Product

ManufacturerABB AG - STOTZ-KONTAKT
Product nameJA/S4.SMI.1M Shutter Actuator man.,4-fold,SMI,MDRC
Order number2CDG 110 028 R0011
HardwareJA/S4.SMI.1M Jalousieaktor man.,4fach,SMI,REG
MediumTwisted Pair
Bus current (mA)12
Rail mountedYes
Width (mm)72
RegistrationRegistered · 2022-03-04
Languagesen-US, de-DE, es-ES, fr-FR, it-IT, nl-NL, pl-PL, ru-RU
Catalog entryM-0002_H-2CDG.20110.20028.20R0011-2_HP-A038-15-0D27_CI-2CDG.20110.20028.20R0011-1
Fingerprint0D27
SHA-2569f7e18a5f7e967200455364b17fcb1f51c60519b4efcda05b48043283e1307d5
First seen2026-11-25
Markets59 markets

Application program: Blind SMI 4f M/1.5 1.5

Application number$A038
Version1.5
Mask versionMV-0701 (7.1)
KNX Data SecureNo
Minimum ETS version5.0
Parameters568
Group objects147
Group objects (147)
NoNameFunctionSizeDPTFlags
0Object 11 Bit1.1 switchCW
1Output AMove blind UP-DOWN1 Bit1.8 up/downCW
1Output AMove shutter Up-Down1 Bit1.8 up/downCW
2Output ASlat adj./Stop Up-Down1 Bit1.7 stepCW
2Output AStop1 Bit1.7 stepCW
3Output ABlind UP-DOWN limited1 Bit1.8 up/downCW
3Output AShutter Up-Down limited1 Bit1.8 up/downCW
4Output AMove to position 0..2551 Byte5.1 percentage (0..100%)CW
5Output AMove slat 0..2551 Byte5.1 percentage (0..100%)CW
6Output AMove to position 1/21 Bit1.22 sceneCW
7Output AMove to position 3/41 Bit1.22 sceneCW
8Output ASet position 1/21 Bit1.22 sceneCW
9Output ASet position 3/41 Bit1.22 sceneCW
10Output AActivation of automatic contr.1 Bit1.3 enableCWTU
11Output ASun1 Bit1.2 booleanCWTU
12Output AAdjust position for sun 0..2551 Byte5.1 percentage (0..100%)CWTU
13Output AAdjust slat for sun 0..2551 Byte5.1 percentage (0..100%)CWTU
14Output APresence1 Bit1.18 occupancyCWTU
15Output AHeating1 Bit1.2 booleanCWTU
16Output ACooling1 Bit1.2 booleanCWTU
17Output AEnable/disable automatic1 Bit1.2 booleanCWTU
18Output AEnable/disable direct control1 Bit1.2 booleanCWTU
19Output ABlock1 Bit1.5 alarmCW
20Output AForced operation2 Bit2.5 alarm controlCW
21Output ATelegr. Status Position 0..2551 Byte5.1 percentage (0..100%)CRT
22Output ATelegr. Status Slat 0..2551 Byte5.1 percentage (0..100%)CRT
23Output ATelegr. Status Upper position1 Bit1.11 stateCRT
24Output ATelegr. Status Lower position1 Bit1.11 stateCRT
25Output ATelegr. Status Operation1 Bit1.11 stateCRT
26Output ATelegr. Status Automatic1 Bit1.11 stateCRT
27Output ATelegr. Status byte1 ByteCRT
28Output ATelegr. Status SMI failure1 Bit1.11 stateCRT
29Output ATelegr. Status No. of drives1 Bit1.11 stateCRT
30Output ATelegr. Diagnostic byte1 ByteCRT
31Output BMove blind UP-DOWN1 Bit1.8 up/downCW
31Output BMove shutter Up-Down1 Bit1.8 up/downCW
32Output BSlat adj./Stop Up-Down1 Bit1.7 stepCW
32Output BStop1 Bit1.7 stepCW
33Output BBlind UP-DOWN limited1 Bit1.8 up/downCW
33Output BShutter Up-Down limited1 Bit1.8 up/downCW
34Output BMove to position 0..2551 Byte5.1 percentage (0..100%)CW
35Output BMove slat 0..2551 Byte5.1 percentage (0..100%)CW
36Output BMove to position 1/21 Bit1.22 sceneCW
37Output BMove to position 3/41 Bit1.22 sceneCW
38Output BSet position 1/21 Bit1.22 sceneCW
39Output BSet position 3/41 Bit1.22 sceneCW
40Output BActivation of automatic contr.1 Bit1.3 enableCWTU
41Output BSun1 Bit1.2 booleanCWTU
42Output BAdjust position for sun 0..2551 Byte5.1 percentage (0..100%)CWTU
43Output BAdjust slat for sun 0..2551 Byte5.1 percentage (0..100%)CWTU
44Output BPresence1 Bit1.18 occupancyCWTU
45Output BHeating1 Bit1.2 booleanCWTU
46Output BCooling1 Bit1.2 booleanCWTU
