S8-WAQ 30802XXX
Arcus-eds · Order number 30802XXX · Arc_S8
Download .knxprod S8-WAQ 1.5 · 74 KB
Product
| Manufacturer | Arcus-eds |
|---|---|
| Product name | S8-WAQ |
| Order number | 30802XXX |
| Hardware | S8-WAQ |
| Medium | Twisted Pair |
| Rail mounted | No |
| Registration | Certified · 2011-12-07 |
| Languages | en-US, de-DE |
| Catalog entry | M-0076_H-30802XXX-0_HP-0023-15-9526_CI-30802XXX-1 |
| Fingerprint | 9526 |
| SHA-256 | f92c68cd4728a6e13b12daa975498cf1f0b1b5ad9c725340bf91053e35989a48 |
| First seen | 2026-11-25 |
| Markets | 18 markets |
Application program: S8-WAQ 1.5
| Application number | $0023 |
|---|---|
| Version | 1.5 |
| Mask version | MV-0701 (7.1) |
| KNX Data Secure | No |
| Minimum ETS version | 3.0d |
| Parameters | 134 |
| Group objects | 40 |
Group objects (40)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Input, calibration | Calibration object | 1 Byte | 5.10 counter pulses (0..255) | CRWU |
| 1 | Input, calibration | Calibration value | 1 Byte | 5.10 counter pulses (0..255) | CRWU |
| 2 | Output, measured value pH | Measured value | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 2 | Output, measured value pH | Measured value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 2 | Output, measured value pH | Measured value | 4 Bytes | 14.5 amplitude | CRT |
| 3 | Input, auxiliary object pH | Auxiliary value | 1 Byte | 5.10 counter pulses (0..255) | CRWU |
| 3 | Input, auxiliary object pH | Auxiliary value | 2 Bytes | 9.1 temperature (°C) | CRWU |
| 3 | Input, auxiliary object pH | Auxiliary value | 4 Bytes | 14.5 amplitude | CRWU |
| 4 | Output, upper limit pH | Exceeding limit | 1 Bit | 1.2 boolean | CRT |
| 5 | Output, lower limit pH | Undercut limit | 1 Bit | 1.2 boolean | CRT |
| 6 | Output, controller pH | Manipulated variable | 1 Bit | 1.1 switch | CRT |
| 6 | Output, controller pH | Manipulated variable | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 7 | Input, enable/lock pH | Enable / disable | 1 Bit | 1.1 switch | CRWU |
| 8 | Output status pH | Status | 1 Byte | CRT | |
| 9 | Output, measured value ORP | Measured value | 2 Bytes | 8.1 pulses difference | CRT |
| 9 | Output, measured value ORP | Measured value | 2 Bytes | 9.20 voltage (mV) | CRT |
| 9 | Output, measured value ORP | Measured value | 4 Bytes | 14.5 amplitude | CRT |
| 10 | Input, auxiliary object ORP | Auxiliary value | 2 Bytes | 8.1 pulses difference | CRWU |
| 10 | Input, auxiliary object ORP | Auxiliary value | 2 Bytes | 9.20 voltage (mV) | CRWU |
| 10 | Input, auxiliary object ORP | Auxiliary value | 4 Bytes | 14.5 amplitude | CRWU |
| 11 | Output, upper limit ORP | Exceeding limit | 1 Bit | 1.2 boolean | CRT |
| 12 | Output, lower limit ORP | Undercut limit | 1 Bit | 1.2 boolean | CRT |
| 13 | Output, controller ORP | Manipulated variable | 1 Bit | 1.1 switch | CRT |
| 13 | Output, controller ORP | Manipulated variable | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 14 | Input, enable/lock ORP | Enable / disable | 1 Bit | 1.1 switch | CRWU |
| 15 | Output status ORP | Status | 1 Byte | CRT | |
