KNX Database
Siemens 5WG1 254-3EY02 Dual Sensor AP 254/02, Brightness/Temp./Switch

Dual Sensor AP 254/02, Brightness/Temp./Switch 5WG1 254-3EY02

Siemens · Order number 5WG1 254-3EY02 · Physical sensors › Brightness and Temperature

Download .knxprod 21 S2 Brightness and Temperature 909712 1.2 · 135 KB

Product

ManufacturerSiemens
Product nameDual Sensor AP 254/02, Brightness/Temp./Switch
Order number5WG1 254-3EY02
Product textDual Sensor AP 254/02
Hardware#Kombisensor AP 254/02
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationRegistered
Languagesen-US, de-DE
Catalog entryM-0001_H-hp.5F00229-1-O0048_HP-9097-12-44E4-O0048_CI-5WG1.20254.2D3EY02-1
Fingerprint44E4
SHA-256a6e15e301e04db3f34d75fdd560745d20b6a862ce939d16e1849024f80b77a06
First seen2026-11-25
Markets59 markets

Application program: 21 S2 Brightness and Temperature 909712 1.2

Application number$9097
Version1.2
Mask versionMV-0021 (2.1)
KNX Data SecureNo
Parameters348
Group objects121
Group objects (121)
NoNameFunctionSizeDPTFlags
0Brightness valueLux value (EIS 5)2 BytesCRT
1Temperature value°C value (EIS 5)2 BytesCRT
2Wind speedLux value (EIS 5)2 BytesCRT
3Rain sensorRain / no rain1 BitCRT
4Channel A.1 universal channelforced control2 BitCRT
4Channel A.1 universal channel8-bit value (EIS 6)1 ByteCRT
4Channel A.1 universal channelOn / Off1 BitCRT
4Channel A.1 brightness thresholdforced control2 BitCRT
4Channel A.1 brightness threshold8-bit value (EIS 6)1 ByteCRT
4Channel A.1 brightness thresholdOn / Off1 BitCRT
4Channel A safetysend1 BitCRT
4Channel A.1 temperature thresholdforced control2 BitCRT
4Channel A.1 temperature threshold8-bit value (EIS 6)1 ByteCRT
4Channel A.1 temperature thresholdOn / Off1 BitCRT
5Channel A.2 brightness threshold8-bit value (EIS 6)1 ByteCRT
5Channel A.2 brightness thresholdforced control2 BitCRT
5Channel A.2 brightness thresholdOn / Off1 BitCRT
5Channel A.2 universal channel8-bit value (EIS 6)1 ByteCRT
5Channel A.2 universal channelforced control2 BitCRT
5Channel A.2 universal channelOn / Off1 BitCRT
5Channel A.2 temperature threshold8-bit value (EIS 6)1 ByteCRT
5Channel A.2 temperature thresholdforced control2 BitCRT
5Channel A.2 temperature thresholdOn / Off1 BitCRT
6Channel A lock0=unlocked / 1=locked1 BitCRW
7Channel A brightness threshold0=unlocked / 1=locked1 ByteCRW
8Channel B.1 universal channel8-bit value (EIS 6)1 ByteCRT
8Channel B.1 universal channelforced control2 BitCRT
8Channel B.1 universal channelOn / Off1 BitCRT
8Channel B.1 brightness threshold8-bit value (EIS 6)1 ByteCRT
8Channel B.1 brightness thresholdforced control2 BitCRT
8Channel B.1 brightness thresholdOn / Off1 BitCRT
8Channel B.1 temperature threshold8-bit value (EIS 6)1 ByteCRT
8Channel B.1 temperature thresholdforced control2 BitCRT
8Channel B.1 temperature thresholdOn / Off1 BitCRT
8Channel B safetysend1 BitCRT
9Channel B.2 universal channel8-bit value (EIS 6)1 ByteCRT
9Channel B.2 universal channelforced control2 BitCRT
9Channel B.2 universal channelOn / Off1 BitCRT
9Channel B.2 brightness threshold8-bit value (EIS 6)1 ByteCRT
9Channel B.2 brightness thresholdforced control2 BitCRT
9Channel B.2 brightness thresholdOn / Off1 BitCRT
9Channel B.2 temperature threshold8-bit value (EIS 6)1 ByteCRT
9Channel B.2 temperature thresholdforced control2 BitCRT
9Channel B.2 temperature thresholdOn / Off1 BitCRT
10Channel B lock0=unlocked / 1=locked1 BitCRW
11Channel B brightness threshold0=unlocked / 1=locked1 ByteCRW
12Channel C solar protectionup / down1 BitCT
13Channel C BlindsHeight1 ByteCRT
13Channel C ShutterHeight1 ByteCRT
13Channel C send value8-bit value (EIS 6)1 ByteCRT
13Channel C Scene 1+2send1 BitCRT
14Channel C SlatsPosition1 ByteCRT
14Channel C Scene 3+4 send1 BitCRT
15Channel C Sun controlMorning=1 / Evening=01 BitCRW
16Channel C safety0=unlocked / 1=locked1 BitCRW
17Channel C brightness thresholds0=unlocked / 1=locked1 ByteCW
18Channel D.1 universal channel8-bit value (EIS 6)1 ByteCRT
18Channel D.1 universal channelforced control2 BitCRT
18Channel D.1 universal channelOn / Off1 BitCRT
