KNX Database

S8-F 30807XXX

Arcus-eds · Order number 30807XXX · Arc_S8

Download .knxprod S8-F 1.5 · 76 KB

Product

ManufacturerArcus-eds
Product nameS8-F
Order number30807XXX
HardwareS8-F
MediumTwisted Pair
Rail mountedNo
RegistrationCertified · 2011-12-07
Languagesen-US, de-DE
Catalog entryM-0076_H-30807XXX-0_HP-002B-15-0F70_CI-30807XXX-1
Fingerprint0F70
SHA-256b49928f8e933c5594a31294f3cf775ef63bca78c54b518e2fd474d50f8d4b926
First seen2026-11-25
Markets18 markets

Application program: S8-F 1.5

Application number$002B
Version1.5
Mask versionMV-0701 (7.1)
KNX Data SecureNo
Minimum ETS version3.0d
Parameters158
Group objects50
Group objects (50)
NoNameFunctionSizeDPTFlags
2Output, measured volume fill levelMeasured value2 Bytes7.1 pulsesCRT
2Output, measured volume fill levelMeasured value2 Bytes9.1 temperature (°C)CRT
2Output, measured volume fill levelMeasured value4 Bytes12.1 counter pulses (unsigned)CRT
2Output, measured volume fill levelMeasured value4 Bytes14.76 volume (m³)CRT
3Input, auxiliary volume fill levelAuxiliary variable2 Bytes7.1 pulsesCRWU
3Input, auxiliary volume fill levelAuxiliary variable2 Bytes9.1 temperature (°C)CRWU
3Input, auxiliary volume fill levelAuxiliary variable4 Bytes12.1 counter pulses (unsigned)CRWU
3Input, auxiliary volume fill levelAuxiliary variable4 Bytes14.76 volume (m³)CRWU
4Output, upper limit volume fill levelLimit1 Bit1.2 booleanCRT
5Output, lower limit volume fill levelLimit1 Bit1.2 booleanCRT
6Output, controller volume fill levelcontrol variable1 Bit1.1 switchCRT
7Input, enable/lock volume fill levelEnable/lock1 Bit1.1 switchCRWU
8Output status volume fill levelChannel status1 ByteCRT
9Output, measured levelMeasured value2 Bytes7.1 pulsesCRT
9Output, measured levelMeasured value2 Bytes9.1 temperature (°C)CRT
9Output, measured levelMeasured value4 Bytes12.1 counter pulses (unsigned)CRT
9Output, measured levelMeasured value4 Bytes14.39 length (m)CRT
10Input, auxiliary object levelAuxiliary variable2 Bytes7.1 pulsesCRWU
10Input, auxiliary object levelAuxiliary variable2 Bytes9.1 temperature (°C)CRWU
10Input, auxiliary object levelAuxiliary variable4 Bytes12.1 counter pulses (unsigned)CRWU
10Input, auxiliary object levelAuxiliary variable4 Bytes14.39 length (m)CRWU
11Output, upper limit levelLimit1 Bit1.2 booleanCRT
12Output, lower limit levelLimit1 Bit1.2 booleanCRT
13Output, controller levelcontrol variable1 Bit1.1 switchCRT
14Input, enable/lock levelEnable/lock1 Bit1.1 switchCRWU
15Output status levelChannel status1 ByteCRT
16Output, measured distanceMeasured value2 Bytes7.1 pulsesCRT
16Output, measured distanceMeasured value2 Bytes9.1 temperature (°C)CRT
16Output, measured distanceMeasured value4 Bytes12.1 counter pulses (unsigned)CRT
16Output, measured distanceMeasured value4 Bytes14.39 length (m)CRT
17Input, auxiliary object distanceAuxiliary variable2 Bytes7.1 pulsesCRWU
17Input, auxiliary object distanceAuxiliary variable2 Bytes9.1 temperature (°C)CRWU
17Input, auxiliary object distanceAuxiliary variable4 Bytes12.1 counter pulses (unsigned)CRWU
17Input, auxiliary object distanceAuxiliary variable4 Bytes14.39 length (m)CRWU
18Output, upper limit distanceLimit1 Bit1.2 booleanCRT
19Output, lower limit distanceLimit1 Bit1.2 booleanCRT
20Output, controller distanceControl variable1 Bit1.1 switchCRT
21Input, enable/lock distanceEnable/lock1 Bit1.1 switchCRWU
22Output status distanceChannel status1 ByteCRT
23Output, measured volume fill level %Measured value1 Byte5.10 counter pulses (0..255)CRT
