STEINEL Multisensor AIR 4007841056346
STEINEL professional · Order number 4007841056346 · Multisensors
Download .knxprod Multisensor AIR 1.0 · 87 KB
Product
| Manufacturer | STEINEL professional |
|---|---|
| Product name | STEINEL Multisensor AIR |
| Order number | 4007841056346 |
| Hardware | Multisensor AIR |
| Medium | Twisted Pair |
| Bus current (mA) | 35 |
| Rail mounted | No |
| Registration | Registered · 2019-05-29 |
| Languages | de-DE, en-US, nl-NL |
| Catalog entry | M-008E_H-4007841056346-1_HP-7077-10-0D42_CI-4007841056346-1 |
| Fingerprint | 0D42 |
| SHA-256 | 1f7917dde83464c7d85dde7c8627bdf77522dd47ddc381c8d546a661a9ece636 |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: Multisensor AIR 1.0
| Application number | $7077 |
|---|---|
| Version | 1.0 |
| Mask version | MV-0705 (7.5) |
| KNX Data Secure | No |
| Minimum ETS version | 4.0 |
| Parameters | 172 |
| Group objects | 86 |
Group objects (86)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 74 | Switch HVAC | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 77 | Disable HVAC | ON/OFF | 1 Bit | 1.1 switch | CWT |
| 78 | Disable HVAC, status | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 80 | Light level measured, mixed light | Lux | 2 Bytes | 9.4 lux (Lux) | CRT |
| 83 | Temperature measured | 0 ... 40�C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 84 | External temperature | 0 ... 40�C | 2 Bytes | 9.1 temperature (°C) | CWT |
| 85 | Temperature limit value 1 | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 86 | Disable temperature limit value 1 | ON/OFF | 1 Bit | 1.1 switch | CWT |
| 87 | Disable temperature limit value 1, status | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 88 | Temperature limit value 2 | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 89 | Disable temperature limit value 2 | ON/OFF | 1 Bit | 1.1 switch | CWT |
| 90 | Disable temperature limit value 2, status | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 91 | Dewpoint temperature | 0 ... 40�C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 92 | Dewpoint alarm | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 93 | Humidity level measured | 0 ... 100% | 2 Bytes | 9.7 humidity (%) | CRT |
| 94 | External humidity | 0 ... 100% | 2 Bytes | 9.7 humidity (%) | CWT |
| 95 | Humidity limit value 1 | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 96 | Disable humidity limit value 1 | ON/OFF | 1 Bit | 1.1 switch | CWT |
| 97 | Disable humidity limit value 1, status | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 98 | Humidity limit value 2 | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 99 | Disable humidity limit value 2 | ON/OFF | 1 Bit | 1.1 switch | CWT |
| 100 | Disable humidity limit value 2, status | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 101 | Absolute air pressure | Pa | 4 Bytes | 14.58 pressure (Pa) | CRT |
| 102 | Relative air pressure | Pa | 4 Bytes | 14.58 pressure (Pa) | CRT |
| 103 | Air pressure limit value 1 | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 104 | Disable air pressure limit value 1 | ON/OFF | 1 Bit | 1.1 switch | CWT |
| 105 | Disable air pressure limit value 1, status | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 106 | Air pressure limit value 2 | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 107 | Disable air pressure limit value 2 | ON/OFF | 1 Bit | 1.1 switch | CWT |
| 108 | Disable air pressure limit value 2, status | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 109 | Comfort text | 14 bytes | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 110 | Comfort status | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 111 | Logic gate 1 output | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 112 | Logic gate 1 output | 0 ... 255 | 1 Byte | DPT.5 | CRT |
| 113 | Logic gate 1, input 1 | ON/OFF | 1 Bit | 1.1 switch | CWT |
| 114 | Logic gate 1, input 2 | ON/OFF | 1 Bit | 1.1 switch | CWT |
| 115 | Logic gate 1, input 3 | ON/OFF | 1 Bit | 1.1 switch | CWT |
| 116 | Logic gate 1, input 4 | ON/OFF | 1 Bit | 1.1 switch | CWT |
| 117 | Disable logic gate 1 | ON/OFF | 1 Bit | 1.1 switch | CWT |
