KNX Database
ABB AG - STOTZ-KONTAKT 2CDG 110 130 R0011 JRA/S4.230.1.1 Blind/RollerShutterAct,4f,230V

JRA/S4.230.1.1 Blind/RollerShutterAct,4f,230V 2CDG 110 130 R0011

ABB AG - STOTZ-KONTAKT · Order number 2CDG 110 130 R0011 · Shading Control › Blind Actuators 230 V AC

Blind/Roller Shutter 4f 230V/1.4a

Download .knxprod Blind/Roller Shutter 4f 230V/1.4a 1.4 · 372 KB

Product

ManufacturerABB AG - STOTZ-KONTAKT
Product nameJRA/S4.230.1.1 Blind/RollerShutterAct,4f,230V
Order number2CDG 110 130 R0011
HardwareJRA/S4.230.1.1 Jal./Rol.Akt.4f,230V,REG
MediumTwisted Pair
Bus current (mA)10
Rail mountedYes
Width (mm)72
RegistrationCertified · 2011-07-15
Languagesen-US, de-DE, es-ES, fr-FR, it-IT, nl-NL, pl-PL, ru-RU
Catalog entryM-0002_H-2CDG.20110.20130.20R0011-1_HP-A078-14-FD8F_CI-2CDG.20110.20130.20R0011-1
FingerprintFD8F
SHA-256ba05bd434e2abbf056aa64d25c6f3992a0fbded2b011eec838eb538d8573080b
First seen2026-11-25
Markets59 markets

