STEINEL Multisensor Aerosol 4007841079192

STEINEL professional · Order number 4007841079192 · Multisensors

Download .knxprod Multisensor Aerosol 1.0 · 98 KB

Product

ManufacturerSTEINEL professional
Product nameSTEINEL Multisensor Aerosol
Order number4007841079192
HardwareMultisensor Aerosol
MediumTwisted Pair
Bus current (mA)35
Rail mountedNo
RegistrationRegistered · 2021-03-10
Languagesde-DE, en-US
Catalog entryM-008E_H-4007841079192-1_HP-7873-10-0386_CI-4007841079192-1
Fingerprint0386
SHA-256160b52c2873d4b36a04cbc9f18864676d4c82063a081990eba92644d323ddf04
First seen2026-11-25
Markets69 markets

Application program: Multisensor Aerosol 1.0

Application number$7873
Version1.0
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version4.0
Parameters420
Group objects104
Group objects (104)
NoNameFunctionSizeDPTFlags
74Switch HVACON/OFF1 Bit1.2 booleanCRT
77Disable HVACON/OFF1 Bit1.3 enableCWT
78Disable HVAC, statusON/OFF1 Bit1.3 enableCRT
80Light level measured1...10002 Bytes9.4 lux (Lux)CRT
83Temperature measured0 ... 40�C2 Bytes9.1 temperature (°C)CRT
84External temperature0 ... 40�C2 Bytes9.1 temperature (°C)CWT
85Temperature limit value 1ON/OFF1 Bit1.2 booleanCRT
86Disable temperature limit value 1ON/OFF1 Bit1.3 enableCWT
87Disable temperature limit value 1, statusON/OFF1 Bit1.3 enableCRT
88Temperature limit value 2ON/OFF1 Bit1.2 booleanCRT
89Disable temperature limit value 2ON/OFF1 Bit1.3 enableCWT
90Disable temperature limit value 2, statusON/OFF1 Bit1.3 enableCRT
91Dewpoint temperature0 ... 40�C2 Bytes9.1 temperature (°C)CRT
92Dewpoint alarmON/OFF1 Bit1.5 alarmCRT
93Humidity level measured0 ... 100%2 Bytes9.7 humidity (%)CRT
94External humidity0 ... 100%2 Bytes9.7 humidity (%)CWT
95Humidity limit value 1ON/OFF1 Bit1.2 booleanCRT
96Disable humidity limit value 1ON/OFF1 Bit1.3 enableCWT
97Disable humidity limit value 1, statusON/OFF1 Bit1.3 enableCRT
98Humidity limit value 2ON/OFF1 Bit1.2 booleanCRT
99Disable humidity limit value 2ON/OFF1 Bit1.3 enableCWT
100Disable humidity limit value 2, statusON/OFF1 Bit1.3 enableCRT
101Absolute air pressurePa4 Bytes14.58 pressure (Pa)CRT
102Relative air pressurePa4 Bytes14.58 pressure (Pa)CRT
103Air pressure limit value 1ON/OFF1 Bit1.2 booleanCRT
104Disable air pressure limit value 1ON/OFF1 Bit1.3 enableCWT
105Disable air pressure limit value 1, statusON/OFF1 Bit1.3 enableCRT
106Air pressure limit value 2ON/OFF1 Bit1.2 booleanCRT
107Disable air pressure limit value 2ON/OFF1 Bit1.3 enableCWT
108Disable air pressure limit value 2, statusON/OFF1 Bit1.3 enableCRT
109Comfort text14 bytes14 Bytes16.0 Character String (ASCII)CRT
110Comfort statusON/OFF1 Bit1.2 booleanCRT
111Logic gate 1 outputON/OFF1 Bit1.2 booleanCRT
112Logic gate 1 output0 ... 2551 ByteDPT.5CRT
113Logic gate 1, input 1ON/OFF1 Bit1.2 booleanCWT
114Logic gate 1, input 2ON/OFF1 Bit1.2 booleanCWT
115Logic gate 1, input 3ON/OFF1 Bit1.2 booleanCWT
116Logic gate 1, input 4ON/OFF1 Bit1.2 booleanCWT
117Disable logic gate 1ON/OFF1 Bit1.3 enableCWT
118Disable logic gate 1, statusON/OFF1 Bit1.3 enableCRT
119Logic gate 2 outputON/OFF1 Bit1.2 booleanCRT
120Logic gate 2 output0 ... 2551 ByteDPT.5CRT
121Logic gate 2, input 1ON/OFF1 Bit1.2 booleanCWT
122Logic gate 2, input 2ON/OFF1 Bit1.2 booleanCWT
123Logic gate 2, input 3ON/OFF1 Bit1.2 booleanCWT