| 118 | Disable logic gate 1, status | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 119 | Logic gate 2 output | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 120 | Logic gate 2 output | 0 ... 255 | 1 Byte | DPT.5 | CRT |
| 121 | Logic gate 2, input 1 | ON/OFF | 1 Bit | 1.1 switch | CWT |
| 122 | Logic gate 2, input 2 | ON/OFF | 1 Bit | 1.1 switch | CWT |
| 123 | Logic gate 2, input 3 | ON/OFF | 1 Bit | 1.1 switch | CWT |
| 124 | Logic gate 2, input 4 | ON/OFF | 1 Bit | 1.1 switch | CWT |
| 125 | Disable logic gate 2 | ON/OFF | 1 Bit | 1.1 switch | CWT |
| 126 | Disable logic gate 2, status | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 127 | CO2 level measured | 0 ... 2000 | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 128 | Disable CO2 limit value | ON/OFF | 1 Bit | 1.1 switch | CWT |
| 129 | Disable CO2 limit value, status | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 130 | CO2 limit value 1 output | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 131 | CO2 limit value 1 switching threshold | 0 ... 2000 | 2 Bytes | 9.8 parts/million (ppm) | CRWT |
| 132 | CO2 limit value 1 hysteresis | 0 ... 2000 | 2 Bytes | 9.8 parts/million (ppm) | CRWT |
| 133 | CO2 limit value 1 stay-on time | 0 ... 65535 s | 2 Bytes | 7.5 time (s) | CRWT |
| 134 | CO2 limit value 2 output | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 135 | CO2 limit value 2 switching threshold | 0 ... 2000 | 2 Bytes | 9.8 parts/million (ppm) | CRWT |
| 136 | CO2 limit value 2 hysteresis | 0 ... 2000 | 2 Bytes | 9.8 parts/million (ppm) | CRWT |
| 137 | CO2 limit value 2 stay-on time | 0 ... 65535 s | 2 Bytes | 7.5 time (s) | CRWT |
| 138 | CO2 limit value 3 output | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 139 | CO2 limit value 3 switching threshold | 0 ... 2000 | 2 Bytes | 9.8 parts/million (ppm) | CRWT |
| 140 | CO2 limit value 3 hysteresis | 0 ... 2000 | 2 Bytes | 9.8 parts/million (ppm) | CRWT |
| 141 | CO2 limit value 3 stay-on time | 0 ... 65535 s | 2 Bytes | 7.5 time (s) | CRWT |
| 142 | CO2 limit value 4 output | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 143 | CO2 limit value 4 switching threshold | 0 ... 2000 | 2 Bytes | 9.8 parts/million (ppm) | CRWT |
| 144 | CO2 limit value 4 hysteresis | 0 ... 2000 | 2 Bytes | 9.8 parts/million (ppm) | CRWT |
| 145 | CO2 limit value 4 stay-on time | 0 ... 65535 s | 2 Bytes | 7.5 time (s) | CRWT |
| 146 | VOC level measured | 0 ... 2000 | 2 Bytes | DPT.9 | CRT |
| 147 | Disable VOC limit value | ON/OFF | 1 Bit | 1.1 switch | CWT |
| 148 | Disable VOC limit value, status | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 149 | VOC limit value 1 output | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 150 | VOC limit value 1 switching threshold | 0 ... 2000 ppb | 2 Bytes | DPT.9 | CRWT |
| 151 | VOC limit value 1 hysteresis | 0 ... 2000 ppb | 2 Bytes | DPT.9 | CRWT |
| 152 | VOC limit value 1 stay-on time | 0 ... 65535 s | 2 Bytes | 7.5 time (s) | CRWT |
| 153 | VOC limit value 2 output | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 154 | VOC limit value 2 switching threshold | 0 ... 2000 ppb | 2 Bytes | DPT.9 | CRWT |
| 155 | VOC limit value 2 hysteresis | 0 ... 2000 ppb | 2 Bytes | DPT.9 | CRWT |
| 156 | VOC limit value 2 stay-on time | 0 ... 65535 s | 2 Bytes | 7.5 time (s) | CRWT |
| 157 | VOC limit value 3 output | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 158 | VOC limit value 3 switching threshold | 0 ... 2000 ppb | 2 Bytes | DPT.9 | CRWT |
| 159 | VOC limit value 3 hysteresis | 0 ... 2000 ppb | 2 Bytes | DPT.9 | CRWT |
| 160 | VOC limit value 3 stay-on time | 0 ... 65535 s | 2 Bytes | 7.5 time (s) | CRWT |
| 161 | VOC limit value 4 output | ON/OFF | 1 Bit | 1.1 switch | CRT |
| 162 | VOC limit value 4 switching threshold | 0 ... 2000 ppb | 2 Bytes | DPT.9 | CRWT |
| 163 | VOC limit value 4 hysteresis | 0 ... 2000 ppb | 2 Bytes | DPT.9 | CRWT |
| 164 | VOC limit value 4 stay-on time | 0 ... 65535 s | 2 Bytes | 7.5 time (s) | CRWT |
Parameters (78)
| Parameter | Type | Default |
|---|---|---|
| Temperature output | list | inactive |
| Humidity output | list | inactive |
| Dewpoint | list | inactive |
| HVAC output | list | inactive |
| CO2 output | list | inactive |
| VOC output | list | inactive |
| Air pressure | list | inactive |
| Comfort | list | inactive |