| 16 | Output, measured value Term | Measured value | 2 Bytes | 7.1 pulses | CRT |
| 17 | Input, auxiliary object Term | Auxiliary value | 2 Bytes | 7.1 pulses | CRWU |
| 18 | Output, upper limit Term | Exceeding limit | 1 Bit | 1.2 boolean | CRT |
| 19 | Output, lower limit Term | Undercut limit | 1 Bit | 1.2 boolean | CRT |
| 23 | Output, measured value Temperature | Measured value | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 23 | Output, measured value Temperature | Measured value | 2 Bytes | 8.1 pulses difference | CRT |
| 23 | Output, measured value Temperature | Measured value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 23 | Output, measured value Temperature | Measured value | 4 Bytes | 14.68 temperature (°C) | CRT |
| 25 | Output, upper limit Temperature | Limit | 1 Bit | 1.2 boolean | CRT |
| 26 | Output, lower limit Temperature | Limit | 1 Bit | 1.2 boolean | CRT |
| 30 | Output, measured value S1 | Port S1 | 1 Bit | 1.1 switch | CRT |
| 37 | Output, measured value S2 | Port S2 | 1 Bit | 1.1 switch | CRT |
| 58 | Equipment time | Date | 3 Bytes | 10.1 time of day | CRWU |
| 59 | Equipment date | Time | 3 Bytes | 11.1 date | CRWU |
Parameters (86)
| Parameter | Type | Default |
|---|---|---|
| General settings | list | 0 |
| Measured value send cycle period | list | 1 min |
| Actuating value send cycle period ( Seconds ) | unsignedInt 10…250 | 60 |
| Kalibrierungszeit | unsignedInt 0…255 | 90 |
| use clock timer | list | no |
| timer until | unsignedInt 0…24 | 0 |
| timer from | unsignedInt 0…24 | 24 |
| Measured value pH | list | 0 |
| Measured value send periodical | list | no |
| Measured value send by change | list | no |
| Type datapoint | list | 2byte float |
| Auxiliary object is | list | Setpoint |
| Auxiliary value store by change | list | no |
| Lower limit x 0,01 | signedInt 0…1400 | 500 |
| Unterer Grenzwert ( *10^X ) | signedInt -100…100 | -2 |
| Upper limit x 0,01 | signedInt 0…1400 | 800 |
| Oberer Grenzwert ( *10^X ) | signedInt -100…100 | -2 |
| Kalibrierung 1 | signedInt -32768…32767 | 316 |
| Kalibrierung 1 Exponent | signedInt -100…100 | -6 |
| Kalibrierung 2 | signedInt -32768…32767 | 700 |
| Kalibrierung 2 Exponent | signedInt -100…100 | -2 |
| Differential gaps send/limits x 0,01 | signedInt 0…1400 | 10 |
| Schaltdifferenz Senden/Grenzwerte ( * 10^X ) | signedInt -100…100 | -2 |
| Controller pH | list | 0 |
| Locking object | list | locked if 1 |
| Actuating variable at rising actual value | list | decreasing |
| Controller | list | Steady PI controller |
| Setpoint x 0,01 | signedInt 0…1400 | 700 |
| Sollwert ( *10^X ) | signedInt -100…100 | -2 |
| Proportional range mantissa x 0,01 | signedInt 0…1400 | 100 |
| Differential gap Controller | signedInt 0…1400 | 100 |
| Proportional range | signedInt 0…1400 | 100 |
| Proportionalbereich Exponent ( *10^X ) | signedInt -100…100 | -2 |
| Schaltdifferenz Regler ( *10^X ) | signedInt -100…100 | -2 |
| Proportionalbereich ( *10^X ) | signedInt -100…100 | -2 |
| Reset time ( in minutes ) | unsignedInt 0…255 | 150 |
| Actuating variable send periodical | list | no |
