KNX Database

STEINEL Multisensor AIR 4007841056346

STEINEL professional · Order number 4007841056346 · Multisensors

Download .knxprod Multisensor AIR 1.0 · 87 KB

Product

ManufacturerSTEINEL professional
Product nameSTEINEL Multisensor AIR
Order number4007841056346
HardwareMultisensor AIR
MediumTwisted Pair
Bus current (mA)35
Rail mountedNo
RegistrationRegistered · 2019-05-29
Languagesde-DE, en-US, nl-NL
Catalog entryM-008E_H-4007841056346-1_HP-7077-10-0D42_CI-4007841056346-1
Fingerprint0D42
SHA-2561f7917dde83464c7d85dde7c8627bdf77522dd47ddc381c8d546a661a9ece636
First seen2026-11-25
Markets69 markets

Application program: Multisensor AIR 1.0

Application number$7077
Version1.0
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version4.0
Parameters172
Group objects86
Group objects (86)
NoNameFunctionSizeDPTFlags
74Switch HVACON/OFF1 Bit1.1 switchCRT
77Disable HVACON/OFF1 Bit1.1 switchCWT
78Disable HVAC, statusON/OFF1 Bit1.1 switchCRT
80Light level measured, mixed lightLux2 Bytes9.4 lux (Lux)CRT
83Temperature measured0 ... 40�C2 Bytes9.1 temperature (°C)CRT
84External temperature0 ... 40�C2 Bytes9.1 temperature (°C)CWT
85Temperature limit value 1ON/OFF1 Bit1.1 switchCRT
86Disable temperature limit value 1ON/OFF1 Bit1.1 switchCWT
87Disable temperature limit value 1, statusON/OFF1 Bit1.1 switchCRT
88Temperature limit value 2ON/OFF1 Bit1.1 switchCRT
89Disable temperature limit value 2ON/OFF1 Bit1.1 switchCWT
90Disable temperature limit value 2, statusON/OFF1 Bit1.1 switchCRT
91Dewpoint temperature0 ... 40�C2 Bytes9.1 temperature (°C)CRT
92Dewpoint alarmON/OFF1 Bit1.1 switchCRT
93Humidity level measured0 ... 100%2 Bytes9.7 humidity (%)CRT
94External humidity0 ... 100%2 Bytes9.7 humidity (%)CWT
95Humidity limit value 1ON/OFF1 Bit1.1 switchCRT
96Disable humidity limit value 1ON/OFF1 Bit1.1 switchCWT
97Disable humidity limit value 1, statusON/OFF1 Bit1.1 switchCRT
98Humidity limit value 2ON/OFF1 Bit1.1 switchCRT
99Disable humidity limit value 2ON/OFF1 Bit1.1 switchCWT
100Disable humidity limit value 2, statusON/OFF1 Bit1.1 switchCRT
101Absolute air pressurePa4 Bytes14.58 pressure (Pa)CRT
102Relative air pressurePa4 Bytes14.58 pressure (Pa)CRT
103Air pressure limit value 1ON/OFF1 Bit1.1 switchCRT
104Disable air pressure limit value 1ON/OFF1 Bit1.1 switchCWT
105Disable air pressure limit value 1, statusON/OFF1 Bit1.1 switchCRT
106Air pressure limit value 2ON/OFF1 Bit1.1 switchCRT
107Disable air pressure limit value 2ON/OFF1 Bit1.1 switchCWT
108Disable air pressure limit value 2, statusON/OFF1 Bit1.1 switchCRT
109Comfort text14 bytes14 Bytes16.0 Character String (ASCII)CRT
110Comfort statusON/OFF1 Bit1.1 switchCRT
111Logic gate 1 outputON/OFF1 Bit1.1 switchCRT
112Logic gate 1 output0 ... 2551 ByteDPT.5CRT
113Logic gate 1, input 1ON/OFF1 Bit1.1 switchCWT
114Logic gate 1, input 2ON/OFF1 Bit1.1 switchCWT
115Logic gate 1, input 3ON/OFF1 Bit1.1 switchCWT
116Logic gate 1, input 4ON/OFF1 Bit1.1 switchCWT
117Disable logic gate 1ON/OFF1 Bit1.1 switchCWT
118Disable logic gate 1, statusON/OFF1 Bit1.1 switchCRT
