KNX Database

KNX-LUNOS-CONTROL4-REG4 65001004

Arcus-eds · Order number 65001004 · KNX-LUNOS-CONTROL4

Rail mounted KNX-LUNOS-CONTROL4 module controls up to 4 decentralized ventilation devices from Lunos.

Download .knxprod KNX-Lunos-Control4 0.5 · 97 KB

Product

ManufacturerArcus-eds
Product nameKNX-LUNOS-CONTROL4-REG4
Order number65001004
HardwareKNX-Lunos-Ex
MediumTwisted Pair
Bus current (mA)10
Rail mountedYes
Width (mm)72
RegistrationRegistered · 2022-03-28
Languagesen-US, de-DE
Catalog entryM-0076_H-6500100x-2_HP-00E5-05-15D0_CI-65001004-1
Fingerprint15D0
SHA-256d5dc34c023f4c56f4af6677eac2cf8c38ef8c7df6db0ceca16e8060fc4872d0d
First seen2026-11-25
Markets16 markets

Application program: KNX-Lunos-Control4 0.5

Application number$00E5
Version0.5
Mask versionMV-0701 (7.1)
KNX Data SecureNo
Minimum ETS version4.0
Parameters202
Group objects48
Group objects (48)
NoNameFunctionSizeDPTFlags
0Input, Operation ModeHVAC Mode1 Byte20.102 HVAC modeCRWU
0Input, Ventilation StageVentilation Mode1 ByteDPT.5CRWU
1Input, Force Operation ModeHVAC Mode1 Byte20.102 HVAC modeCRWU
1Input, Force Ventilation StageVentilation Mode1 ByteDPT.5CRWU
2Input, Night ModeHVAC Mode1 Bit1.2 booleanCRWU
3Input, Intense VentilationHVAC Mode1 Bit1.2 booleanCRWTU
3Input, Force Overwrite 1 ModeHVAC Mode1 Bit1.2 booleanCRWTU
3Input, Force Stage 3Ventilation Mode1 Bit1.2 booleanCRWTU
3Input, Force Overwrite 1 ModeVentilation Mode1 Bit1.2 booleanCRWTU
4Input, SilenceHVAC Mode1 Bit1.2 booleanCRWTU
4Input, Force Overwrite 2 ModeHVAC Mode1 Bit1.2 booleanCRWTU
4Input, Force Stage OffVentilation Mode1 Bit1.2 booleanCRWTU
4Input, Force Overwrite 2 ModeVentilation Mode1 Bit1.2 booleanCRWTU
5Input, ComfortHVAC Mode1 Bit1.2 booleanCRWTU
5Input, Force Overwrite 3 ModeHVAC Mode1 Bit1.2 booleanCRWTU
5Input, Force Stage 2Ventilation Mode1 Bit1.2 booleanCRWTU
5Input, Force Overwrite 3 ModeVentilation Mode1 Bit1.2 booleanCRWTU
6IO, Fan StageFAN Control1 ByteDPT.5CRWTU
7IO, Manual OverwriteFAN Control1 Bit1.3 enableCRWTU
8Input, Fan Stage Up/DownFAN Control1 Bit1.8 up/downCRWU
9Input, Summer ModeFAN Control1 Bit1.2 booleanCRWU
10Input, Temperature InsideLead Temperature2 Bytes9.1 temperature (°C)CRWU
11Input, Temperature OutsideLead Temperature2 Bytes9.1 temperature (°C)CRWU
12Input, Temperature SetpointLead Temperature2 Bytes9.1 temperature (°C)CRWU
13Input, Lead Temperature EnableLead Temperature1 Bit1.3 enableCRWU
14Input, Humidity InsideLead Humidity2 Bytes9.7 humidity (%)CRWU
15Input, Humidity OutsideLead Humidity2 Bytes9.7 humidity (%)CRWU
16Input, Lead Humidity EnableLead Humidity1 Bit1.3 enableCRWU