| Actuating variable distance to limit in % | unsignedInt 0…50 | 0 |
| duty cycle in % | unsignedInt 0…50 | 0 |
| Cycle duration in seconds | unsignedInt 0…65535 | 60 |
| Measured value ORP | list | 0 |
| Lower limit mV | signedInt -1200…1200 | 300 |
| Unterer Grenzwert ( *10^X ) | signedInt -100…100 | 0 |
| Upper limit mV | signedInt -1200…1200 | 800 |
| Oberer Grenzwert ( *10^X ) | signedInt -100…100 | 0 |
| Kalibrierung 1 | signedInt -32768…32767 | 3662 |
| Kalibrierung 1 Exponent | signedInt -100…100 | -5 |
| Kalibrierung 2 | signedInt -32768…32767 | 0 |
| Kalibrierung 2 Exponent | signedInt -100…100 | 0 |
| Differential gaps send/limits mV | signedInt -1200…1200 | 5 |
| Schaltdifferenz Senden/Grenzwerte ( * 10^X ) | signedInt -100…100 | 0 |
| Controller ORP | list | 0 |
| Setpoint mV | signedInt -1200…1200 | 500 |
| Sollwert ( *10^X ) | signedInt -100…100 | 0 |
| Proportional range mV | signedInt -1200…1200 | 100 |
| Differential gap Controller ( in °C) | signedInt -1200…1200 | 100 |
| Proportionalbereich Exponent ( *10^X ) | signedInt -100…100 | 0 |
| Schaltdifferenz Regler ( *10^X ) | signedInt -100…100 | 0 |
| Measured value Laufzeit | list | 0 |
| Wertetyp | list | 2byte unsigned |
| Hilfsgröße ist | list | Setpoint |
| Hilfsgröße bei Änderung speichern | list | no |
| Lower limit ( x 100 ) Hours | signedInt 0…9999 | 20 |
| Unterer Grenzwert ( *10^X ) | signedInt -100…100 | 2 |
| Upper limit ( x 100 ) Hours | signedInt 0…9999 | 20 |
| Oberer Grenzwert ( *10^X ) | signedInt -100…100 | 2 |
| Kalibrierung 1 | signedInt -32768…32767 | 1 |
| Kalibrierung 1 Exponent | signedInt -100…100 | 0 |
| Schaltdifferenz Senden/Grenzwerte ( x 0,01 °C) | signedInt 0…9999 | 5 |
| Schaltdifferenz Senden/Grenzwerte ( * 10^X ) | signedInt -100…100 | -100 |
| Measured value Water temperature | list | 0 |
| Lower limit ( x 0,01 °C) | signedInt -9999…9999 | 700 |
| Upper limit ( x 0,01 °C) | signedInt -9999…9999 | 1700 |
| Kalibrierung 1 Exponent | signedInt -100…100 | -2 |
| Calibration2 | signedInt -32768…32767 | 0 |
| Differential gaps send/limits ( x 0,01 °C) | signedInt 0…1000 | 50 |
| Contact input 1 | list | 0 |
| Wertetyp | list | 1bit |
| Unterer Grenzwert ( x 0,01 °C) | signedInt -9999…9999 | 700 |
| Oberer Grenzwert ( x 0,01 °C) | signedInt -9999…9999 | 1700 |
| Schaltdifferenz Senden/Grenzwerte ( x 0,01 °C) | signedInt -9999…9999 | 50 |
| Contact input 2 | list | 0 |
| Unterer Grenzwert | signedInt -9999…9999 | 1 |
| Oberer Grenzwert | signedInt -9999…9999 | 1 |
| Schaltdifferenz Senden/Grenzwerte | signedInt -9999…9999 | 1 |
| Helper | list | 0 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| S8-WAQ 1.5 latest | $0023 | 9526 | 2026-11-25 | 74 KB | Download |
About this file
This is the official ETS product database for the Arcus-eds S8-WAQ (30802XXX), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Arcus-eds
- S8-T8 30801XXX
- S8-CO2 30803XXX
- S8-GLBS 30804XXX
- S8-BFT 3080500X
- S8-BFTLFT 3080502X
- S8-AN2 30806XXX
- S8-F 30807XXX
- S8-UNI 3080XXXX
- SK80_F 1180440001
- Touch_IT-Plugin 22310xxx
- Sensor Temperature IP65 30101xxx
- Sensor Temperature SK03 30103xxx