47Output BEnable/disable automatic1 Bit1.2 booleanCWTU
48Output BEnable/disable direct control1 Bit1.2 booleanCWTU
49Output BBlock1 Bit1.5 alarmCW
50Output BForced operation2 Bit2.5 alarm controlCW
51Output BTelegr. Status Position 0..2551 Byte5.1 percentage (0..100%)CRT
52Output BTelegr. Status Slat 0..2551 Byte5.1 percentage (0..100%)CRT
53Output BTelegr. Status Upper position1 Bit1.11 stateCRT
54Output BTelegr. Status Lower position1 Bit1.11 stateCRT
55Output BTelegr. Status Operation1 Bit1.11 stateCRT
56Output BTelegr. Status Automatic1 Bit1.11 stateCRT
57Output BTelegr. Status byte1 ByteCRT
58Output BTelegr. Status SMI failure1 Bit1.11 stateCRT
59Output BTelegr. Status No. of drives1 Bit1.11 stateCRT
60Output BTelegr. Diagnostic byte1 ByteCRT
61Output CMove blind UP-DOWN1 Bit1.8 up/downCW
61Output CMove shutter Up-Down1 Bit1.8 up/downCW
62Output CSlat adj./Stop Up-Down1 Bit1.7 stepCW
62Output CStop1 Bit1.7 stepCW
63Output CBlind UP-DOWN limited1 Bit1.8 up/downCW
63Output CShutter Up-Down limited1 Bit1.8 up/downCW
64Output CMove to position 0..2551 Byte5.1 percentage (0..100%)CW
65Output CMove slat 0..2551 Byte5.1 percentage (0..100%)CW
66Output CMove to position 1/21 Bit1.22 sceneCW
67Output CMove to position 3/41 Bit1.22 sceneCW
68Output CSet position 1/21 Bit1.22 sceneCW
69Output CSet position 3/41 Bit1.22 sceneCW
70Output CActivation of automatic contr.1 Bit1.3 enableCWTU
71Output CSun1 Bit1.2 booleanCWTU
72Output CAdjust position for sun 0..2551 Byte5.1 percentage (0..100%)CWTU
73Output CAdjust slat for sun 0..2551 Byte5.1 percentage (0..100%)CWTU
74Output CPresence1 Bit1.18 occupancyCWTU
75Output CHeating1 Bit1.2 booleanCWTU
76Output CCooling1 Bit1.2 booleanCWTU
77Output CEnable/disable automatic1 Bit1.2 booleanCWTU
78Output CEnable/disable direct control1 Bit1.2 booleanCWTU
79Output CBlock1 Bit1.5 alarmCW
80Output CForced operation2 Bit2.5 alarm controlCW
81Output CTelegr. Status Position 0..2551 Byte5.1 percentage (0..100%)CRT
82Output CTelegr. Status Slat 0..2551 Byte5.1 percentage (0..100%)CRT
83Output CTelegr. Status Upper position1 Bit1.11 stateCRT
84Output CTelegr. Status Lower position1 Bit1.11 stateCRT
85Output CTelegr. Status Operation1 Bit1.11 stateCRT
86Output CTelegr. Status Automatic1 Bit1.11 stateCRT
87Output CTelegr. Status byte1 ByteCRT
88Output CTelegr. Status SMI failure1 Bit1.11 stateCRT
89Output CTelegr. Status No. of drives1 Bit1.11 stateCRT
90Output CTelegr. Diagnostic byte1 ByteCRT
91Output DMove blind UP-DOWN1 Bit1.8 up/downCW
91Output DMove shutter Up-Down1 Bit1.8 up/downCW
92Output DSlat adj./Stop Up-Down1 Bit1.7 stepCW
92Output DStop1 Bit1.7 stepCW
93Output DBlind UP-DOWN limited1 Bit1.8 up/downCW
93Output DShutter Up-Down limited1 Bit1.8 up/downCW
94Output DMove to position 0..2551 Byte5.1 percentage (0..100%)CW
95Output DMove slat 0..2551 Byte5.1 percentage (0..100%)CW
96Output DMove to position 1/21 Bit1.22 sceneCW
97Output DMove to position 3/41 Bit1.22 sceneCW
98Output DSet position 1/21 Bit1.22 sceneCW
99Output DSet position 3/41 Bit1.22 sceneCW
100Output DActivation of automatic contr.1 Bit1.3 enableCWTU
101Output DSun1 Bit1.2 booleanCWTU
102Output DAdjust position for sun 0..2551 Byte5.1 percentage (0..100%)CWTU
103Output DAdjust slat for sun 0..2551 Byte5.1 percentage (0..100%)CWTU
104Output DPresence1 Bit1.18 occupancyCWTU
105Output DHeating1 Bit1.2 booleanCWTU
106Output DCooling1 Bit1.2 booleanCWTU
107Output DEnable/disable automatic1 Bit1.2 booleanCWTU