18Channel D.1 brightness threshold8-bit value (EIS 6)1 ByteCRT
18Channel D.1 brightness thresholdforced control2 BitCRT
18Channel D.1 brightness thresholdOn / Off1 BitCRT
18Channel D.1 temperature threshold8-bit value (EIS 6)1 ByteCRT
18Channel D.1 temperature thresholdforced control2 BitCRT
18Channel D.1 temperature thresholdOn / Off1 BitCRT
18Channel D safetysend1 BitCRWT
19Channel D.2 universal channel8-bit value (EIS 6)1 ByteCRT
19Channel D.2 universal channelforced control2 BitCRT
19Channel D.2 universal channelOn / Off1 BitCRT
19Channel D.2 brightness threshold8-bit value (EIS 6)1 ByteCRT
19Channel D.2 brightness thresholdforced control2 BitCRT
19Channel D.2 brightness thresholdOn / Off1 BitCRT
19Channel D.2 temperature threshold8-bit value (EIS 6)1 ByteCRT
19Channel D.2 temperature thresholdforced control2 BitCRT
19Channel D.2 temperature thresholdOn / Off1 BitCRT
20Channel D lock0=unlocked / 1=locked1 BitCRW
21Channel D brightness threshold0=unlocked / 1=locked1 ByteCRW
22Channel E.1 universal channelforced control2 BitCRT
22Channel E.1 universal channelOn / Off1 BitCRT
22Channel E.1 universal channel8-bit value (EIS 6)1 ByteCRT
22Channel E.1 brightness thresholdforced control2 BitCRT
22Channel E.1 brightness thresholdOn / Off1 BitCRT
22Channel E.1 brightness threshold8-bit value (EIS 6)1 ByteCRT
22Channel E.1 temperature thresholdforced control2 BitCRT
22Channel E.1 temperature thresholdOn / Off1 BitCRT
22Channel E.1 temperature threshold8-bit value (EIS 6)1 ByteCRT
22Channel E safetysend1 BitCRT
23Channel E.2 universal channelforced control2 BitCRT
23Channel E.2 universal channelOn / Off1 BitCRT
23Channel E.2 universal channel8-bit value (EIS 6)1 ByteCRT
23Channel E.2 brightness thresholdforced control2 BitCRT
23Channel E.2 brightness thresholdOn / Off1 BitCRT
23Channel E.2 brightness threshold8-bit value (EIS 6)1 ByteCRT
23Channel E.2 temperature thresholdforced control2 BitCRT
23Channel E.2 temperature thresholdOn / Off1 BitCRT
23Channel E.2 temperature threshold8-bit value (EIS 6)1 ByteCRT
24Channel E lock0=unlocked / 1=locked1 BitCRW
25Channel E brightness threshold0=unlocked / 1=locked1 ByteCRW
26C6 up / downdrives up / down1 BitCT
27C6 Scene 1+2send1 BitCRT
27C6 ShutterHeight1 ByteCRT
27C6 Value8-bit value (EIS 6)1 ByteCRT
27C6 BlindsHeight1 ByteCRT
28C6 SlatsPosition1 ByteCRT
28C6 Scene 3+4send1 BitCRT
29C6 Sun controlMorning=1 / Evening=01 BitCRW
30C6 Safety0=unlocked / 1=locked1 BitCRW
31C6 remote brightness Val.0=unlocked / 1=locked2 BytesCRW
32C6 Teach in0=unlocked / 1=locked1 ByteCW
33C7 up / downdrives up / down1 BitCT
34C7 Scene 1+2send1 BitCRT
34C7 Value8-bit value (EIS 6)1 ByteCRT
34C7 ShutterHeight1 ByteCRT
34C7 BlindsHeight1 ByteCRT
35C7 SlatsPosition1 ByteCRT
35C7 Scene 3+4 send1 BitCRT
36C7 Sun controlMorning=1 / Evening=01 BitCRW
37C7 Safety0=unlocked / 1=locked1 BitCRW
38C7 remote bright. Val.0=unlocked / 1=locked2 BytesCRW
39C7 Teach in0=unlocked / 1=locked1 ByteCW
40Brightness thresholdsreport2 BytesCT
Parameters (108)
ParameterTypeDefault
Send wind speed value on change oflistnot due to a change
Send wind speed inlistm/s
Send wind speed value cyclicallylistdon't send cyclically
Send brightness value on change oflist30 %, but at least 1 Lux
Send brightness value cyclicallylistdon't send cyclically
Send temperature on change oflist1.0 °C
Send temperature cyclicallylistdon't send cyclically
Temperature offset in 1/10°C (-64 .. 64)signedInt -64…640
Send rain on change andlistno
Send rain cyclicallylistnot cyclically
Delay after rain stoplist5 minutes
Function of channel Alistbrightness sensor 2 .. 100 000 Lux
Function of channel Blisttemperature sensor
Function of channel Clistsun protection
Use more channels?listno
Function of channel Dlistuniversal channel
Function of channel Elistuniversal channel
Function of C6listsun protection
Function of C7listsun protection
Brightness conditionlistabove 10000 Lux
Hysteresis lightlist20 %, but at least 1 Lux
Delay on increasing brightnesslist3 minutes
Delay on decreasing brightnesslist10 minutes
AND windlistdon't care
