STEINEL Multisensor Aerosol 4007841079192
STEINEL professional · Order number 4007841079192 · Multisensors
Download .knxprod Multisensor Aerosol 1.0 · 98 KB
Product
| Manufacturer | STEINEL professional |
|---|---|
| Product name | STEINEL Multisensor Aerosol |
| Order number | 4007841079192 |
| Hardware | Multisensor Aerosol |
| Medium | Twisted Pair |
| Bus current (mA) | 35 |
| Rail mounted | No |
| Registration | Registered · 2021-03-10 |
| Languages | de-DE, en-US |
| Catalog entry | M-008E_H-4007841079192-1_HP-7873-10-0386_CI-4007841079192-1 |
| Fingerprint | 0386 |
| SHA-256 | 160b52c2873d4b36a04cbc9f18864676d4c82063a081990eba92644d323ddf04 |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: Multisensor Aerosol 1.0
| Application number | $7873 |
|---|---|
| Version | 1.0 |
| Mask version | MV-0705 (7.5) |
| KNX Data Secure | No |
| Minimum ETS version | 4.0 |
| Parameters | 420 |
| Group objects | 104 |
Group objects (104)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 74 | Switch HVAC | ON/OFF | 1 Bit | 1.2 boolean | CRT |
| 77 | Disable HVAC | ON/OFF | 1 Bit | 1.3 enable | CWT |
| 78 | Disable HVAC, status | ON/OFF | 1 Bit | 1.3 enable | CRT |
| 80 | Light level measured | 1...1000 | 2 Bytes | 9.4 lux (Lux) | CRT |
| 83 | Temperature measured | 0 ... 40�C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 84 | External temperature | 0 ... 40�C | 2 Bytes | 9.1 temperature (°C) | CWT |
| 85 | Temperature limit value 1 | ON/OFF | 1 Bit | 1.2 boolean | CRT |
| 86 | Disable temperature limit value 1 | ON/OFF | 1 Bit | 1.3 enable | CWT |
| 87 | Disable temperature limit value 1, status | ON/OFF | 1 Bit | 1.3 enable | CRT |
| 88 | Temperature limit value 2 | ON/OFF | 1 Bit | 1.2 boolean | CRT |
| 89 | Disable temperature limit value 2 | ON/OFF | 1 Bit | 1.3 enable | CWT |
| 90 | Disable temperature limit value 2, status | ON/OFF | 1 Bit | 1.3 enable | CRT |
| 91 | Dewpoint temperature | 0 ... 40�C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 92 | Dewpoint alarm | ON/OFF | 1 Bit | 1.5 alarm | CRT |
| 93 | Humidity level measured | 0 ... 100% | 2 Bytes | 9.7 humidity (%) | CRT |
| 94 | External humidity | 0 ... 100% | 2 Bytes | 9.7 humidity (%) | CWT |
| 95 | Humidity limit value 1 | ON/OFF | 1 Bit | 1.2 boolean | CRT |
| 96 | Disable humidity limit value 1 | ON/OFF | 1 Bit | 1.3 enable | CWT |
| 97 | Disable humidity limit value 1, status | ON/OFF | 1 Bit | 1.3 enable | CRT |
| 98 | Humidity limit value 2 | ON/OFF | 1 Bit | 1.2 boolean | CRT |
| 99 | Disable humidity limit value 2 | ON/OFF | 1 Bit | 1.3 enable | CWT |
| 100 | Disable humidity limit value 2, status | ON/OFF | 1 Bit | 1.3 enable | CRT |
| 101 | Absolute air pressure | Pa | 4 Bytes | 14.58 pressure (Pa) | CRT |
| 102 | Relative air pressure | Pa | 4 Bytes | 14.58 pressure (Pa) | CRT |
| 103 | Air pressure limit value 1 | ON/OFF | 1 Bit | 1.2 boolean | CRT |
| 104 | Disable air pressure limit value 1 | ON/OFF | 1 Bit | 1.3 enable | CWT |
| 105 | Disable air pressure limit value 1, status | ON/OFF | 1 Bit | 1.3 enable | CRT |
| 106 | Air pressure limit value 2 | ON/OFF | 1 Bit | 1.2 boolean | CRT |
| 107 | Disable air pressure limit value 2 | ON/OFF | 1 Bit | 1.3 enable | CWT |
| 108 | Disable air pressure limit value 2, status | ON/OFF | 1 Bit | 1.3 enable | CRT |
| 109 | Comfort text | 14 bytes | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 110 | Comfort status | ON/OFF | 1 Bit | 1.2 boolean | CRT |
| 111 | Logic gate 1 output | ON/OFF | 1 Bit | 1.2 boolean | CRT |
