KNX Database

6194/22 Binärausgang,4f,16/20A,C-Last,REG 6194/22

ABB AG - BUSCH-JAEGER · Order number 6194/22 · Output › Binary output, 8-fold

Download .knxprod Switch 8f 16C/3.2 3.2 · 501 KB

Product

ManufacturerABB AG - BUSCH-JAEGER
Product name6194/22 Binärausgang,4f,16/20A,C-Last,REG
Order number6194/22
HardwareSA/S8.16.5.1
MediumTwisted Pair
Bus current (mA)12
Rail mountedYes
Width (mm)144
RegistrationRegistered
Languagesde-DE
Catalog entryM-0007_H-2CDG.20110.20134.20R0011-1-O0002_HP-A06B-32-B007-O0002_CI-6194.2F22-1
FingerprintB007
SHA-256375b93232f4d460dd659cf06cefdca3a9380bd94006b7e11b4ae80ba670eccdb
First seen2026-11-25
MarketsAustralia

Application program: Switch 8f 16C/3.2 3.2

Application number$A06B
Version3.2
Mask versionMV-0701 (7.1)
KNX Data SecureNo
Parameters1056
Group objects250
Group objects (250)
NoNameFunctionSizeDPTFlags
0GeneralIn Operation1 BitCRT
1GeneralSafety Priority 11 BitCWU
2GeneralSafety Priority 21 BitCWU
3GeneralSafety Priority 31 BitCWU
4xDummy1 Bit
5xDummy1 Bit
6xDummy1 Bit
7xDummy1 Bit
8xDummy1 Bit
9xDummy1 Bit
10Output AControl value (PWM)1 ByteCW
10Output ASwitch1 BitCW
11Output ATrigger valve purge1 BitCW
11Output APermanent ON1 BitCW
12Output AStatus valve purge1 BitCT
12Output ADisable time function1 BitCW
13Output ARTR fault1 BitCT
13Output ADuration of staircase lighting2 BytesCRW
14Output AForced operation1 BitCW
14Output Awarning stair lighting1 BitCT
15Output AStatus heating1 ByteCT
15Output AStatus heating1 BitCT
15Output ACall preset 1/21 BitCW
16Output ASet preset 1/21 BitCW
17Output A8 bitScene1 ByteCW
18Output ALogical connection 11 BitCW
19Output ALogical connection 21 BitCW
20Output AForced Positioning2 BitCW
20Output AForced Positioning1 BitCW
21Output AThreshold input2 BytesCW
21Output AThreshold input1 ByteCW
22Output AChange Threshold value 11 ByteCW
22Output AChange Threshold value 12 BytesCW
23xDummy1 Bit
24xDummy1 Bit
25Output AContact monitoring1 BitCT
26Output ACurrent Value2 BytesCRT
27Output AStatus Current-Threshold 11 BitCT
28Output AStatus Current-Threshold 21 BitCT
29Output AStatus Switch1 BitCRT
30Output BControl value (PWM)1 ByteCW
30Output BSwitch1 BitCW
31Output BTrigger valve purge1 BitCW
31Output BPermanent ON1 BitCW
32Output BStatus valve purge1 BitCT
32Output BDisable time function1 BitCW
33Output BRTR fault1 BitCT
33Output BDuration of staircase lighting2 BytesCRW
34Output BForced operation1 BitCW
34Output Bwarning stair lighting1 BitCT
35Output BStatus heating1 ByteCT
35Output BStatus heating1 BitCT
35Output BCall preset 1/21 BitCW
36Output BSet preset 1/21 BitCW
37Output B8 bitScene1 ByteCW
38Output BLogical connection 11 BitCW
39Output BLogical connection 21 BitCW
40Output BForced Positioning2 BitCW
40Output BForced Positioning1 BitCW
41Output BThreshold input2 BytesCW
41Output BThreshold input1 ByteCW
42Output BChange Threshold value 11 ByteCW
42Output BChange Threshold value 12 BytesCW
43xDummy1 Bit
44xDummy1 Bit
45Output BContact monitoring1 BitCT
46Output BCurrent Value2 BytesCRT
47Output BStatus Current-Threshold 11 BitCT
48Output BStatus Current-Threshold 21 BitCT
49Output BStatus Switch1 BitCRT
50Output CControl value (PWM)1 ByteCW
50Output CSwitch1 BitCW
51Output CTrigger valve purge1 BitCW
51Output CPermanent ON1 BitCW
52Output CStatus valve purge1 BitCT
52Output CDisable time function1 BitCW
53Output CRTR fault1 BitCT
53Output CDuration of staircase lighting2 BytesCRW
54Output CForced operation1 BitCW
54Output Cwarning stair lighting1 BitCT
55Output CStatus heating1 ByteCT
55Output CStatus heating1 BitCT
55Output CCall preset 1/21 BitCW
56Output CSet preset 1/21 BitCW
57Output C8 bitScene1 ByteCW
58Output CLogical connection 11 BitCW
59Output CLogical connection 21 BitCW
60Output CForced Positioning2 BitCW
60Output CForced Positioning1 BitCW
61Output CThreshold input2 BytesCW
61Output CThreshold input1 ByteCW
62Output CChange Threshold value 11 ByteCW
62Output CChange Threshold value 12 BytesCW
63xDummy1 Bit
64xDummy1 Bit