Wind conditionlistdon't care
Safety telegram (ON) in the event of windlistabove 5 m/s (18 km/h)
Off-delay windlist3 minutes
AND temperaturelistabove 18°C
Temperature conditionlistabove 18°C
OR temperaturelistbelow 5°C
Hysteresis temperaturelist1.0 °C
AND rain condition (off-delay fixed 1 min.)listno rain
Rain conditionlistno rain
OR rain conditionlistrain
Delay rainlist1 minute
Telegram type channel A.1listswitching
If all conditions are metlistsend following telegram once
If the condition is metlistsend following telegram once
If safety condition is metlistsend following telegram once
Telegramlistswitch on
Telegramlistforced ON (down)
TelegramunsignedInt 0…255255
If not all conditions are metlistsend following telegram once
If the condition is not metlistsend following telegram once
If safety condition is not metlistsend following telegram once
Telegramlistforced OFF (up)
Telegramlistswitch off
TelegramunsignedInt 0…2550
Cycle time for channel A (if used)listevery 60 min.
Send safety telegram cyclicallylistevery 60 min.
Behaviour when setting the locklistignore lock
Behaviour when releasing the locklistupdate channel
Should a second telegram be sentlistno
Telegram type channel A.2listswitching
Telegram type channel B.1listswitching
Cycle time (if used)listevery 60 min.
Telegram type channel B.2listswitching
Light measurement throughlistinternal sensor
Twilight thresholdlist10 Lux
How many brightness thresholdslist3 thresholds
Brightness threshold 1list20000 Lux
Brightness threshold 2list30000 Lux
Brightness threshold 3list45000 Lux
Delay when brightness increaseslist3 minutes
Delay when brightness decreaseslist15 minutes
Telegram typelistblinds
Activation of sun controllistthrough object
Reaction to sun control ONlistmove up & sun control ON
Reaction to dawnlistmove up & sun control ON
Solar protection height from threshold 1list80%
Telegram between threshold 1 and 2listScene 2
Telegram above threshold 1listScene 2
Telegram between threshold 1 and 2unsignedInt 0…25510
Telegram above threshold 1unsignedInt 0…25510
Turn slats between threshold 1 and 2list40%
Turn slats above threshold 1list40%
Solar protection height between threshold 1 and 2list40%
Solar protection height above threshold 1list40%
Telegram between threshold 2 and 3listScene 3
Telegram above threshold 2listScene 3
Telegram between threshold 2 and 3unsignedInt 0…25520
Telegram above threshold 2unsignedInt 0…25520
Turn slats between threshold 2 and 3list60%
Turn slats above threshold 2list60%
Solar protection height between threshold 2 and 3list60%
Solar protection height above threshold 2list60%
Telegram above threshold 3listScene 4
Telegram above threshold 3unsignedInt 0…25530
Turn slats above threshold 3list75%
Solar protection height above threshold 3list75%
Reaction to sun control OFFlistsun control OFF & move up
Reaction to dusklistsun control OFF & move up
Safety check triggered bylistthrough object safety
Reaction to safety beginninglistno reaction
Reaction to safety endlistupdate position
Telegram type channel D.1listswitching
Telegram type channel D.2listswitching
Telegram type channel E.1listswitching
Telegram type channel E.2listswitching
Telegram typelistshutters / textile sun protection
Solar protection height between threshold 1 and 2list30%
Solar protection height above threshold 1list30%
Turn slats between threshold 1 and 2list30%
Turn slats above threshold 1list30%
Solar protection height above threshold 3list80%
Turn slats above threshold 3list80%
Temperature limit heating resistance with +30K offset 80 = 50°CunsignedInt 40…8070
Value $AA, so that Controller recognises that Application was downloadedunsignedInt 0…255170

Version history

ApplicationApp noFingerprintFirst seenSizeFile
21 S2 Brightness and Temperature 909712 1.2 latest$909744E42026-11-25135 KBDownload

About this file

This is the official ETS product database for the Siemens Dual Sensor AP 254/02, Brightness/Temp./Switch (5WG1 254-3EY02), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from Siemens

All Siemens products