNX-LUNOS-CONTROL4-IW (65001002), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Arcus-eds
- KNX-LUNOS-CONTROL4-REG4 65001004
- KNX-LUNOS-Control4 6500100x
- SK80_F 1180440001
- Touch_IT-Plugin 22310xxx
- Sensor Temperature IP65 30101xxx
- Sensor Temperature SK03 30103xxx
- Sensor Temperature/Humidity 30201xxx
- Sensor Temperature/Humidity SK03 30203xxx
- Sensor Temperature/Humidity/Climatecontrol IP65 30301xxx
- Sensor Temperature/Humidity/Climatecontrol SK02 30302xxx
- Sensor Temperature/Humidity/Climatecontrol SK03 30303xxx
- Sensor Temperature/Humidity/Climatecontrol+ IP65 30401xxx