65Output CContact monitoring1 BitCT
66Output CCurrent Value2 BytesCRT
67Output CStatus Current-Threshold 11 BitCT
68Output CStatus Current-Threshold 21 BitCT
69Output CStatus Switch1 BitCRT
70Output DSwitch1 BitCW
70Output DControl value (PWM)1 ByteCW
71Output DPermanent ON1 BitCW
71Output DTrigger valve purge1 BitCW
72Output DDisable time function1 BitCW
72Output DStatus valve purge1 BitCT
73Output DDuration of staircase lighting2 BytesCRW
73Output DRTR fault1 BitCT
74Output Dwarning stair lighting1 BitCT
74Output DForced operation1 BitCW
75Output DCall preset 1/21 BitCW
75Output DStatus heating1 ByteCT
75Output DStatus heating1 BitCT
76Output DSet preset 1/21 BitCW
77Output D8 bitScene1 ByteCW
78Output DLogical connection 11 BitCW
79Output DLogical connection 21 BitCW
80Output DForced Positioning2 BitCW
80Output DForced Positioning1 BitCW
81Output DThreshold input2 BytesCW
81Output DThreshold input1 ByteCW
82Output DChange Threshold value 11 ByteCW
82Output DChange Threshold value 12 BytesCW
83xDummy1 Bit
84xDummy1 Bit
85Output DContact monitoring1 BitCT
86Output DCurrent Value2 BytesCRT
87Output DStatus Current-Threshold 11 BitCT
88Output DStatus Current-Threshold 21 BitCT
89Output DStatus Switch1 BitCRT
90Output ESwitch1 BitCW
90Output EControl value (PWM)1 ByteCW
91Output ETrigger valve purge1 BitCW
91Output EPermanent ON1 BitCW
92Output EDisable time function1 BitCW
92Output EStatus valve purge1 BitCT
93Output EDuration of staircase lighting2 BytesCRW
93Output ERTR fault1 BitCT
94Output Ewarning stair lighting1 BitCT
94Output EForced operation1 BitCW
95Output ECall preset 1/21 BitCW
95Output EStatus heating1 BitCT
95Output EStatus heating1 ByteCT
96Output ESet preset 1/21 BitCW
97Output E8 bitScene1 ByteCW
98Output ELogical connection 11 BitCW
99Output ELogical connection 21 BitCW
100Output EForced Positioning2 BitCW
100Output EForced Positioning1 BitCW
101Output EThreshold input1 ByteCW
101Output EThreshold input2 BytesCW
102Output EChange Threshold value 11 ByteCW
102Output EChange Threshold value 12 BytesCW
103xDummy1 Bit
104xDummy1 Bit
105Output EContact monitoring1 BitCT
106Output ECurrent Value2 BytesCRT
107Output EStatus Current-Threshold 11 BitCT
108Output EStatus Current-Threshold 21 BitCT
109Output EStatus Switch1 BitCRT
110Output FControl value (PWM)1 ByteCW
110Output FSwitch1 BitCW
111Output FTrigger valve purge1 BitCW
111Output FPermanent ON1 BitCW
112Output FStatus valve purge1 BitCT
112Output FDisable time function1 BitCW
113Output FRTR fault1 BitCT
113Output FDuration of staircase lighting2 BytesCRW
114Output FForced operation1 BitCW
114Output Fwarning stair lighting1 BitCT
115Output FStatus heating1 ByteCT
115Output FStatus heating1 BitCT
115Output FCall preset 1/21 BitCW
116Output FSet preset 1/21 BitCW
117Output F8 bitScene1 ByteCW
118Output FLogical connection 11 BitCW
119Output FLogical connection 21 BitCW
120Output FForced Positioning2 BitCW
120Output FForced Positioning1 BitCW
121Output FThreshold input2 BytesCW
121Output FThreshold input1 ByteCW
122Output FChange Threshold value 11 ByteCW
122Output FChange Threshold value 12 BytesCW
123xDummy1 Bit
124xDummy1 Bit
125Output FContact monitoring1 BitCT
126Output FCurrent Value2 BytesCRT
127Output FStatus Current-Threshold 11 BitCT
128Output FStatus Current-Threshold 21 BitCT
129Output FStatus Switch1 BitCRT
130Output GControl value (PWM)1 ByteCW
130Output GSwitch1 BitCW
131Output GTrigger valve purge1 BitCW
131Output GPermanent ON1 BitCW
132Output GStatus valve purge1 BitCT
132Output GDisable time function1 BitCW
133Output GRTR fault1 BitCT
133Output GDuration of staircase lighting2 BytesCRW
134Output GForced operation1 BitCW
134Output Gwarning stair lighting1 BitCT
135Output GStatus heating1 ByteCT
135Output GStatus heating1 BitCT
135Output GCall preset 1/21 BitCW
136Output GSet preset 1/21 BitCW
137Output G8 bitScene1 ByteCW
138Output GLogical connection 11 BitCW
139Output GLogical connection 21 BitCW
140Output GForced Positioning2 BitCW
140Output GForced Positioning1 BitCW