Application program: Blind/Roller Shutter 4f 230V/1.4a 1.4

Application number$A078
Version1.4
Mask versionMV-0701 (7.1)
KNX Data SecureNo
Parameters1212
Group objects158
Group objects (158)
NoNameFunctionSizeDPTFlags
0GeneralIn operation1 BitCRT
1GeneralRequest status values1 BitCW
2GeneralDisable/enable man. operation1 BitCW
3GeneralStatus Manual operation1 BitCRT
4Output A-XWind alarm no. 11 BitCWTU
5Output A-XWind alarm no. 21 BitCWTU
6Output A-XWind alarm no. 31 BitCWTU
7Output A-XRain alarm1 BitCWTU
8Output A-XFrost alarm1 BitCWTU
9Object 91 BitCW
10Output AMove blinds/shutter up-down1 BitCW
10Output AFlaps open-closed/on-off1 BitCW
11Output ASlat adjustm./stop up-down1 BitCW
11Output AStop Up-Down1 BitCW
12Output AEnable limitation1 BitCW
12Output ABlinds/shutter up-down limited1 BitCW
13Output AMove to position height 0..2551 ByteCW
14Output AMove slats 0..2551 ByteCW
15Output AMove to position 1, 21 BitCW
16Output AMove to position 3, 41 BitCW
17Output ASet position 1, 21 BitCW
18Output ASet position 3, 41 BitCW
19Output ATrigger travel detection1 BitCW
19Output ATrigger reference movement1 BitCW
20Output A8-bit scene1 ByteCW
21Output AActivation of autom. control1 BitCWTU
22Output ASun1 BitCWTU
23Output AMove to height for sun 0..2551 ByteCWTU
24Output AAdjust slat for sun 0..2551 ByteCWTU
25Output APresence1 BitCWTU
26Output AHeating1 BitCWTU
27Output ACooling1 BitCWTU
28Output AReceive room temperature2 BytesCWTU
29Output ADisable/enable autom. control1 BitCWTU
30Output ADisable/enable direct control1 BitCWTU
31Output ABlock1 BitCWTU
32Output AForced operation 1 bit1 BitCWTU
32Output AForced operation 2 bit2 BitCWTU
32Output AForced operation 2 bit2 BitCW
33Output AStatus Open-Closed/On-Off1 BitCRT
33Output AStatus Height 0...2551 ByteCRT
34Output AStatus Slat 0...2551 ByteCRT
35Output AStatus Upper end position1 BitCRT
36Output AStatus Lower end position1 BitCRT
37Output AStatus Operability1 BitCRT
38Output AStatus Automatic1 BitCRT
39Output AStatus information2 BytesCRT
40Output BMove blinds/shutter up-down1 BitCW
40Output BFlaps open-closed/on-off1 BitCW
41Output BSlat adjustm./stop up-down1 BitCW
41Output BStop Up-Down1 BitCW
42Output BBlinds/shutter up-down limited1 BitCW
42Output BEnable limitation1 BitCW
43Output BMove to position height 0..2551 ByteCW
44Output BMove slats 0..2551 ByteCW
45Output BMove to position 1, 21 BitCW
46Output BMove to position 3, 41 BitCW
47Output BSet position 1, 21 BitCW
48Output BSet position 3, 41 BitCW
49Output BTrigger reference movement1 BitCW
49Output BTrigger travel detection1 BitCW
50Output B8-bit scene1 ByteCW
51Output BActivation of autom. control1 BitCWTU
52Output BSun1 BitCWTU
53Output BMove to height for sun 0..2551 ByteCWTU
54Output BAdjust slat for sun 0..2551 ByteCWTU
55Output BPresence1 BitCWTU
56Output BHeating1 BitCWTU
57Output BCooling1 BitCWTU
58Output BReceive room temperature2 BytesCWTU
59Output BDisable/enable autom. control1 BitCWTU
60Output BDisable/enable direct control1 BitCWTU
61Output BBlock1 BitCWTU
62Output BForced operation 1 bit1 BitCWTU
62Output BForced operation 2 bit2 BitCWTU
62Output BForced operation 2 bit2 BitCW
63Output BStatus Height 0...2551 ByteCRT
63Output BStatus Open-Closed/On-Off1 BitCRT
64Output BStatus Slat 0...2551 ByteCRT
65Output BStatus Upper end position1 BitCRT
66Output BStatus Lower end position1 BitCRT
67Output BStatus Operability1 BitCRT
68Output BStatus Automatic1 BitCRT
69Output BStatus information2 BytesCRT
70Output CMove blinds/shutter up-down1 BitCW
70Output CFlaps open-closed/on-off1 BitCW
71Output CSlat adjustm./stop up-down1 BitCW
71Output CStop Up-Down1 BitCW
72Output CBlinds/shutter up-down limited1 BitCW
72Output CEnable limitation1 BitCW
73Output CMove to position height 0..2551 ByteCW
74Output CMove slats 0..2551 ByteCW
75Output CMove to position 1, 21 BitCW
76Output CMove to position 3, 41 BitCW
77Output CSet position 1, 21 BitCW
78Output CSet position 3, 41 BitCW
79Output CTrigger reference movement1 BitCW
79Output CTrigger travel detection1 BitCW
80Output C8-bit scene1 ByteCW
81Output CActivation of autom. control1 BitCWTU
82Output CSun1 BitCWTU