108Output DEnable/disable direct control1 Bit1.2 booleanCWTU
109Output DBlock1 Bit1.5 alarmCW
110Output DForced operation2 Bit2.5 alarm controlCW
111Output DTelegr. Status Position 0..2551 Byte5.1 percentage (0..100%)CRT
112Output DTelegr. Status Slat 0..2551 Byte5.1 percentage (0..100%)CRT
113Output DTelegr. Status Upper position1 Bit1.11 stateCRT
114Output DTelegr. Status Lower position1 Bit1.11 stateCRT
115Output DTelegr. Status Operation1 Bit1.11 stateCRT
116Output DTelegr. Status Automatic1 Bit1.11 stateCRT
117Output DTelegr. Status byte1 ByteCRT
118Output DTelegr. Status SMI failure1 Bit1.11 stateCRT
119Output DTelegr. Status No. of drives1 Bit1.11 stateCRT
120Output DTelegr. Diagnostic byte1 ByteCRT
121Output A-DTelegr. Status Auxiliary volt.1 Bit1.11 stateCRT
122Output A-DEnable/block manual operation1 Bit1.2 booleanCW
123Output A-DTelegr. Status Man. operation1 Bit1.11 stateCRT
124Output A-DWind alarm no. 11 Bit1.5 alarmCWTU
125Output A-DWind alarm no. 21 Bit1.5 alarmCWTU
126Output A-DWind alarm no. 31 Bit1.5 alarmCWTU
127Output A-DRain alarm1 Bit1.5 alarmCWTU
128Output A-DFrost alarm1 Bit1.5 alarmCWTU
129Output A-DScene1 Byte18.1 scene controlCW
130Output A-DTime for autom. reactivation2 Bytes7.6 time (min)CW
131Output A-DDelay time on sun = 12 Bytes7.5 time (s)CW
132Output A-DDelay time on sun = 02 Bytes7.5 time (s)CW
133Output A-DDelay for presence=12 Bytes7.5 time (s)CW
134Output A-DDelay for presence=02 Bytes7.5 time (s)CW
Parameters (101)
ParameterTypeDefault
Convertible from version 1.0unsignedInt 0…25516
Parameter settingslistSimilar for all outputs
Time-delayed switching of driveslistDeactivated
If parent = inactive, 0 is downloaded hereunsignedInt 0…40
Time delay [s] 1...15unsignedInt 1…151
Maximum rate of telegramslist1 telegram per second
Allow parameter changes via EIB/KNXlistNo
Overwrite parameter changes on downloadlistNo
Allow SMI service accesslistNo
Manual operationlistEnabled
Reset manual operation to EIB/KNX operationlistAutomatically and via push button
Time for automatic reset [s] 10...6,000unsignedInt 10…6000300
Send status Manual operationlistNo
Send status Auxiliary voltage/ SMI supply voltagelistNo
Position after programming/ resetlistStop
Read automatic objectslistNo
Position on bus voltage failurelistNo reaction
Position after bus voltage recoverylistStop
Read automatic- and safety objectslistNo
Pos. aft. auxiliary voltage recoverylistStop
Order of priority for weather alarm functionslist1.Wind alarm - 2.Rain alarm - 3.Frost alarm
Group object no. 1 for wind alarmlistDeactivated
Group object no. 2 for wind alarmlistDeactivated
Group object no. 3 for wind alarmlistDeactivated
Monitoring time for wind alarm [s] 0...1,000 (0=cycl.monitor. deactiv.)unsignedInt 0…10000
Group object for rain alarmlistDeactivated
Monitoring time for rain alarm [s] 0...1,000 (0=cycl.monitor. deactiv.)unsignedInt 0…10000
Group object for frost alarmlistDeactivated
Monitoring time for frost alarm [s] 0...1,000 (0=cycl.monitor. deactiv.)unsignedInt 0…10000
Number of SMI drives Output AunsignedInt 0…41
Number of SMI drives Output BunsignedInt 0…41
Number of SMI drives Output CunsignedInt 0…41
Number of SMI drives Output DunsignedInt 0…41
Operating modelistBlind
Rotation angle of motor shaft for complete slat adjustment 10..500unsignedInt 10…500300
Number of slat adjustments 1..250unsignedInt 1…2507
Position of slat after move down [%] 0..100unsignedInt 0…100100