141Output GThreshold input2 BytesCW
141Output GThreshold input1 ByteCW
142Output GChange Threshold value 11 ByteCW
142Output GChange Threshold value 12 BytesCW
143xDummy1 Bit
144xDummy1 Bit
145Output GContact monitoring1 BitCT
146Output GCurrent Value2 BytesCRT
147Output GStatus Current-Threshold 11 BitCT
148Output GStatus Current-Threshold 21 BitCT
149Output GStatus Switch1 BitCRT
150Output HControl value (PWM)1 ByteCW
150Output HSwitch1 BitCW
151Output HTrigger valve purge1 BitCW
151Output HPermanent ON1 BitCW
152Output HStatus valve purge1 BitCT
152Output HDisable time function1 BitCW
153Output HRTR fault1 BitCT
153Output HDuration of staircase lighting2 BytesCRW
154Output HForced operation1 BitCW
154Output Hwarning stair lighting1 BitCT
155Output HStatus heating1 ByteCT
155Output HStatus heating1 BitCT
155Output HCall preset 1/21 BitCW
156Output HSet preset 1/21 BitCW
157Output H8 bitScene1 ByteCW
158Output HLogical connection 11 BitCW
159Output HLogical connection 21 BitCW
160Output HForced Positioning2 BitCW
160Output HForced Positioning1 BitCW
161Output HThreshold input2 BytesCW
161Output HThreshold input1 ByteCW
162Output HChange Threshold value 11 ByteCW
162Output HChange Threshold value 12 BytesCW
163xDummy1 Bit
164xDummy1 Bit
165Output HContact monitoring1 BitCT
166Output HCurrent Value2 BytesCRT
167Output HStatus Current-Threshold 11 BitCT
168Output HStatus Current-Threshold 21 BitCT
169Output HStatus Switch1 BitCRT
Parameters (113)
ParameterTypeDefault
Transmission and switching delay after recovery of bus voltage (2...255s)unsignedInt 2…2552
Rate of telegramslistnot limited
Rate of telegramsunsignedInt 0…25559
Send cyclical "In operation" telegram (0...65.535s, 0 = inactiv)unsignedInt 0…655350
Enable Safety object for operating mode "Switch Actuator"listno
Remark: Reaction of output on "Function Safety Priority x"listis set on parameter-window "X: Safety"
Function Safety Priority 1listinactive
Control period in seconds (0...65.535, 0 = inactive)unsignedInt 0…655350
Function Safety Priority 2listinactive
Function Safety Priority 3listinactive
Operating mode of output AlistSwitch Actuator
Status response of switching state object "Status Switch"listonly after changing
object value switching status (object "Status Switch")list1=closed, 0=open
Reaction on bus voltage failurelistContact unchanged
Connected valve typelistnormally closed
Control telegram is received aslist1 bit (PWM or on-off control)
Transmit status response object "Status heating"listno
Value object "Switch" on bus voltage recoverylistnot write
Overwrite scene, preset and threshold value 1 with downloadlistyes
PWM-cycle time for continuous control Minutes (3...65.535)unsignedInt 3…6553510
PWM-cycle time for continuous control Seconds (0...59)unsignedInt 0…590
Position of the valve drive on bus voltage recoverylist0% (closed)
Enable monitoring of the controllerlistno
Enable function "forced operation"listno
Reaction of output AlistNormally open contact
Enable function "valve purge"listno
Enable time functions "delay, staircase lighting, flashing"listno
Value object "Disable Time Function" after bus voltage recoverylist"0", enable time functions
Enable function "presets"listno
Enable function "scene (8 bit)"listno
Enable function "logic"listno
Enable functions "priorty and safety, operation"listno
Enable function "threshold"listno
Enable function "current detection"listno
State without functionlistnot write
Time functionlistStaircase lighting function
in seconds (0...59)unsignedInt 0…590
Flashing if object "Switching" islistalways flashing, ON (1) or OFF (0)
in minutes (0...65.535)unsignedInt 0…6553560
Duration of staircase lighting Minutes (0...1000)unsignedInt 0…10005
Delay for switching on: (Min.(0...65535)unsignedInt 0…655350
Time for ON: Min. (0...65.535)unsignedInt 0…655350
Seconds (0...59)unsignedInt 0…590
Delay for switching on: Sec. (0...59)unsignedInt 0…590
Time for ON: Sec. (1...59)unsignedInt 1…595