| 112 | Logic gate 1 output | 0 ... 255 | 1 Byte | DPT.5 | CRT |
| 113 | Logic gate 1, input 1 | ON/OFF | 1 Bit | 1.2 boolean | CWT |
| 114 | Logic gate 1, input 2 | ON/OFF | 1 Bit | 1.2 boolean | CWT |
| 115 | Logic gate 1, input 3 | ON/OFF | 1 Bit | 1.2 boolean | CWT |
| 116 | Logic gate 1, input 4 | ON/OFF | 1 Bit | 1.2 boolean | CWT |
| 117 | Disable logic gate 1 | ON/OFF | 1 Bit | 1.3 enable | CWT |
| 118 | Disable logic gate 1, status | ON/OFF | 1 Bit | 1.3 enable | CRT |
| 119 | Logic gate 2 output | ON/OFF | 1 Bit | 1.2 boolean | CRT |
| 120 | Logic gate 2 output | 0 ... 255 | 1 Byte | DPT.5 | CRT |
| 121 | Logic gate 2, input 1 | ON/OFF | 1 Bit | 1.2 boolean | CWT |
| 122 | Logic gate 2, input 2 | ON/OFF | 1 Bit | 1.2 boolean | CWT |
| 123 | Logic gate 2, input 3 | ON/OFF | 1 Bit | 1.2 boolean | CWT |
| 124 | Logic gate 2, input 4 | ON/OFF | 1 Bit | 1.2 boolean | CWT |
| 125 | Disable logic gate 2 | ON/OFF | 1 Bit | 1.3 enable | CWT |
| 126 | Disable logic gate 2, status | ON/OFF | 1 Bit | 1.3 enable | CRT |
| 127 | CO2 level measured | 0 ... 2000ppm | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 128 | Disable CO2 limit value | ON/OFF | 1 Bit | 1.3 enable | CWT |
| 129 | Disable CO2 limit value, status | ON/OFF | 1 Bit | 1.3 enable | CRT |
| 130 | CO2 limit value 1 output | ON/OFF | 1 Bit | 1.2 boolean | CRT |
| 131 | CO2 limit value 1 switching threshold | 0 ... 2000ppm | 2 Bytes | 9.8 parts/million (ppm) | CRWT |
| 132 | CO2 limit value 1 hysteresis | 0 ... 2000ppm | 2 Bytes | 9.8 parts/million (ppm) | CRWT |
| 133 | CO2 limit value 1 stay-on time | 0 ... 65535 s | 2 Bytes | 7.5 time (s) | CRWT |
| 134 | CO2 limit value 2 output | ON/OFF | 1 Bit | 1.2 boolean | CRT |
| 135 | CO2 limit value 2 switching threshold | 0 ... 2000ppm | 2 Bytes | 9.8 parts/million (ppm) | CRWT |
| 136 | CO2 limit value 2 hysteresis | 0 ... 2000ppm | 2 Bytes | 9.8 parts/million (ppm) | CRWT |
| 137 | CO2 limit value 2 stay-on time | 0 ... 65535 s | 2 Bytes | 7.5 time (s) | CRWT |
| 138 | CO2 limit value 3 output | ON/OFF | 1 Bit | 1.2 boolean | CRT |
| 139 | CO2 limit value 3 switching threshold | 0 ... 2000ppm | 2 Bytes | 9.8 parts/million (ppm) | CRWT |
| 140 | CO2 limit value 3 hysteresis | 0 ... 2000ppm | 2 Bytes | 9.8 parts/million (ppm) | CRWT |
| 141 | CO2 limit value 3 stay-on time | 0 ... 65535 s | 2 Bytes | 7.5 time (s) | CRWT |
| 142 | CO2 limit value 4 output | ON/OFF | 1 Bit | 1.2 boolean | CRT |
| 143 | CO2 limit value 4 switching threshold | 0 ... 2000ppm | 2 Bytes | 9.8 parts/million (ppm) | CRWT |
| 144 | CO2 limit value 4 hysteresis | 0 ... 2000ppm | 2 Bytes | 9.8 parts/million (ppm) | CRWT |
| 145 | CO2 limit value 4 stay-on time | 0 ... 65535 s | 2 Bytes | 7.5 time (s) | CRWT |
| 146 | VOC level measured | 0 ... 2000 | 2 Bytes | CRT | |
| 147 | Disable VOC limit value | ON/OFF | 1 Bit | 1.3 enable | CWT |
| 148 | Disable VOC limit value, status | ON/OFF | 1 Bit | 1.3 enable | CRT |
| 149 | VOC limit value 1 output | ON/OFF | 1 Bit | 1.2 boolean | CRT |
| 150 | VOC limit value 1 switching threshold | 0 ... 2000 ppb | 2 Bytes | CRWT | |
| 151 | VOC limit value 1 hysteresis | 0 ... 2000 ppb | 2 Bytes | CRWT | |
| 152 | VOC limit value 1 stay-on time | 0 ... 65535 s | 2 Bytes | 7.5 time (s) | CRWT |
| 153 | VOC limit value 2 output | ON/OFF | 1 Bit | 1.2 boolean | CRT |
| 154 | VOC limit value 2 switching threshold | 0 ... 2000 ppb | 2 Bytes | CRWT | |
| 155 | VOC limit value 2 hysteresis | 0 ... 2000 ppb | 2 Bytes | CRWT | |