83Output CMove to height for sun 0..2551 ByteCWTU
84Output CAdjust slat for sun 0..2551 ByteCWTU
85Output CPresence1 BitCWTU
86Output CHeating1 BitCWTU
87Output CCooling1 BitCWTU
88Output CReceive room temperature2 BytesCWTU
89Output CDisable/enable autom. control1 BitCWTU
90Output CDisable/enable direct control1 BitCWTU
91Output CBlock1 BitCWTU
92Output CForced operation 1 bit1 BitCWTU
92Output CForced operation 2 bit2 BitCWTU
92Output CForced operation 2 bit2 BitCW
93Output CStatus Height 0...2551 ByteCRT
93Output CStatus Open-Closed/On-Off1 BitCRT
94Output CStatus Slat 0...2551 ByteCRT
95Output CStatus Upper end position1 BitCRT
96Output CStatus Lower end position1 BitCRT
97Output CStatus Operability1 BitCRT
98Output CStatus Automatic1 BitCRT
99Output CStatus information2 BytesCRT
100Output DMove blinds/shutter up-down1 BitCW
100Output DFlaps open-closed/on-off1 BitCW
101Output DSlat adjustm./stop up-down1 BitCW
101Output DStop Up-Down1 BitCW
102Output DBlinds/shutter up-down limited1 BitCW
102Output DEnable limitation1 BitCW
103Output DMove to position height 0..2551 ByteCW
104Output DMove slats 0..2551 ByteCW
105Output DMove to position 1, 21 BitCW
106Output DMove to position 3, 41 BitCW
107Output DSet position 1, 21 BitCW
108Output DSet position 3, 41 BitCW
109Output DTrigger reference movement1 BitCW
109Output DTrigger travel detection1 BitCW
110Output D8-bit scene1 ByteCW
111Output DActivation of autom. control1 BitCWTU
112Output DSun1 BitCWTU
113Output DMove to height for sun 0..2551 ByteCWTU
114Output DAdjust slat for sun 0..2551 ByteCWTU
115Output DPresence1 BitCWTU
116Output DHeating1 BitCWTU
117Output DCooling1 BitCWTU
118Output DReceive room temperature2 BytesCWTU
119Output DDisable/enable autom. control1 BitCWTU
120Output DDisable/enable direct control1 BitCWTU
121Output DBlock1 BitCWTU
122Output DForced operation 1 bit1 BitCWTU
122Output DForced operation 2 bit2 BitCWTU
122Output DForced operation 2 bit2 BitCW
123Output DStatus Height 0...2551 ByteCRT
123Output DStatus Open-Closed/On-Off1 BitCRT
124Output DStatus Slat 0...2551 ByteCRT
125Output DStatus Upper end position1 BitCRT
126Output DStatus Lower end position1 BitCRT
127Output DStatus Operability1 BitCRT
128Output DStatus Automatic1 BitCRT
129Output DStatus information2 BytesCRT
Parameters (175)
ParameterTypeDefault
Konvertierbar ab Version 0.6unsignedInt 0…2556
Wird bei jedem Download auf 0xFF gesetzt App. setzt es dann auf 0unsignedInt 0…255255
Time-delayed switching of driveslistDeactivated
Falls Parent = inaktiv wird hier 0 runter geladenunsignedInt 0…2550
Time delay in s [1...15]unsignedInt 1…151
Sending and switching delay after bus voltage recovery in s [2...255]unsignedInt 2…2552
During sending and switching delay outputs remain unchanged.list<-- Note
Send object "In operation"listNo
Sending cycle time in s [1...65,535]unsignedInt 1…6553560
Object valuelist1
Limit number of telegramslistNo
Max. number of sent telegramsunsignedInt 1…2551
In periodlist1 s
Enable communication object "Request status values" 1 bitlistNo
Request with object valuelist1
JA bei JRA/Sx.yyy.5.1 d.h. alle Geräte mit HandbedienunglistNo
Manual operationlistEnabled
Manual operation after bus voltage recovery, programming and resetlistEnabled
Reset manual operat. to KNX operationlistAutomatically and via push button
Time for automatic reset in s [10...6,000]unsignedInt 10…6000300
Enable communication object "Status Man. operation" 1 bitlistNo
Send object valuelistNo, update only
Safety commands like weather alarms, blocking and forced operation havelist<-- Note
Parameter settingslistStandard
Order of priority for weather alarm functionslist1.Wind alarm - 2.Rain alarm - 3.Frost alarm
Communication object no. 1 for wind alarmlistActivated
Communication object no. 2 for wind alarmlistDeactivated
Communication object no. 3 for wind alarmlistDeactivated
Monitoring period wind alarm in s [0...1,000] (0 = monitoring deact.)unsignedInt 0…10000
Communication object for rain alarmlistDeactivated
Monitoring period rain alarm in s [0...1,000] (0 = monitoring deact.)unsignedInt 0…10000
Communication object for frost alarmlistDeactivated