119Logic gate 2 outputON/OFF1 Bit1.1 switchCRT
120Logic gate 2 output0 ... 2551 ByteDPT.5CRT
121Logic gate 2, input 1ON/OFF1 Bit1.1 switchCWT
122Logic gate 2, input 2ON/OFF1 Bit1.1 switchCWT
123Logic gate 2, input 3ON/OFF1 Bit1.1 switchCWT
124Logic gate 2, input 4ON/OFF1 Bit1.1 switchCWT
125Disable logic gate 2ON/OFF1 Bit1.1 switchCWT
126Disable logic gate 2, statusON/OFF1 Bit1.1 switchCRT
127CO2 level measured0 ... 20002 Bytes9.8 parts/million (ppm)CRT
128Disable CO2 limit valueON/OFF1 Bit1.1 switchCWT
129Disable CO2 limit value, statusON/OFF1 Bit1.1 switchCRT
130CO2 limit value 1 outputON/OFF1 Bit1.1 switchCRT
131CO2 limit value 1 switching threshold0 ... 20002 Bytes9.8 parts/million (ppm)CRWT
132CO2 limit value 1 hysteresis0 ... 20002 Bytes9.8 parts/million (ppm)CRWT
133CO2 limit value 1 stay-on time0 ... 65535 s2 Bytes7.5 time (s)CRWT
134CO2 limit value 2 outputON/OFF1 Bit1.1 switchCRT
135CO2 limit value 2 switching threshold0 ... 20002 Bytes9.8 parts/million (ppm)CRWT
136CO2 limit value 2 hysteresis0 ... 20002 Bytes9.8 parts/million (ppm)CRWT
137CO2 limit value 2 stay-on time0 ... 65535 s2 Bytes7.5 time (s)CRWT
138CO2 limit value 3 outputON/OFF1 Bit1.1 switchCRT
139CO2 limit value 3 switching threshold0 ... 20002 Bytes9.8 parts/million (ppm)CRWT
140CO2 limit value 3 hysteresis0 ... 20002 Bytes9.8 parts/million (ppm)CRWT
141CO2 limit value 3 stay-on time0 ... 65535 s2 Bytes7.5 time (s)CRWT
142CO2 limit value 4 outputON/OFF1 Bit1.1 switchCRT
143CO2 limit value 4 switching threshold0 ... 20002 Bytes9.8 parts/million (ppm)CRWT
144CO2 limit value 4 hysteresis0 ... 20002 Bytes9.8 parts/million (ppm)CRWT
145CO2 limit value 4 stay-on time0 ... 65535 s2 Bytes7.5 time (s)CRWT
146VOC level measured0 ... 20002 BytesDPT.9CRT
147Disable VOC limit valueON/OFF1 Bit1.1 switchCWT
148Disable VOC limit value, statusON/OFF1 Bit1.1 switchCRT
149VOC limit value 1 outputON/OFF1 Bit1.1 switchCRT
150VOC limit value 1 switching threshold0 ... 2000 ppb2 BytesDPT.9CRWT
151VOC limit value 1 hysteresis0 ... 2000 ppb2 BytesDPT.9CRWT
152VOC limit value 1 stay-on time0 ... 65535 s2 Bytes7.5 time (s)CRWT
153VOC limit value 2 outputON/OFF1 Bit1.1 switchCRT
154VOC limit value 2 switching threshold0 ... 2000 ppb2 BytesDPT.9CRWT
155VOC limit value 2 hysteresis0 ... 2000 ppb2 BytesDPT.9CRWT
156VOC limit value 2 stay-on time0 ... 65535 s2 Bytes7.5 time (s)CRWT
157VOC limit value 3 outputON/OFF1 Bit1.1 switchCRT
158VOC limit value 3 switching threshold0 ... 2000 ppb2 BytesDPT.9CRWT
159VOC limit value 3 hysteresis0 ... 2000 ppb2 BytesDPT.9CRWT
160VOC limit value 3 stay-on time0 ... 65535 s2 Bytes7.5 time (s)CRWT
161VOC limit value 4 outputON/OFF1 Bit1.1 switchCRT
162VOC limit value 4 switching threshold0 ... 2000 ppb2 BytesDPT.9CRWT
163VOC limit value 4 hysteresis0 ... 2000 ppb2 BytesDPT.9CRWT
164VOC limit value 4 stay-on time0 ... 65535 s2 Bytes7.5 time (s)CRWT
Parameters (78)
ParameterTypeDefault
Temperature outputlistinactive
Humidity outputlistinactive
Dewpointlistinactive
HVAC outputlistinactive
CO2 outputlistinactive
VOC outputlistinactive
