S8-T8 30801XXX

Arcus-eds · Order number 30801XXX · Arc_S8

Download .knxprod SK08-T8 1.5 · 83 KB

Product

ManufacturerArcus-eds
Product nameS8-T8
Order number30801XXX
HardwareS8-T8
MediumTwisted Pair
Rail mountedNo
RegistrationCertified · 2011-12-07
Languagesen-US, de-DE
Catalog entryM-0076_H-30801XXX-0_HP-0024-15-6DCD_CI-30801XXX-1
Fingerprint6DCD
SHA-256d75172073c568c5d3e8967c9e792cc894cc8e0a52a1082dcc6b631921285f599
First seen2026-11-25
Markets18 markets

Application program: SK08-T8 1.5

Application number$0024
Version1.5
Mask versionMV-0701 (7.1)
KNX Data SecureNo
Minimum ETS version3.0d
Parameters246
Group objects116
Group objects (116)
NoNameFunctionSizeDPTFlags
0Output,sensor status shortedOutput status4 BytesCRWU
1Output,sensor status breakOutput status4 BytesCRWU
2Output, measured value C1Measured value1 Byte6.10 counter pulses (-128..127)CRT
2Output, measured value C1Measured value2 Bytes8.1 pulses differenceCRT
2Output, measured value C1Measured value2 Bytes9.1 temperature (°C)CRT
2Output, measured value C1Measured value4 Bytes14.68 temperature (°C)CRT
3Input, auxiliary object C1Auxiliary object1 Byte6.10 counter pulses (-128..127)CRWU
3Input, auxiliary object C1Auxiliary object2 Bytes8.1 pulses differenceCRWU
3Input, auxiliary object C1Auxiliary object2 Bytes9.1 temperature (°C)CRWU
3Input, auxiliary object C1Auxiliary object4 Bytes14.68 temperature (°C)CRWU
4Output, upper limit C1Limit1 Bit1.2 booleanCRT
5Output, lower limit C1Limit1 Bit1.2 booleanCRT
6Output, controller C1Actuating value1 Bit1.1 switchCRT
6Output, controller C1Actuating value1 Byte5.10 counter pulses (0..255)CRT
7Input, enable/lock C1Enable/lock1 Bit1.1 switchCRWU
8Output, Object status C1Channel status1 ByteCRT
9Output, measured value C2Measured value 1 Byte6.10 counter pulses (-128..127)CRT
9Output, measured value C2Measured value 2 Bytes8.1 pulses differenceCRT
9Output, measured value C2Measured value 2 Bytes9.1 temperature (°C)CRT
9Output, measured value C2Measured value4 Bytes14.68 temperature (°C)CRT
10Input, auxiliary object C2Auxiliary object 1 Byte6.10 counter pulses (-128..127)CRWU
10Input, auxiliary object C2Auxiliary object2 Bytes8.1 pulses differenceCRWU
10Input, auxiliary object C2Auxiliary object 2 Bytes9.1 temperature (°C)CRWU
10Input, auxiliary object C2Auxiliary object 4 Bytes14.68 temperature (°C)CRWU
11Output, upper limit C2Limit1 Bit1.2 booleanCRT
12Output, lower limit C2Limit1 Bit1.2 booleanCRT
13Output, controller C2Actuating value1 Bit1.1 switchCRT
13Output, controller C2Actuating value1 Byte5.10 counter pulses (0..255)CRT
14Input, enable/lock C2Enable/lock1 Bit1.1 switchCRWU
15Output, Object status C2Channel status1 ByteCRT
16Output, measured value C3Measured value1 Byte6.10 counter pulses (-128..127)CRT
16Output, measured value C3Measured value2 Bytes8.1 pulses differenceCRT
16Output, measured value C3Measured value2 Bytes9.1 temperature (°C)CRT
16Output, measured value C3Measured value4 Bytes14.68 temperature (°C)CRT
17Input, auxiliary object C3Auxiliary object2 Bytes8.1 pulses differenceCRWU
17Input, auxiliary object C3Auxiliary object1 Byte6.10 counter pulses (-128..127)CRWU
17Input, auxiliary object C3Auxiliary object2 Bytes9.1 temperature (°C)CRWU
17Input, auxiliary object C3Auxiliary object4 Bytes14.68 temperature (°C)CRWU
18Output, upper limit C3Limit1 Bit1.2 booleanCRT
19Output, lower limit C3Limit1 Bit1.2 booleanCRT
20Output, controller C3Actuating value1 Bit1.1 switchCRT
20Output, controller C3Actuating value1 Byte5.10 counter pulses (0..255)CRT
21Input, enable/lock C3Enable/lock1 Bit1.1 switchCRWU
22Output, Object status C3Channel status1 ByteCRT