Position of the valve drive during fault of room thermostatlistunchanged
Time for OFF: Min. (0...65.535)unsignedInt 0…655350
Delay for switching OFF: Min. (0...65.53unsignedInt 0…655350
Delay for switching OFF: Sec. (0...59)unsignedInt 0…590
Time for OFF: Sec. (1...59)unsignedInt 1…595
Enable object "RTR fault"listno
Number of ON-impulses: (1...100)unsignedInt 1…1005
Extending staircase lighting by multiple operation ("pumping up")listyes (retriggerable)
Contact position after flashinglistcalculate present contact position
Staircase lighting can be switched offlistON with "1" and OFF with "0"
Warning before end of staircase lightinglistvia object
Warning time in sec. (0...65.535) add to duration of staircase lightingunsignedInt 0…6553545
Valve position during forced positioninglistunchanged
Duration of staircase lighting can be changed by objectlistno
Restart of staircase time after end of permanent ONlistno
Remamber: Attend contact live and switching frequency per minuteslistsee technical data
Time of valve purge in minutes (0...255)unsignedInt 0…25510
Automatic valve purgelistdisable
Automatic valve purgeunsignedInt 0…650000
Reaction on preset 1 (telegr. value 0)listno reaction
Reaction on preset 2 (telegr. value 1)listno reaction
Preset can be set via the buslistyes
Output is assigned to (Scene 1...64)listno allocation
Standard valuelistON
Logical Connection 1listdisable
Function of object "Logical connection2"listAND
Gate disabled, if Object value "Logical connection 1" islist"0"
Result is invertedlistno
Object value "Logical connection 1" after bus voltage recoverylist"0"
Logical Connection 2listdisable
Gate disabled, if Object value "Logical connection 2" islist"0"
Object value "Logical connection 2" after bus voltage recoverylist"0"
Enable "Safety Priority x"liston parameter-window "General"
Contact position if Safety Priority 1listinactive
Contact position if forced operationlistinactive
Object value "Forced positioning" on bus voltage recoverylistdisable
Object value "Forced positioning" on bus voltage recoverylist"0" inactive
Contact position if Safety Priority 2listinactive
Contact position if Safety Priority 3listinactive
Reaction when forced operation and all Safety Priority x endlistcalculate present contact position
Data type of object "Threshold input"list1 byte (0...255)
Change Threshold 1 over buslistno
Threshold value 1 (0...65.535))unsignedInt 0…6553520000
Threshold value 1 (0...255)unsignedInt 0…25580
Threshold value 2 (0...255)unsignedInt 0…255160
Threshold value 2 (0...65.535)unsignedInt 0…6553540000
Threshold values define hysteresislistyes
Falling below lower thresholdlistno reaction
Object value < lower thresholdlistno reaction
Lower thrsh. <= object <= upper thrsh.listno reaction
Object value > lower thresholdlistno reaction
Exceeding upper thresholdlistno reaction
Object "threshold input" value on bus voltage recovery (0...255)unsignedInt 0…2550
Object "threshold input" value on bus voltage recovery (0...65.535)unsignedInt 0…655350
Operating mode of output BlistSwitch Actuator
Reaction of output BlistNormally open contact
Operating mode of output ClistSwitch Actuator
Reaction of output ClistNormally open contact
Operating mode of output DlistSwitch Actuator
Reaction of output DlistNormally open contact
Operating mode of output ElistSwitch Actuator
Reaction of output ElistNormally open contact
Operating mode of output FlistSwitch Actuator
Reaction of output FlistNormally open contact
Operating mode of output GlistSwitch Actuator
Reaction of output GlistNormally open contact
Operating mode of output HlistSwitch Actuator
Reaction of output HlistNormally open contact

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Switch 8f 16C/3.2 3.2 latest$A06BB0072026-11-25501 KBDownload

About this file

This is the official ETS product database for the ABB AG - BUSCH-JAEGER 6194/22 Binärausgang,4f,16/20A,C-Last,REG (6194/22), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from ABB AG - BUSCH-JAEGER

All ABB AG - BUSCH-JAEGER products