Air pressurelistinactive
Comfortlistinactive
Brightness outputlistinactive
Logic gatelistinactive
Bluetoothlistinactive
CO2listinactive
CO2 switch ON valueunsignedInt 0…65535800
CO2 switch OFF valueunsignedInt 0…65535400
VOClistinactive
VOC switch ON valueunsignedInt 0…65535800
VOC switch OFF valueunsignedInt 0…65535400
Disable outputlistNo
Behaviour on disablinglistno action
Behaviour on enablinglistContinue control
Send measured value cyclically or upon changelistChange
Min. light-level changeunsignedInt 1…25530
Send measured value cyclicallytime30
Min. changeunsignedInt 1…25510
Send measured value cyclicallytime60
Sensor calibrationsignedInt -128…1270
External temperaturelistinactive
External temperature weightingunsignedInt 1…10050
Temperature limit valueunsignedInt 0…400200
Hysteresis limit valueunsignedInt 0…40050
Limit value, mode switching outputlistTHR over = ON / THR - hyst. under = OFF
Limit value, send status cyclicallylistDo not send status cyclically
Interval for sending cyclicallytime30
Disable thresholdlistNo
Send dewpoint temperaturelistChange
Lead, dewpoint alarmunsignedInt 1…25520
Hysteresis, dewpoint alarmunsignedInt 1…25510
External humiditylistinactive
Weighting, external humidityunsignedInt 1…10050
Limit value, humidityunsignedInt 0…10065
Hysteresis limit valueunsignedInt 0…10010
Interval for sending cyclicallytime10
Local altitudeunsignedInt 0…500070
Limit value, air pressure, inputlistAbsolute air pressure
Air pressure limit valueunsignedInt 3000…1300010200
Hysteresis limit valueunsignedInt 0…11000100
Maximum temperatureunsignedInt 0…5026
Minimum temperatureunsignedInt 0…5020
Max. rel. humidityunsignedInt 0…10065
Min. rel. humidityunsignedInt 0…10030
Max. absolute humidityunsignedInt 50…150115
Text message inside comfort fieldtextbehaglich
Text message outside comfort fieldtextunbehaglich
Status, comfort levellistcomfortable = ON / uncomfortable = OFF
Type of logic operationlistOR
Number of inputsunsignedInt 1…42
Type of output objectlistON / OFF
Switching command for logic 0listOFF
Switching command for logic 1listON
Value at logic 0unsignedInt 0…2550
Value at logic 1unsignedInt 0…255255
Send Behaviour, outputlistwhen logic changes
Disable logic gatelistNo
Switching command for logic 1listOFF
Number, limit valuesunsignedInt 1…41
Limit valueunsignedInt 0…655351200
Hysteresis limit valueunsignedInt 0…65535600
Stay-on timetime0
Send status cyclicallylistON
Limit valueunsignedInt 0…655351000
Hysteresis limit valueunsignedInt 0…65535500
Limit value in ppmunsignedInt 0…65535800
Hysteresis limit valueunsignedInt 0…65535300
Limit value in ppmunsignedInt 0…65535600
Hysteresis limit valueunsignedInt 0…65535200
INIT_FlagAppSaveunsignedInt 0…6553565535
INIT_FlagEtsDownloadunsignedInt 0…6553545054
HW_TYPElisttest

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Multisensor AIR 1.0 latest$70770D422026-11-2587 KBDownload

About this file

This is the official ETS product database for the STEINEL professional STEINEL Multisensor AIR (4007841056346), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.