| 156 | VOC limit value 2 stay-on time | 0 ... 65535 s | 2 Bytes | 7.5 time (s) | CRWT |
| 157 | VOC limit value 3 output | ON/OFF | 1 Bit | 1.2 boolean | CRT |
| 158 | VOC limit value 3 switching threshold | 0 ... 2000 ppb | 2 Bytes | CRWT | |
| 159 | VOC limit value 3 hysteresis | 0 ... 2000 ppb | 2 Bytes | CRWT | |
| 160 | VOC limit value 3 stay-on time | 0 ... 65535 s | 2 Bytes | 7.5 time (s) | CRWT |
| 161 | VOC limit value 4 output | ON/OFF | 1 Bit | 1.2 boolean | CRT |
| 162 | VOC limit value 4 switching threshold | 0 ... 2000 ppb | 2 Bytes | CRWT | |
| 163 | VOC limit value 4 hysteresis | 0 ... 2000 ppb | 2 Bytes | CRWT | |
| 164 | VOC limit value 4 stay-on time | 0 ... 65535 s | 2 Bytes | 7.5 time (s) | CRWT |
| 179 | Aerosol input presence | ON/OFF | 1 Bit | 1.10 start/stop | CWT |
| 180 | Aerosol input number of people | 0... 255 | 1 Byte | 5.5 ratio (0..255) | CWT |
| 181 | Aerosol stale air | 0... 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 182 | Aerosol risk of infection | 0... 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 183 | Aerosol presence duration | min | 2 Bytes | 7.6 time (min) | CRT |
| 184 | Aerosol absence duration | min | 2 Bytes | 7.6 time (min) | CRT |
| 185 | Aerosol stale air green | ON/OFF | 1 Bit | 1.2 boolean | CRT |
| 186 | Aerosol stale air yellow | ON/OFF | 1 Bit | 1.2 boolean | CRT |
| 187 | Aerosol stale air red | ON/OFF | 1 Bit | 1.2 boolean | CRT |
| 188 | Aerosol stale air threshold green/yellow | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRWT |
| 189 | Aerosol stale air threshold yellow/red | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRWT |
| 190 | Aerosol stale air hysteresis | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRWT |
| 191 | Aerosol risk of infection green | ON/OFF | 1 Bit | 1.2 boolean | CRT |
| 192 | Aerosol risk of infection yellow | ON/OFF | 1 Bit | 1.2 boolean | CRT |
| 193 | Aerosol risk of infection red | ON/OFF | 1 Bit | 1.2 boolean | CRT |
| 194 | Aerosol risk of infection threshold green/yellow | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRWT |
| 195 | Aerosol risk of infection threshold yellow/red | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRWT |
| 196 | Aerosol risk of infection hysteresis | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRWT |
Parameters (150)
| Parameter | Type | Default |
|---|---|---|
| Number of light outputs | unsignedInt 0…4 | 1 |
| Temperature output | list | inactive |
| Humidity output | list | inactive |
| Dewpoint | list | inactive |
| HVAC output | list | inactive |
| CO2 output | list | inactive |
| VOC output | list | inactive |
| Air pressure | list | inactive |
| Comfort | list | inactive |
| Brightness output | list | inactive |
| Constant-lighting control | list | inactive |
| Presence output | list | inactive |
| Logic gate | list | inactive |
| Bluetooth | list | inactive |
| Object light output | list | ON /OFF |
| ON level in percent | unsignedInt 0…100 | 100 |
| OFF level in percent | unsignedInt 0…100 | 0 |
| Send switching object | list | ON /OFF |
| Switch ON scene | unsignedInt 1…64 | 1 |
| Switch OFF scene | unsignedInt 1…64 | 2 |
| Send status cyclically | list | Do not send status cyclically |
| Interval for sending cyclically | time | 30 |
| Light output mode | list | automatically ON and OFF |
| Daytime operation | list | No |
| Light-level sensor ON | list | Internal |
| Initial level, light-level sensor, external | unsignedInt 10…1000 | 200 |