23Output, measured value C4Measured value1 Byte6.10 counter pulses (-128..127)CRT
23Output, measured value C4Measured value2 Bytes8.1 pulses differenceCRT
23Output, measured value C4Measured value2 Bytes9.1 temperature (°C)CRT
23Output, measured value C4Measured value4 Bytes14.68 temperature (°C)CRT
24Input, auxiliary object C4Auxiliary object2 Bytes8.1 pulses differenceCRWU
24Input, auxiliary object C4Auxiliary object1 Byte6.10 counter pulses (-128..127)CRWU
24Input, auxiliary object C4Auxiliary object2 Bytes9.1 temperature (°C)CRWU
24Input, auxiliary object C4Auxiliary object4 Bytes14.68 temperature (°C)CRWU
25Output, upper limit C4Limit1 Bit1.2 booleanCRT
26Output, lower limit C4Limit1 Bit1.2 booleanCRT
27Output, controller C4Actuating value1 Bit1.1 switchCRT
27Output, controller C4Actuating value1 Byte5.10 counter pulses (0..255)CRT
28Input, enable/lock C4Enable/lock1 Bit1.1 switchCRWU
29Output, Object status C4Channel status1 ByteCRT
30Output, measured value C5Measured value1 Byte6.10 counter pulses (-128..127)CRT
30Output, measured value C5Measured value2 Bytes8.1 pulses differenceCRT
30Output, measured value C5Measured value2 Bytes9.1 temperature (°C)CRT
30Output, measured value C5Measured value4 Bytes14.68 temperature (°C)CRT
31Input, auxiliary object C5Auxiliary object2 Bytes8.1 pulses differenceCRWU
31Input, auxiliary object C5Auxiliary object1 Byte6.10 counter pulses (-128..127)CRWU
31Input, auxiliary object C5Auxiliary object2 Bytes9.1 temperature (°C)CRWU
31Input, auxiliary object C5Auxiliary object4 Bytes14.68 temperature (°C)CRWU
32Output, upper limit C5Limit1 Bit1.2 booleanCRT
33Output, lower limit C5Limit1 Bit1.2 booleanCRT
34Output, controller C5Actuating value1 Bit1.1 switchCRT
34Output, controller C5Actuating value1 Byte5.10 counter pulses (0..255)CRT
35Input, enable/lock C5Enable/lock1 Bit1.1 switchCRWU
36Output, Object status C5Channel status1 ByteCRT
37Output, measured value C6Measured value1 Byte6.10 counter pulses (-128..127)CRT
37Output, measured value C6Measured value2 Bytes8.1 pulses differenceCRT
37Output, measured value C6Measured value2 Bytes9.1 temperature (°C)CRT
37Output, measured value C6Measured value4 Bytes14.68 temperature (°C)CRT
38Input, auxiliary object C6Auxiliary object2 Bytes8.1 pulses differenceCRWU
38Input, auxiliary object C6Auxiliary object1 Byte6.10 counter pulses (-128..127)CRWU
38Input, auxiliary object C6Auxiliary object2 Bytes9.1 temperature (°C)CRWU
38Input, auxiliary object C6Auxiliary object4 Bytes14.68 temperature (°C)CRWU
39Output, upper limit C6Limit1 Bit1.2 booleanCRT
40Output, lower limit C6Limit1 Bit1.2 booleanCRT
41Output, controller C6Actuating value1 Bit1.1 switchCRT
41Output, controller C6Actuating value1 Byte5.10 counter pulses (0..255)CRT
42Input, enable/lock C6Enable/lock1 Bit1.1 switchCRWU
43Output, object status C6Channel status1 ByteCRT
44Output,measured value C7Measured value1 Byte6.10 counter pulses (-128..127)CRT
44Output,measured value C7Measured value 2 Bytes8.1 pulses differenceCRT
44Output,measured value C7Measured value 2 Bytes9.1 temperature (°C)CRT
44Output,measured value C7Measured value 4 Bytes14.68 temperature (°C)CRT
45Input, auxiliary object C7Auxiliary object 2 Bytes8.1 pulses differenceCRWU
45Input, auxiliary object C7Auxiliary object 1 Byte6.10 counter pulses (-128..127)CRWU
45Input, auxiliary object C7Auxiliary object 2 Bytes9.1 temperature (°C)CRWU
45Input, auxiliary object C7Auxiliary object4 Bytes14.68 temperature (°C)CRWU
46Output, upper limit C7Limit1 Bit1.2 booleanCRT
47Output, lower limit C7Limit1 Bit1.2 booleanCRT