Monitoring period frost alarm in s [0...1,000] (0 = monitoring deact.)unsignedInt 0…10000
Wind, rain, and frost alarm are active only if a position is setlist<-- Note
Read activated weather alarm objects after bus voltage recoverylistNo
Read flags must be set in sending device!list<-- Note
Operation modelistControl with slat adjustment
To control venetian or vertical blinds and other shading systems with slatslist<-- Note
To control roller shutters, awnings and other products without slatslist<-- Note
Reaction on bus voltage failurelistStop
Reaction on bus voltage failurelistOpen/on
Reaction after bus voltage recoverylistStop
Reaction after bus voltage recoverylistOpen/on
Position Height in % [0...100] (0% = top; 100% = bottom)unsignedInt 0…1000
Position Slat in % [0...100] (0% = open; 100% = closed)unsignedInt 0…1000
Reaction after programming or after ETS resetlistStop
Reaction after programming or after ETS resetlistOpen/on
Invert outputlistNo
Staircase lighting functionlistDeactivated
Duration/opening time for staircase lighting function in s [0...30,000]unsignedInt 0…3000060
Output reacts on communication object for wind alarm no.list1
Position on wind alarmlistActivated - up
Position on wind alarmlistDeactivated
Position Height in % [0...100] (0% = top; 100% = bottom)unsignedInt 0…1000
Position Slat in % [0...100] (0% = open; 100% = closed)unsignedInt 0…1000
Position on rain alarmlistDeactivated
Position for frost alarmlistDeactivated
BlocklistDeactivated
Position during blockinglistNo reaction
Forced operation (1 bit/2 bit)listDeactivated
Position during forced operationlistOpen/on
Position on reset of weather alarm, blocking and forced operationlistNo reaction
Position on reset of weather alarm, blocking and forced operationlistOpen/on
Position will only be carried out with inactive autom. sun protectionlist<-- Note
Order of priority for safety alarm functionslist1.Weather alarm - 2.Block - 3.Forced operation
Disable automatic sun protection on reset of safety functionlistNo
Wind, rain, and frost alarm are active if objects on page "Weather alarms"list<-- Note
Detect travel times (Up/Down)listNo - set travel times
Enable travel detectionlistAutomatically
Position after travel detectionlistNo reaction, remain in upper end position
UP time in s [0...6,000]unsignedInt 0…600060
DOWN time in s [0...6,000]unsignedInt 0…600060
Disconnect output from power afterlistTotal travel time + 10% Overflow
Enable communication object "Trigger reference movement" 1 bitlistNo
Position after reference movementlistNo reaction, remain in reference position
Delete saved travel times after DownloadlistNo
Pause on change in direct. in ms (see technical data of drive!) 50...10,000unsignedInt 50…10000500
Delay times for drivelistStandard
Diff. between start-up and coasting delay: time in ms/4 [-128...127]signedInt -128…1270
Minimum run time for drive in ms [10...255]unsignedInt 10…25550
Jalousie/Raffstore mit ArbeitsstellunglistNo
Lamellenstellung bei Ab-Fahrt in % (0% = offen;100% = geschlossenunsignedInt 0…2550
Determine times for slatlistVia duration of slat adjustment (step)
Duration to turn slat from 0% - 100% in ms [50...60,000]unsignedInt 50…600001500
Duration of slat adjustment (step) in ms [50...1,000]unsignedInt 50…1000200
Number of slat adjustments (from 0% = open to 100% = closed)unsignedInt 1…607
Quotient of slat adjustment time and number of slat adj.: >= 50 ms!list<-- Note
Limit step commands to number of slat adjustmentslistYes
Total turning of slats after move DOWNlistNo
Position of slat after arriving on lower end position (100% = disabled)unsignedInt 0…100100
Limit travelling rangelistNo
Upper limit in % [0...100] (0% = top; 100% = bottom)unsignedInt 0…1000
Upper limit valid for automatic commandslistNo
Upper limit valid for direct commandslistNo
Lower limit in % [0...100] (0% = top; 100% = bottom)unsignedInt 0…100100
Lower limit valid for automatic commandslistNo
Lower limit valid for direct commandslistNo
Set dead timeslistStandard
Dead time blinds/shutter from bottom until moving up in ms [0...5,000]unsignedInt 0…50000
Dead time of slat from 100% closed until slat turn in ms [0...5,000]unsignedInt 0…50000