| Brightness output | list | inactive |
| Logic gate | list | inactive |
| Bluetooth | list | inactive |
| CO2 | list | inactive |
| CO2 switch ON value | unsignedInt 0…65535 | 800 |
| CO2 switch OFF value | unsignedInt 0…65535 | 400 |
| VOC | list | inactive |
| VOC switch ON value | unsignedInt 0…65535 | 800 |
| VOC switch OFF value | unsignedInt 0…65535 | 400 |
| Disable output | list | No |
| Behaviour on disabling | list | no action |
| Behaviour on enabling | list | Continue control |
| Send measured value cyclically or upon change | list | Change |
| Min. light-level change | unsignedInt 1…255 | 30 |
| Send measured value cyclically | time | 30 |
| Min. change | unsignedInt 1…255 | 10 |
| Send measured value cyclically | time | 60 |
| Sensor calibration | signedInt -128…127 | 0 |
| External temperature | list | inactive |
| External temperature weighting | unsignedInt 1…100 | 50 |
| Temperature limit value | unsignedInt 0…400 | 200 |
| Hysteresis limit value | unsignedInt 0…400 | 50 |
| Limit value, mode switching output | list | THR over = ON / THR - hyst. under = OFF |
| Limit value, send status cyclically | list | Do not send status cyclically |
| Interval for sending cyclically | time | 30 |
| Disable threshold | list | No |
| Send dewpoint temperature | list | Change |
| Lead, dewpoint alarm | unsignedInt 1…255 | 20 |
| Hysteresis, dewpoint alarm | unsignedInt 1…255 | 10 |
| External humidity | list | inactive |
| Weighting, external humidity | unsignedInt 1…100 | 50 |
| Limit value, humidity | unsignedInt 0…100 | 65 |
| Hysteresis limit value | unsignedInt 0…100 | 10 |
| Interval for sending cyclically | time | 10 |
| Local altitude | unsignedInt 0…5000 | 70 |
| Limit value, air pressure, input | list | Absolute air pressure |
| Air pressure limit value | unsignedInt 3000…13000 | 10200 |
| Hysteresis limit value | unsignedInt 0…11000 | 100 |
| Maximum temperature | unsignedInt 0…50 | 26 |
| Minimum temperature | unsignedInt 0…50 | 20 |
| Max. rel. humidity | unsignedInt 0…100 | 65 |
| Min. rel. humidity | unsignedInt 0…100 | 30 |
| Max. absolute humidity | unsignedInt 50…150 | 115 |
| Text message inside comfort field | text | behaglich |
| Text message outside comfort field | text | unbehaglich |
| Status, comfort level | list | comfortable = ON / uncomfortable = OFF |
| Type of logic operation | list | OR |
| Number of inputs | unsignedInt 1…4 | 2 |
| Type of output object | list | ON / OFF |
| Switching command for logic 0 | list | OFF |
| Switching command for logic 1 | list | ON |
| Value at logic 0 | unsignedInt 0…255 | 0 |
| Value at logic 1 | unsignedInt 0…255 | 255 |
| Send Behaviour, output | list | when logic changes |
| Disable logic gate | list | No |
| Switching command for logic 1 | list | OFF |
| Number, limit values | unsignedInt 1…4 | 1 |
| Limit value | unsignedInt 0…65535 | 1200 |
| Hysteresis limit value | unsignedInt 0…65535 | 600 |
| Stay-on time | time | 0 |
| Send status cyclically | list | ON |
| Limit value | unsignedInt 0…65535 | 1000 |
| Hysteresis limit value | unsignedInt 0…65535 | 500 |
| Limit value in ppm | unsignedInt 0…65535 | 800 |
| Hysteresis limit value | unsignedInt 0…65535 | 300 |
| Limit value in ppm | unsignedInt 0…65535 | 600 |
| Hysteresis limit value | unsignedInt 0…65535 | 200 |
| INIT_FlagAppSave | unsignedInt 0…65535 | 65535 |
| INIT_FlagEtsDownload | unsignedInt 0…65535 | 45054 |
| HW_TYPE | list | test |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Multisensor AIR 1.0 latest | $7077 | 0D42 | 2026-11-25 | 87 KB | Download |
About this file
This is the official ETS product database for the STEINEL professional STEINEL Multisensor AIR (4007841056346), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from STEINEL professional
- STEINEL True Presence Multisensor 4007841056353
- STEINEL Multisensor Aerosol 4007841079192
- STEINEL True Presence Multisensor Aerosol 4007841079208
- STEINEL True Presence Multisensor Black 4007841086060
- STEINEL IR Quattro KNX 4007841002701
- STEINEL IR Quattro HD KNX 4007841002763
- STEINEL HF 360 KNX 4007841002824
- STEINEL DUAL HF KNX 4007841002992
- STEINEL sensIQ S KNX 40078410040xx
- STEINEL iHF 3D KNX 40078410076xx
- STEINEL IR Quattro KNX 4007841008772
- STEINEL IR Quattro HD KNX 4007841008789