48Output, controller C7Actuating value1 Bit1.1 switchCRT
48Output, controller C7Actuating value1 Byte5.10 counter pulses (0..255)CRT
49Input, enable/lock C7Enable/lock1 Bit1.1 switchCRWU
50Output, Object status C7Channel status1 ByteCRT
51Output, measured value C8Measured value1 Byte6.10 counter pulses (-128..127)CRT
51Output, measured value C8Measured value2 Bytes8.1 pulses differenceCRT
51Output, measured value C8Measured value2 Bytes9.1 temperature (°C)CRT
51Output, measured value C8Measured value 4 Bytes14.68 temperature (°C)CRT
52Input, auxiliary object C8Auxiliary object2 Bytes8.1 pulses differenceCRWU
52Input, auxiliary object C8Auxiliary object1 Byte6.10 counter pulses (-128..127)CRWU
52Input, auxiliary object C8Auxiliary object2 Bytes9.1 temperature (°C)CRWU
52Input, auxiliary object C8Auxiliary object 4 Bytes14.68 temperature (°C)CRWU
53Output, upper limit C8Limit1 Bit1.2 booleanCRT
54Output, lower limit C8Limit1 Bit1.2 booleanCRT
55Output, controller C8Actuating value1 Bit1.1 switchCRT
55Output, controller C8Actuating value1 Byte5.10 counter pulses (0..255)CRT
56Input, enable/lock C8Enable/lock1 Bit1.1 switchCRWU
57Output, Object status C8Channel status1 ByteCRT
58Equipment timeTime3 Bytes10.1 time of dayCRWU
59Equipment dateDate3 Bytes11.1 dateCRWU
Parameters (54)
ParameterTypeDefault
General Settingslist0
Measured value send cycle periodlist1 min
Actuating value send cycle period ( Seconds )unsignedInt 10…25060
Use clock timerlistNo
Timer fromunsignedInt 0…240
Timer untilunsignedInt 0…2424
Measured value 1list0
Measured value send cyclicallistNo
Measured value send by changelistNo
Type datapointlist2byte float
Auxiliary object islistSetpoint
Auxiliary value store by changelistNo
Lower limit ( x 0,01 °C)signedInt -9999…19999700
Unterer Grenzwert ( *10^X )signedInt -100…100-2
Upper limit ( x 0,01 °C)signedInt -9999…199991700
Oberer Grenzwert ( *10^X )signedInt -100…100-2
Kalibrierung 1signedInt -32768…327671
Kalibrierung 1 ExponentsignedInt -100…100-2
Measured value shift ( x 0,01 °C)signedInt -32768…327670
Kalibrierung 2 ExponentsignedInt -100…100-2
Differential gap send/limits ( x 0,01 °C)signedInt -9999…1999950
Schaltdifferenz Senden/Grenzwerte ( * 10^X )signedInt -100…100-2
Controller 1list0
Locking objectlistlocked if 1
Actuating value by ascending actual valuelistdecreasing
ControllerlistSteady PI controller
Setpoint ( x 0,01 °C)signedInt -9999…199991800
Sollwert ( *10^X )signedInt -100…100-2
Proportional range ( x 0.01 °C)signedInt -9999…19999500
Differential gap Controller ( x 0.01 °C)signedInt -9999…19999500
Differential gap Controller ( x 00.1 °C)signedInt -9999…19999500
Proportionalbereich Exponent ( *10^X )signedInt -100…100-2
Schaltdifferenz Regler ( *10^X )signedInt -100…100-2
Proportionalbereich ( *10^X )signedInt -100…100-2
Reset time ( in minutes )unsignedInt 0…255150
Actuating value send cyclicallistNo
Actuating value distance to limit in %unsignedInt 0…500
Duty cycle in %unsignedInt 0…500
Cycle duration in secondsunsignedInt 0…6553560
Measured value 2list0
Controller 2list0
Measured value 3list0
Controller 3list0
Measured value 4list0
Kalibrierung 2signedInt -100…100-2
Controller 4list0
Measured value 5list0
Controller 5list0
Measured value 6list0
Controller 6list0
Measured value 7list0
Controller 7list0
Measured value 8list0
Controller 8list0

Version history

ApplicationApp noFingerprintFirst seenSizeFile
SK08-T8 1.5 latest$00246DCD2026-11-2583 KBDownload

About this file

This is the official ETS product database for the Arcus-eds S8-T8 (30801XXX), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from Arcus-eds

All Arcus-eds products