124Logic gate 2, input 4ON/OFF1 Bit1.2 booleanCWT
125Disable logic gate 2ON/OFF1 Bit1.3 enableCWT
126Disable logic gate 2, statusON/OFF1 Bit1.3 enableCRT
127CO2 level measured0 ... 2000ppm2 Bytes9.8 parts/million (ppm)CRT
128Disable CO2 limit valueON/OFF1 Bit1.3 enableCWT
129Disable CO2 limit value, statusON/OFF1 Bit1.3 enableCRT
130CO2 limit value 1 outputON/OFF1 Bit1.2 booleanCRT
131CO2 limit value 1 switching threshold0 ... 2000ppm2 Bytes9.8 parts/million (ppm)CRWT
132CO2 limit value 1 hysteresis0 ... 2000ppm2 Bytes9.8 parts/million (ppm)CRWT
133CO2 limit value 1 stay-on time0 ... 65535 s2 Bytes7.5 time (s)CRWT
134CO2 limit value 2 outputON/OFF1 Bit1.2 booleanCRT
135CO2 limit value 2 switching threshold0 ... 2000ppm2 Bytes9.8 parts/million (ppm)CRWT
136CO2 limit value 2 hysteresis0 ... 2000ppm2 Bytes9.8 parts/million (ppm)CRWT
137CO2 limit value 2 stay-on time0 ... 65535 s2 Bytes7.5 time (s)CRWT
138CO2 limit value 3 outputON/OFF1 Bit1.2 booleanCRT
139CO2 limit value 3 switching threshold0 ... 2000ppm2 Bytes9.8 parts/million (ppm)CRWT
140CO2 limit value 3 hysteresis0 ... 2000ppm2 Bytes9.8 parts/million (ppm)CRWT
141CO2 limit value 3 stay-on time0 ... 65535 s2 Bytes7.5 time (s)CRWT
142CO2 limit value 4 outputON/OFF1 Bit1.2 booleanCRT
143CO2 limit value 4 switching threshold0 ... 2000ppm2 Bytes9.8 parts/million (ppm)CRWT
144CO2 limit value 4 hysteresis0 ... 2000ppm2 Bytes9.8 parts/million (ppm)CRWT
145CO2 limit value 4 stay-on time0 ... 65535 s2 Bytes7.5 time (s)CRWT
146VOC level measured0 ... 20002 BytesCRT
147Disable VOC limit valueON/OFF1 Bit1.3 enableCWT
148Disable VOC limit value, statusON/OFF1 Bit1.3 enableCRT
149VOC limit value 1 outputON/OFF1 Bit1.2 booleanCRT
150VOC limit value 1 switching threshold0 ... 2000 ppb2 BytesCRWT
151VOC limit value 1 hysteresis0 ... 2000 ppb2 BytesCRWT
152VOC limit value 1 stay-on time0 ... 65535 s2 Bytes7.5 time (s)CRWT
153VOC limit value 2 outputON/OFF1 Bit1.2 booleanCRT
154VOC limit value 2 switching threshold0 ... 2000 ppb2 BytesCRWT
155VOC limit value 2 hysteresis0 ... 2000 ppb2 BytesCRWT
156VOC limit value 2 stay-on time0 ... 65535 s2 Bytes7.5 time (s)CRWT
157VOC limit value 3 outputON/OFF1 Bit1.2 booleanCRT
158VOC limit value 3 switching threshold0 ... 2000 ppb2 BytesCRWT
159VOC limit value 3 hysteresis0 ... 2000 ppb2 BytesCRWT
160VOC limit value 3 stay-on time0 ... 65535 s2 Bytes7.5 time (s)CRWT
161VOC limit value 4 outputON/OFF1 Bit1.2 booleanCRT
162VOC limit value 4 switching threshold0 ... 2000 ppb2 BytesCRWT
163VOC limit value 4 hysteresis0 ... 2000 ppb2 BytesCRWT
164VOC limit value 4 stay-on time0 ... 65535 s2 Bytes7.5 time (s)CRWT
179Aerosol input presenceON/OFF1 Bit1.10 start/stopCWT
180Aerosol input number of people0... 2551 Byte5.5 ratio (0..255)CWT
181Aerosol stale air0... 100%1 Byte5.1 percentage (0..100%)CRT
182Aerosol risk of infection0... 100%1 Byte5.1 percentage (0..100%)CRT
183Aerosol presence durationmin2 Bytes7.6 time (min)CRT
184Aerosol absence durationmin2 Bytes7.6 time (min)CRT
185Aerosol stale air greenON/OFF1 Bit1.2 booleanCRT
186Aerosol stale air yellowON/OFF1 Bit1.2 booleanCRT
187Aerosol stale air redON/OFF1 Bit1.2 booleanCRT
188Aerosol stale air threshold green/yellow0-100%1 Byte5.1 percentage (0..100%)CRWT
189Aerosol stale air threshold yellow/red0-100%1 Byte5.1 percentage (0..100%)CRWT