| Weighting, light-level sensor, external | unsignedInt 1…100 | 100 |
| Switching threshold ON | unsignedInt 10…1000 | 500 |
| Switch OFF in relation to light level | list | Yes |
| Offset switching threshold OFF | unsignedInt 10…1000 | 100 |
| Stay-ON time, IQ mode | list | inactive |
| Light output stay-on time | time | 300 |
| Disable output | list | No |
| Behaviour on disabling | list | no action |
| Behaviour on enabling | list | Continue control |
| Basic illumination | list | inactive |
| Basic illumination ON | list | for a limited time |
| Basic illumination dimming level | unsignedInt 1…100 | 10 |
| Basic illumination threshold value | unsignedInt 10…1000 | 50 |
| Basic illumination ON period | time | 900 |
| Slave input | list | inactive |
| Day/night switchover | list | inactive |
| Switch-ON delay (only in relation to presence) | time | 300 |
| Stay-on time (only in relation to presence) | time | 900 |
| CO2 | list | inactive |
| CO2 switch ON value | unsignedInt 0…65535 | 800 |
| CO2 switch OFF value | unsignedInt 0…65535 | 400 |
| VOC | list | inactive |
| VOC switch ON value | unsignedInt 0…65535 | 800 |
| VOC switch OFF value | unsignedInt 0…65535 | 400 |
| Send measured value cyclically or upon change | list | Change |
| Min. light-level change | unsignedInt 1…255 | 30 |
| Send measured value cyclically | time | 30 |
| Min. change | unsignedInt 1…255 | 10 |
| Send measured value cyclically | time | 60 |
| Sensor calibration | signedInt -128…127 | 0 |
| External temperature | list | inactive |
| External temperature weighting | unsignedInt 1…100 | 50 |
| Temperature limit value | unsignedInt 0…400 | 200 |
| Hysteresis limit value | unsignedInt 0…400 | 50 |
| Limit value, mode switching output | list | THR over = ON / THR - hyst. under = OFF |
| Limit value, send status cyclically | list | Do not send status cyclically |
| Disable threshold | list | No |
| Send dewpoint temperature | list | Change |
| Lead, dewpoint alarm | unsignedInt 1…255 | 20 |
| Hysteresis, dewpoint alarm | unsignedInt 1…255 | 10 |
| External humidity | list | inactive |
| Weighting, external humidity | unsignedInt 1…100 | 50 |
| Limit value, humidity | unsignedInt 0…100 | 65 |
| Hysteresis limit value | unsignedInt 0…100 | 10 |
| Interval for sending cyclically | time | 10 |
| Local altitude | unsignedInt 0…5000 | 70 |
| Limit value, air pressure, input | list | Absolute air pressure |
| Air pressure limit value | unsignedInt 3000…13000 | 10200 |
| Hysteresis limit value | unsignedInt 0…11000 | 100 |
| Maximum temperature | unsignedInt 0…50 | 26 |
| Minimum temperature | unsignedInt 0…50 | 20 |
| Max. rel. humidity | unsignedInt 0…100 | 65 |
| Min. rel. humidity | unsignedInt 0…100 | 30 |
| Max. specific humidity | unsignedInt 0…255 | 255 |
| Text message inside comfort field | text | behaglich |
| Text message outside comfort field | text | unbehaglich |
| Status, comfort level | list | comfortable = ON / uncomfortable = OFF |
| Type of logic operation | list | OR |
| Number of inputs | unsignedInt 1…4 | 2 |
| Type of output object | list | ON / OFF |
| Switching command for logic 0 | list | OFF |
| Switching command for logic 1 | list | ON |
| Value at logic 0 | unsignedInt 0…255 | 0 |
| Value at logic 1 | unsignedInt 0…255 | 255 |
| Send Behaviour, output | list | when logic changes |
| Disable logic gate | list | No |
| Number, limit values | unsignedInt 1…4 | 1 |
| Limit value | unsignedInt 0…65535 | 1200 |
| Hysteresis limit value | unsignedInt 0…65535 | 600 |