24Input, auxiliary object volume fill level %Auxiliary variable1 Byte5.10 counter pulses (0..255)CRWU
25Output, upper limit volume fill level %Limit1 Bit1.2 booleanCRT
26Output, lower limit volume fill level %Limit1 Bit1.2 booleanCRT
27Output, controller volume fill level %control variable1 Bit1.1 switchCRT
28Input, enable/lock volume fill level %Enable/lock1 Bit1.1 switchCRWU
29Output status volume fill level %Channel status1 ByteCRT
30Output, measured output 1Measured value1 Bit1.1 switchCRT
37Output, measured output 2Measured value1 Bit1.1 switchCRT
58Equipment timeTime3 Bytes10.1 time of dayCRWU
59Equipment dateDate3 Bytes11.1 dateCRWU
Parameters (75)
ParameterTypeDefault
General settingslist0
Peroiod measured value send periodicallist1 min
Actuating value send cycle period (Seconds)unsignedInt 10…25060
KalibrierungszeitunsignedInt 0…25590
use clock timerlistno
timer untilunsignedInt 0…240
timer fromunsignedInt 0…2424
Volume fill levellist0
Measured value send periodicallistno
Measured value send by changelistno
Unit volume fill levellistLiter (l)
Type datapointlist4byte float
Auxiliary object islistSetpoint
Auxiliary value store by changelistno
Lower limitsignedInt -32000…320001
Unit lower limitlistLiter (l)
Upper limitsignedInt -32000…320001
Unit upper limitlistLiter (l)
MultiplikatorsignedInt -32768…327671
Kalibrierung 2signedInt -32768…327670
Kalibrierung 2 ExponentsignedInt -100…1000
Differential gaps send/limitssignedInt -32000…320001
Unit differential gaps send/limitslistLiter (l)
Controller volume fill levellist0
Locking objectlistlocked if 1
Actuating variable at rising actual valuelistdecreasing
ControllerlistTwo-level controller
SetpointsignedInt -32000…320001
Unit SetpointlistLiter (l)
Differential gap ControllersignedInt -32000…320001
Unit differential gap ControllerlistLiter (l)
Actuating variable send periodicallistno
duty cycle in %unsignedInt 0…500
Cycle duration in secondsunsignedInt 0…6553560
Levellist0
Level unitlistm
Unit lower limitlistm
Unit upper limitlistm
Unit differential gaps send/limitslistm
Controller levellist0
Unit setpointlistm
Unit differential gap Controllerlistm
Distancelist0
Distance unitlistm
Unit Differential gaps send/limitslistm
Controller distancelist0
Unit Setpointlistm
Volume fill level in %list0
Rangelist0 to 100 % (DP 5.001)
Wertetyplist1 byte unsigned
Lower limitunsignedInt 0…25515
Unterer Grenzwert ( *10^X )signedInt -100…1000
Upper limitunsignedInt 0…25590
Oberer Grenzwert ( *10^X )signedInt -100…1000
Kalibrierung 1signedInt -32768…327671
Kalibrierung 1 ExponentsignedInt -100…1000
Kalibrierung 2signedInt -100…1000
Schaltdifferenz Senden/Grenzwerte ( * 10^X )signedInt -100…1000
Controller volume fill level in %list0
controllerlistTwo-level controller
SetpointunsignedInt 0…25550
Sollwert ( *10^X )signedInt -100…1000
Einheit Schaltdifferenz ReglersignedInt -100…1000
Actuating variable send by changelistno
Output 1list0
Wertetyplist1 Bit
Hilfsgröße istlistSetpoint
Hilfsgröße bei Änderung speichernlistno
Unterer GrenzwertsignedInt -32000…320001
Unterer Grenzwert ( *10^X )signedInt -100…1002
Oberer GrenzwertsignedInt -32000…320001
Oberer Grenzwert ( *10^X )signedInt -100…1002
Schaltdifferenz Senden/GrenzwertesignedInt -32000…320001
Output 2list0
Helperlist0

Version history

ApplicationApp noFingerprintFirst seenSizeFile
S8-F 1.5 latest$002B0F702026-11-2576 KBDownload

About this file

This is the official ETS product database for the Arcus-eds S8-F (30807XXX), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from Arcus-eds

All Arcus-eds products