17Input, CO2 InsideLead CO22 Bytes9.8 parts/million (ppm)CRWU
18Input, Lead CO2 EnableLead CO21 Bit1.3 enableCRWU
19Input, Exhaust RequestExhaust/Supply Control1 Bit1.2 booleanCRWU
20Input, Exhaust LockExhaust/Supply Control1 Bit1.2 booleanCRWU
21Input, Air Request {{117}}Exhaust/Supply Control1 Bit1.2 booleanCRWU
22Output, Exhaust RequestExhaust/Supply Control1 Bit1.2 booleanCRT
23Output, Short PressedDry Contacts1 Bit1.1 switchCRT
23Output, Switch 1Dry Contacts1 Bit1.1 switchCRT
24Output, Switch 2Dry Contacts1 Bit1.1 switchCRT
24Output, Long PressedDry Contacts1 Bit1.1 switchCRT
25Input, System LockSystem1 Bit1.2 booleanCRWU
26Output, Master/Slave ModeSystem1 Byte5.1 percentage (0..100%)CRWTU
26Input, Master/Slave ModeSystem1 Byte5.1 percentage (0..100%)CRWTU
26Input, Master/Slave ModeSystem1 ByteDPT.5CRWTU
26Output, Master/Slave ModeSystem1 ByteDPT.5CRWTU
27Output, Master/Slave DirectionSystem1 Bit1.2 booleanCRWTU
27Input, Master/Slave DirectionSystem1 Bit1.2 booleanCRWTU
28Output, Filter Change RequestSystem1 Bit1.5 alarmCRWTU
29Input, Filter Change AcknowledgeSystem1 Bit1.16 acknowledgeCRWTU
30IO, Timeout ControlSystem2 Bytes7.5 time (s)CRWTU
Parameters (135)
ParameterTypeDefault
TemperaturelistInactive
SelectionlistInactive
HumiditylistInactive
CO2listInactive
Fan StagelistStage 2
Fan StagelistStage 1
Fan StagelistStage 3
Fan StagelistOff
Balance Supply 1 [*10 mV]signedInt -128…1270
Balance Supply 2 [*10 mV]signedInt -128…1270
Balance Supply 3 [*10 mV]signedInt -128…1270
Balance Supply 4 [*10 mV]signedInt -128…1270
Balance Exhaust 1 [*10 mV]signedInt -128…1270
Balance Exhaust 2 [*10 mV]signedInt -128…1270
Balance Exhaust 3 [*10 mV]signedInt -128…1270
Balance Exhaust 4 [*10 mV]signedInt -128…1270
ProtectionlistActive
Lead CO2listActive
Humidity RemovallistInactive
Interval ModelistInactive
Lead HumiditylistActive
Lead TemperaturelistActive
Sommer Modelistby Object
Lead TemperaturelistInactive
Lead CO2listInactive
Lead HumiditylistInactive
Sommer ModelistStatic
Settingslist1 h --- 15 min
SelectionlistSilvento FK
PrioritylistEqual
DPT for StagecontrollistFan Scale [0-100%]
Interval period --- Active timelistStatic
Timeout [min]unsignedInt 0…24030
Pair 1 -- Pair 2listNone -- None
Pair 1listNone
OverwritelistBoth Pairs
Protection [°C]unsignedInt 5…168
Lock Control BehaviourlistSlave
Gap [°C]unsignedInt 0…100
TH 1 [%]unsignedInt 0…9048
TH 2 [%]unsignedInt 0…9053
TH 3 [%]unsignedInt 0…9058
TH 4 [%]unsignedInt 0…9062
Minimum Gap (*0.1) [g/kg] ( Outside/Inside )unsignedInt 0…205
TH 1list800 ppm
TH 2list1000 ppm
TH 3list1500 ppm
TH 4list2000 ppm