| Stay-on time | time | 0 |
| Send status cyclically | list | ON |
| Limit value | unsignedInt 0…65535 | 1000 |
| Hysteresis limit value | unsignedInt 0…65535 | 500 |
| Limit value | unsignedInt 0…65535 | 800 |
| Hysteresis limit value | unsignedInt 0…65535 | 300 |
| Limit value | unsignedInt 0…65535 | 600 |
| Hysteresis limit value | unsignedInt 0…65535 | 200 |
| INIT_FlagAppSave | unsignedInt 0…65535 | 65535 |
| INIT_FlagEtsDownload | unsignedInt 0…65535 | 45054 |
| Switch-ON delay (in seconds) | unsignedInt 0…10 | 1 |
| Stay-on time | time | 30 |
| Stay-on time, constant-lighting control | time | 300 |
| Light-level setting | unsignedInt 10…1000 | 500 |
| Light-level sensor input | list | Internal |
| Weighting, light-level sensor, external | unsignedInt 1…100 | 1 |
| Automatic starting value | list | Yes |
| Starting value, dimming level until first Teach | unsignedInt 1…100 | 80 |
| Starting value, dimming level | unsignedInt 1…100 | 80 |
| Constant-lighting control mode | list | automatically ON and OFF |
| Max. variation from the setting | unsignedInt 10…1000 | 30 |
| Max. dimming step | list | 2,00% |
| Send new dimming level after | list | 2.0 s |
| Lighting with sufficient daylight | list | switch OFF |
| Minimum dimming level | list | 0,50% |
| Light-level control for dimming input | list | disable and dim |
| 2nd output | list | inactive |
| Offset, 2nd output | signedInt -100…100 | 0 |
| Slave input | list | ON |
| Stay-ON time, constant-lighting control | time | 300 |
| Basic illumination ON period | time | 10 |
| Basic illumination threshold value | unsignedInt 10…1000 | 10 |
| Type of installation | list | Concealed wiring |
| Mounting height | unsignedInt 200…1200 | 200 |
| Szenario (Sensitivität) | list | (1) Sehr unruhige Umgebung, schwere Industrie |
| Reach | unsignedInt 50…750 | 100 |
| Absence output | list | inactive |
| HW-Type | list | test |
| Aerosolstatus | list | inactive |
| Temperature max | unsignedInt 0…100 | 30 |
| Temperatur Steigung | unsignedInt 0…100 | 0 |
| Humidity min | unsignedInt 0…100 | 40 |
| Humidity max | unsignedInt 0…100 | 60 |
| send stale air cyclically | time | 10 |
| send risk cyclically | time | 10 |
| Min. change | unsignedInt 1…100 | 10 |
| Threshold Green/Yellow | unsignedInt 0…100 | 38 |
| Threshold Yellow/Red | unsignedInt 0…100 | 63 |
| Hysteresis | unsignedInt 0…100 | 5 |
| Threshold Green/Yellow | unsignedInt 0…100 | 25 |
| Threshold Yellow/Red | unsignedInt 0…100 | 50 |
| send presence/absence duration | list | cyclically |
| depending on presence | list | No |
| presence input | list | inactive |
| input number of people | list | inactive |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Multisensor Aerosol 1.0 latest | $7873 | 0386 | 2026-11-25 | 98 KB | Download |
About this file
This is the official ETS product database for the STEINEL professional STEINEL Multisensor Aerosol (4007841079192), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from STEINEL professional
- STEINEL Multisensor AIR 4007841056346
- STEINEL True Presence Multisensor 4007841056353
- STEINEL True Presence Multisensor Aerosol 4007841079208
- STEINEL True Presence Multisensor Black 4007841086060
- STEINEL IR Quattro KNX 4007841002701
- STEINEL IR Quattro HD KNX 4007841002763
- STEINEL HF 360 KNX 4007841002824
- STEINEL DUAL HF KNX 4007841002992
- STEINEL sensIQ S KNX 40078410040xx
- STEINEL iHF 3D KNX 40078410076xx
- STEINEL IR Quattro KNX 4007841008772
- STEINEL IR Quattro HD KNX 4007841008789