| Transmission and switching delay after
recovery of bus voltage (2...255s) | unsignedInt 2…255 | 2 |
| Telegrammrate_Zeittics
59 = 1sec | unsignedInt 0…255 | 59 |
| Send cyclical "In operation" telegram
(0...65.535s, 0 = inactiv) | unsignedInt 0…65535 | 0 |
| Enable Safety object for operating mode
"Switch Actuator" | list | no |
| Hinweis: Aktion des Ausgangs auf
"Funktion Sicherheit Priorität x" | list | is set on parameter-window "X: Safety" |
| Function Safety Priority 1 | list | inactive |
| Control period in seconds
(0...65.535, 0 = inactive) | unsignedInt 0…65535 | 0 |
| Function Safety Priority 2 | list | inactive |
| Function Safety Priority 3 | list | inactive |
| Operating mode of output A | list | Switch Actuator |
| Status response of switching state
object "Status Switch" | list | only after changing |
| object value switching status
(object "Status Switch") | list | 1=closed, 0=open |
| Reaction on bus voltage failure | list | Contact unchanged |
| Connected valve type | list | normally closed |
| Control telegram is received as | list | 1 bit (PWM or on-off control) |
| Transmit status response
object "Status heating" | list | no |
| Value object "Switch" on
bus voltage recovery | list | not write |
| Overwrite scene, preset and
threshold value 1 with download | list | yes |
| PWM-cycle time for continuous control
Minutes (3...65.535) | unsignedInt 3…65535 | 10 |
| PWM-cycle time for continuous control
Seconds (0...59) | unsignedInt 0…59 | 0 |
| Position of the valve drive on
bus voltage recovery | list | 0% (closed) |
| Enable monitoring of the controller | list | no |
| Enable function "forced operation" | list | no |
| Reaction of output A | list | Normally open contact |
| Enable function "valve purge" | list | no |
| Enable time functions "delay,
staircase lighting, flashing" | list | no |
| Value object "Disable Time Function"
after bus voltage recovery | list | "0", enable time functions |
| Enable function "presets" | list | no |
| Enable function "scene (8 bit)" | list | no |
| Enable function "logic" | list | no |
| Enable functions "priorty and safety,
operation" | list | no |
| Enable function "threshold" | list | no |
| State without function | list | not write |
| Time function | list | Staircase lighting function |
| Flashing if object "Switching" is | list | always flashing, ON (1) or OFF (0) |
| in seconds (0...59) | unsignedInt 0…59 | 0 |
| in minutes (0...65.535) | unsignedInt 0…65535 | 60 |
| Duration of staircase lighting
Minutes (0...1000) | unsignedInt 0…1000 | 5 |
| Delay for switching on: (Min.(0...65535) | unsignedInt 0…65535 | 0 |
| Time for ON: Min. (0...65.535) | unsignedInt 0…65535 | 0 |
| Time for ON: Sec. (1...59) | unsignedInt 1…59 | 5 |
| Seconds (0...59) | unsignedInt 0…59 | 0 |
| Delay for switching on: Sec. (0...59) | unsignedInt 0…59 | 0 |
| Position of the valve drive during
fault of room thermostat | list | unchanged |
| Time for OFF: Min. (0...65.535) | unsignedInt 0…65535 | 0 |
| Delay for switching OFF: Min. (0...65.53 | unsignedInt 0…65535 | 0 |
| Time for OFF: Sec. (1...59) | unsignedInt 1…59 | 5 |
| Delay for switching OFF: Sec. (0...59) | unsignedInt 0…59 | 0 |
| Number of ON-impulses: (1...100) | unsignedInt 1…100 | 5 |
| Extending staircase lighting by
multiple operation ("pumping up") | list | yes (retriggerable) |
| Enable object "RTR fault" | list | no |
| Contact position after flashing | list | calculate present contact position |
| Staircase lighting can be switched off | list | ON with "1" and OFF with "0" |
| Warning before end of staircase lighting | list | via object |
| Warning time in sec. (0...65.535) add
to duration of staircase lighting | unsignedInt 0…65535 | 45 |
| Valve position during forced
positioning | list | unchanged |
| Duration of staircase lighting can be
changed by object | list | no |
| Note: Observe contact life and
switching frequency per minute | list | see technical data |
| Restart of staircase time after
end of permanent ON | list | no |
| Time of valve purge in minutes
(0...255) | unsignedInt 0…255 | 10 |
| Automatic valve purge | list | disable |
| Automatische Spülung | unsignedInt 0…65000 | 0 |
| Reaction on preset 1 (telegr. value 0) | list | no reaction |
| Reaction on preset 2 (telegr. value 1) | list | no reaction |
| Preset can be set via the bus | list | yes |
| Output is assigned to
(Scene 1...64) | list | no allocation |
| Standard value | list | ON |
| Logical Connection 1 | list | disable |
| Function of object "Logical connection2" | list | AND |
| Gate disabled, if Object value
"Logical connection 1" is | list | "0" |
| Result is inverted | list | no |
| Object value "Logical connection 1"
after bus voltage recovery | list | "0" |
| Logical Connection 2 | list | disable |
| Gate disabled, if Object value
"Logical connection 2" is | list | "0" |
| Object value "Logical connection 2"
after bus voltage recovery | list | "0" |
| Enable "Safety Priority x" | list | on parameter-window "General" |
| Contact position if Safety Priority 1 | list | inactive |
| Contact position if forced operation | list | inactive |
| Object value "Forced positioning"
on bus voltage recovery | list | disable |
| Object value "Forced positioning"
on bus voltage recovery | list | "0" inactive |
| Contact position if Safety Priority 2 | list | inactive |
| Contact position if Safety Priority 3 | list | inactive |
| Reaction when forced operation
and all Safety Priority x end | list | calculate present contact position |
| Data type of object "Threshold input" | list | 1 byte (0...255) |
| Change Threshold 1 over bus | list | no |
| Threshold value 1 (0...65.535)) | unsignedInt 0…65535 | 20000 |
| Threshold value 1 (0...255) | unsignedInt 0…255 | 80 |
| Threshold value 2 (0...255) | unsignedInt 0…255 | 160 |
| Threshold value 2 (0...65.535) | unsignedInt 0…65535 | 40000 |
| Threshold values define hysteresis | list | yes |
| Falling below lower threshold | list | no reaction |
| Object value < lower threshold | list | no reaction |
| Lower thrsh. <= object <= upper thrsh. | list | no reaction |
| Object value > lower threshold | list | no reaction |
| Exceeding upper threshold | list | no reaction |
| Object "threshold input" value
on bus voltage recovery (0...255) | unsignedInt 0…255 | 0 |
| Object "threshold input" value
on bus voltage recovery (0...65.535) | unsignedInt 0…65535 | 0 |
| Operating mode of output B | list | Switch Actuator |
| Reaction of output B | list | Normally open contact |