Lag Time [min]unsignedInt 0…6015
Lead Timelist2 min
Basic Flow [%]unsignedInt 0…10030
Basic Flow [m³/h]list30 m³/h
Basic Flow [m³/h]list15 m³/h
Basic Flow [m³/h]list0 m³/h
ConfigurationlistBasic/Master
Fan 1 [mOhm]unsignedInt 0…20000
Fan 2 [mOhm]unsignedInt 0…20000
Fan 3 [mOhm]unsignedInt 0…20000
Fan 4 [mOhm]unsignedInt 0…20000
Flow 1 [m³/h]unsignedInt 0…1005
Exhaust 1 [mV]unsignedInt 0…100004500
Supply 1 [mV]unsignedInt 0…100005500
Flow 2 [m³/h]unsignedInt 0…10017
Exhaust 2 [mV]unsignedInt 0…100004093
Supply 2 [mV]unsignedInt 0…100006727
Flow 3 [m³/h]unsignedInt 0…10032
Exhaust 3 [mV]unsignedInt 0…100002373
Supply 3 [mV]unsignedInt 0…100008457
Flow 4 [m³/h]unsignedInt 0…10038
Exhaust 4 [mV]unsignedInt 0…1000015
Supply 4 [mV]unsignedInt 0…100009759
Flow [m³/h]unsignedInt 0…10015
Exhaust [mV]unsignedInt 0…100001570
Supply [mV]unsignedInt 0…100000
Flow [m³/h]unsignedInt 0…10030
Exhaust [mV]unsignedInt 0…100003560
Flow [m³/h]unsignedInt 0…10060
Exhaust [mV]unsignedInt 0…100008150
Double Presslist500 ms
Long Presslist800 ms
Switch Functionlistintern
Short FunctionlistSpeed Up/Down
Long FunctionlistOff
Function Switch 2 [OFF]listFan Stage 1
Double FunctionlistIntense Ventilation
Function Switch 2 [ON]listFan Stage 3
Debounce Time [ms]unsignedInt 2…10010
Hight above sea level [m]unsignedInt 0…200050
Fan TypelistE²
Operation SetuplistHVAC Mode
ShowRuler_VlistNo
Stage 1list70 s
Stage 1list60 s
Stage 1list50 s
Stage 2list70 s
Stage 2list60 s
Stage 2list50 s
Stage 3list70 s
Stage 3list60 s
Stage 3list50 s
Summer Modelist1 h
Summer Mode NexxtsignedInt 0…00
OW 2 ModelistSilence
OW 2 ModelistOff
OW 1 ModelistIntense Ventilation
OW 1 ModelistStage 3
OW 3 ModelistComfort
OW 3 ModelistStage 2
Default ModelistStandby
Default ModelistStage 1
Active Flow [%]unsignedInt 0…10050
Active Flow [m³/h]list60 m³/h
Active Flow [m³/h]list100 m³/h
ShowInterval_VlistNo
Stage 1list15 m³/h
Stage 1list5 m³/h
Stage 1list17 m³/h
Stage 1listSpeed 1
Stage 2list25 m³/h
Stage 2list15 m³/h
Stage 2list20 m³/h
Stage 2list26 m³/h
Stage 2listSpeed 5
Stage 3list38 m³/h
Stage 3list20 m³/h
Stage 3listSpeed 8
ShowLead_VlistNo
ShowRequestCom_VlistNo
COM_Request_Rename_Vtext
Flow per Fanlist38 m³/h
Flow per Fanlist20 m³/h
Flow per FanlistSpeed 8
Stage 2list40 m³/h
Stage 3list60 m³/h
Flow per Fanlist60 m³/h

Version history

ApplicationApp noFingerprintFirst seenSizeFile
KNX-Lunos-Control4 0.5 latest$00E515D02026-11-2597 KBDownload

About this file

This is the official ETS product database for the Arcus-eds KNX-LUNOS-CONTROL4-REG4 (65001004), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.