Limit traveling rangelistNo
Upper limit [%] 0..100unsignedInt 0…1000
Lower limit [%] 0..100unsignedInt 0…100100
Output reacts to group object for wind alarm no.listOutput does not react to wind alarm
Position on wind alarmlistDeactivated
Position on rain alarmlistDeactivated
Position for frost alarmlistDeactivated
Disable via group objectlistDeactivated
Position during blockinglistNo reaction
Forced operationlistDeactivated
Position on reset of weather alarm, blocking and forced operationlistNo reaction
Order of priority for safety alarm functionslist1.Weather alarm - 2.Block - 3.Forced operation
Send position: 0..255listNo
Send position: end position reachedlistNo
Send status OperationlistNo
Send status Automatic controllistNo
Send status bytelistNo
Send status SMI failurelistNo
Send status Number of SMI driveslistNo
Send SMI diagnostic bytelistNo
Move to position 0..255listDeactivated
Move to position: 1-bit presetlistDeactivated
Overwrite preset values dur. downloadlistYes
Position 1 [%] 0..100 (0% = top; 100% = bottom)unsignedInt 0…10020
Slat 1 [%] 0..100 (0% = open; 100% = closed)unsignedInt 0…10020
Position 2 [%] 0..100 (0% = top; 100% = bottom)unsignedInt 0…10040
Slat 2 [%] 0..100 (0% = open; 100% = closed)unsignedInt 0…10040
Position 3 [%] 0..100 (0% = top; 100% = bottom)unsignedInt 0…10060
Slat 3 [%] 0..100 (0% = open; 100% = closed)unsignedInt 0…10060
Position 4 [%] 0..100 (0% = top; 100% = bottom)unsignedInt 0…10080
Slat 4 [%] 0..100 (0% = open; 100% = closed)unsignedInt 0…10080
Use sun automatic controllistNo
Deactivation of automatic controllistvia obj. "Activation" and move command
Automatic reactivation of automatic controllistDeactivated
Time for automation reaction of autom. control [min.] 10..6,000unsignedInt 10…6000300
Toggling to automatic controllistEnabled
Toggling to direct controllistEnabled
Position for sun = '1' (sun)listDown
Position for sun = "1" (sun)listDown
Position for sun = "0" (no sun)listUp
Delay for sun = "1" [s] 0..6,000unsignedInt 0…60000
Delay for sun = "0" [s] 0..6,000unsignedInt 0…60000
Heating/Cooling automatic controllistDeactivated
Delay for presence = "1" [s] 0..6,000unsignedInt 0…60000
Delay for presence = "0" [s] 0..6,000unsignedInt 0…6000600
Position for heating = '1' and sun = '1'listUp
Position for heating = "1" and sun = "1"listUp
Position for heating = '1' and sun = '0'listNo reaction
Position for heating = "1" and sun = "0"listNo reaction
Position for cooling = '1' and sun = '1'listDown
Position for cooling = "1" and sun = "1"listDown
Position for cooling = '1' and sun = '0'listNo reaction
Position for cooling = "1" and sun = "0"listNo reaction
1 byte scenelistDeactivated
Scene assignment (1)listNo assignment
Scene assignment (2)listNo assignment
Scene assignment (3)listNo assignment
Scene assignment (4)listNo assignment
Scene assignment (5)listNo assignment
Scene assignment (6)listNo assignment
Scene assignment (7)listNo assignment
Scene assignment (8)listNo assignment
Scene assignment (9)listNo assignment
Scene assignment (10)listNo assignment

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Blind SMI 4f M/1.5 1.5 latest$A0380D272026-11-25226 KBDownload

About this file

This is the official ETS product database for the ABB AG - STOTZ-KONTAKT JA/S4.SMI.1M Shutter Actuator man.,4-fold,SMI,MDRC (2CDG 110 028 R0011), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from ABB AG - STOTZ-KONTAKT

All ABB AG - STOTZ-KONTAKT products