Slippage of blinds/shutter on change of direction in ms [0...5,000]unsignedInt 0…50000
Slippage of slat on change of direction in ms [0...5,000]unsignedInt 0…50000
Tensioning blinds/shutter or slot positioninglistNo
Time for tensioning/slot positioning in ms [0...5,000]unsignedInt 0…50000
Enable positions/presetslistNo
Enable automatic sun protectionlistNo
Enable 8 bit scenelistNo
Enable communication object "Move to pos. height 0..255"listNo
Enable communication objects "Move to pos. height/Move slat 0..255"listNo
Enable communication objects "Move to/set position 1-4" 1 bitlistNo
Overwrite position values (presets) during downloadlistYes
Enable communication object "Status Open-Closed/On-Off" 1 bitlistNo
Position 1: Height in % [0...100] (0% = top; 100% = bottom)unsignedInt 0…10020
Position 1: Slat in % [0...100] (0% = open; 100% = closed)unsignedInt 0…10020
Position 2: Height in % [0...100] (0% = top; 100% = bottom)unsignedInt 0…10040
Enable communication object "Status Operability" 1 bitlistNo
Position 2: Slat in % [0...100] (0% = open; 100% = closed)unsignedInt 0…10040
Position 3: Height in % [0...100] (0% = top; 100% = bottom)unsignedInt 0…10060
Enable communication object "Status information" 16 bitlistNo
Position 3: Slat in % [0...100] (0% = open; 100% = closed)unsignedInt 0…10060
Position 4: Height in % [0...100] (0% = top; 100% = bottom)unsignedInt 0…10080
Position 4: Slat in % [0...100] (0% = open; 100% = closed)unsignedInt 0…10080
Move to positionlistDirectly
Deactivation of automatic controllistVia object "Activation" and move command
Automatic reactivation of automatic controllistDeactivated
Time to reactivate autom. control automatically in min. [10...6,000]unsignedInt 10…6000300
Toggling to automatic controllistEnabled
Toggling to direct controllistEnabled
Position for sun = 1 (sun)listDown
Position for sun = 0 (no sun)listUp
Delay for sun = 1 in s [0...6,000]unsignedInt 0…60000
Delay for sun = 0 in s [0...6,000]unsignedInt 0…60000
Read activated automatic objects after bus voltage recoverylistNo
Read flags must be set at sending devicelist<-- Note
Enable automatic heating/coolinglistNo
Delay for presence = 1 in s [0...6,000]unsignedInt 0…60000
Delay for presence = 0 in s [0...6,000]unsignedInt 0…60000
Position for heating = 1 and sun = 1listUp
Use overheat controllistNo
Upper threshold value room temperature in °C [21...50]unsignedInt 21…5024
Position at upper threshold value and sun = 1listDown
Position Height in % [0...100] (0% = top; 100% = bottom)unsignedInt 0…1000
Position Slat in % [0...100] (0% = open; 100% = closed)unsignedInt 0…1000
Position for heating = 1 and sun = 0listNo reaction
Position for cooling = 1 and sun = 1listDown
Position for cooling = 1 and sun = 0listNo reaction
On heating = 1 and cooling = 1 or on heating = 0 and cooling = 0list<-- Note
A: ScenelistDeactivated
Overwrite scenes on downloadlistNo
Use 1st assignmentlistNo
Assignment to scene number 1...64listScene No. 1
Use 2nd assignmentlistNo
Use 3rd assignmentlistNo
Use 4th assignmentlistNo
Use 5th assignmentlistNo
Use 6th assignmentlistNo
Use 7th assignmentlistNo
Use 8th assignmentlistNo
Use 9th assignmentlistNo
Use 10th assignmentlistNo
Use 11th assignmentlistNo
Use 12th assignmentlistNo
Use 13th assignmentlistNo
Use 14th assignmentlistNo
Use 15th assignmentlistNo
Use 16th assignmentlistNo
Use 17th assignmentlistNo
Use 18th assignmentlistNo
Enable communication object "Status Height/Slat 0...255" 1 bytelistNo
Enable communication object "Status Height 0...255" 1 bytelistNo
Enable communication object "Status Upper/Lower end pos." 1 bitlistNo
Enable communication object "Status Automatic" 1 bitlistNo
B: ScenelistDeactivated
C: ScenelistDeactivated
D: ScenelistDeactivated

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Blind/Roller Shutter 4f 230V/1.4a 1.4 latest$A078FD8F2026-11-25372 KBDownload

About this file

This is the official ETS product database for the ABB AG - STOTZ-KONTAKT JRA/S4.230.1.1 Blind/RollerShutterAct,4f,230V (2CDG 110 130 R0011), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from ABB AG - STOTZ-KONTAKT

All ABB AG - STOTZ-KONTAKT products