190Aerosol stale air hysteresis0-100%1 Byte5.1 percentage (0..100%)CRWT
191Aerosol risk of infection greenON/OFF1 Bit1.2 booleanCRT
192Aerosol risk of infection yellowON/OFF1 Bit1.2 booleanCRT
193Aerosol risk of infection redON/OFF1 Bit1.2 booleanCRT
194Aerosol risk of infection threshold green/yellow0-100%1 Byte5.1 percentage (0..100%)CRWT
195Aerosol risk of infection threshold yellow/red0-100%1 Byte5.1 percentage (0..100%)CRWT
196Aerosol risk of infection hysteresis0-100%1 Byte5.1 percentage (0..100%)CRWT
Parameters (150)
ParameterTypeDefault
Number of light outputsunsignedInt 0…41
Temperature outputlistinactive
Humidity outputlistinactive
Dewpointlistinactive
HVAC outputlistinactive
CO2 outputlistinactive
VOC outputlistinactive
Air pressurelistinactive
Comfortlistinactive
Brightness outputlistinactive
Constant-lighting controllistinactive
Presence outputlistinactive
Logic gatelistinactive
Bluetoothlistinactive
Object light outputlistON /OFF
ON level in percentunsignedInt 0…100100
OFF level in percentunsignedInt 0…1000
Send switching objectlistON /OFF
Switch ON sceneunsignedInt 1…641
Switch OFF sceneunsignedInt 1…642
Send status cyclicallylistDo not send status cyclically
Interval for sending cyclicallytime30
Light output modelistautomatically ON and OFF
Daytime operationlistNo
Light-level sensor ONlistInternal
Initial level, light-level sensor, externalunsignedInt 10…1000200
Weighting, light-level sensor, externalunsignedInt 1…100100
Switching threshold ONunsignedInt 10…1000500
Switch OFF in relation to light levellistYes
Offset switching threshold OFFunsignedInt 10…1000100
Stay-ON time, IQ modelistinactive
Light output stay-on timetime300
Disable outputlistNo
Behaviour on disablinglistno action
Behaviour on enablinglistContinue control
Basic illuminationlistinactive
Basic illumination ONlistfor a limited time
Basic illumination dimming levelunsignedInt 1…10010
Basic illumination threshold valueunsignedInt 10…100050
Basic illumination ON periodtime900
Slave inputlistinactive
Day/night switchoverlistinactive
Switch-ON delay (only in relation to presence)time300
Stay-on time (only in relation to presence)time900
CO2listinactive
CO2 switch ON valueunsignedInt 0…65535800
CO2 switch OFF valueunsignedInt 0…65535400
VOClistinactive
VOC switch ON valueunsignedInt 0…65535800
VOC switch OFF valueunsignedInt 0…65535400
Send measured value cyclically or upon changelistChange
Min. light-level changeunsignedInt 1…25530
Send measured value cyclicallytime30
Min. changeunsignedInt 1…25510
Send measured value cyclicallytime60
Sensor calibrationsignedInt -128…1270
External temperaturelistinactive
External temperature weightingunsignedInt 1…10050
Temperature limit valueunsignedInt 0…400200
Hysteresis limit valueunsignedInt 0…40050
Limit value, mode switching outputlistTHR over = ON / THR - hyst. under = OFF
Limit value, send status cyclicallylistDo not send status cyclically
Disable thresholdlistNo
Send dewpoint temperaturelistChange
Lead, dewpoint alarmunsignedInt 1…25520
Hysteresis, dewpoint alarmunsignedInt 1…25510
External humiditylistinactive
Weighting, external humidityunsignedInt 1…10050
Limit value, humidityunsignedInt 0…10065
Hysteresis limit valueunsignedInt 0…10010
Interval for sending cyclicallytime10
Local altitudeunsignedInt 0…500070
Limit value, air pressure, inputlistAbsolute air pressure
Air pressure limit valueunsignedInt 3000…1300010200
Hysteresis limit valueunsignedInt 0…11000100
Maximum temperatureunsignedInt 0…5026
Minimum temperatureunsignedInt 0…5020
Max. rel. humidityunsignedInt 0…10065
Min. rel. humidityunsignedInt 0…10030
Max. specific humidityunsignedInt 0…255255
Text message inside comfort fieldtextbehaglich
Text message outside comfort fieldtextunbehaglich
Status, comfort levellistcomfortable = ON / uncomfortable = OFF
Type of logic operationlistOR
Number of inputsunsignedInt 1…42
Type of output objectlistON / OFF
Switching command for logic 0listOFF
Switching command for logic 1listON
Value at logic 0unsignedInt 0…2550
Value at logic 1unsignedInt 0…255255
Send Behaviour, outputlistwhen logic changes
Disable logic gatelistNo
Number, limit valuesunsignedInt 1…41
Limit valueunsignedInt 0…655351200
Hysteresis limit valueunsignedInt 0…65535600
Stay-on timetime0
Send status cyclicallylistON
Limit valueunsignedInt 0…655351000
Hysteresis limit valueunsignedInt 0…65535500
Limit valueunsignedInt 0…65535800
Hysteresis limit valueunsignedInt 0…65535300
Limit valueunsignedInt 0…65535600
Hysteresis limit valueunsignedInt 0…65535200
INIT_FlagAppSaveunsignedInt 0…6553565535
INIT_FlagEtsDownloadunsignedInt 0…6553545054
Switch-ON delay (in seconds)unsignedInt 0…101
Stay-on timetime30
Stay-on time, constant-lighting controltime300
Light-level settingunsignedInt 10…1000500
Light-level sensor inputlistInternal
Weighting, light-level sensor, externalunsignedInt 1…1001
Automatic starting valuelistYes
Starting value, dimming level until first TeachunsignedInt 1…10080
Starting value, dimming levelunsignedInt 1…10080
Constant-lighting control modelistautomatically ON and OFF
Max. variation from the settingunsignedInt 10…100030
Max. dimming steplist2,00%
Send new dimming level afterlist2.0 s
Lighting with sufficient daylightlistswitch OFF
Minimum dimming levellist0,50%
Light-level control for dimming inputlistdisable and dim
2nd outputlistinactive
Offset, 2nd outputsignedInt -100…1000
Slave inputlistON
Stay-ON time, constant-lighting controltime300
Basic illumination ON periodtime10
Basic illumination threshold valueunsignedInt 10…100010
Type of installationlistConcealed wiring
Mounting heightunsignedInt 200…1200200
Szenario (Sensitivität)list(1) Sehr unruhige Umgebung, schwere Industrie
ReachunsignedInt 50…750100
Absence outputlistinactive
HW-Typelisttest
Aerosolstatuslistinactive
Temperature maxunsignedInt 0…10030
Temperatur SteigungunsignedInt 0…1000
Humidity minunsignedInt 0…10040
Humidity maxunsignedInt 0…10060
send stale air cyclicallytime10
send risk cyclicallytime10
Min. changeunsignedInt 1…10010
Threshold Green/YellowunsignedInt 0…10038
Threshold Yellow/RedunsignedInt 0…10063
HysteresisunsignedInt 0…1005
Threshold Green/YellowunsignedInt 0…10025
Threshold Yellow/RedunsignedInt 0…10050
send presence/absence durationlistcyclically
depending on presencelistNo
presence inputlistinactive
input number of peoplelistinactive

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Multisensor Aerosol 1.0 latest$787303862026-11-2598 KBDownload

About this file

This is the official ETS product database for the STEINEL professional STEINEL Multisensor Aerosol (4007841079192), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.