KNX Database
Siemens 5WG1 257-3AB22 Weather Station GPS AP 257/22

Weather Station GPS AP 257/22 5WG1 257-3AB22

Siemens · Order number 5WG1 257-3AB22 · Physical sensors › Weather station with integrated sensors and GPS

Download .knxprod 0701 CO Weather Station 914201 0.1 · 162 KB

Product

ManufacturerSiemens
Product nameWeather Station GPS AP 257/22
Order number5WG1 257-3AB22
Hardware#Wetterzentrale AP 257/22
MediumTwisted Pair
Bus current (mA)9
Rail mountedNo
RegistrationRegistered
Languagesen-US, de-DE
Catalog entryM-0001_H-hp.5F00233-1_HP-9142-01-327B-O00C9_CI-5WG1.20257.2D3AB22-1
Fingerprint327B
SHA-25635062b20b4d8ca3b2c9a72aeb52ebdc86c810883f1e613d95435f1233e05b841
First seen2026-11-25
Markets59 markets

Application program: 0701 CO Weather Station 914201 0.1

Application number$9142
Version0.1
Mask versionMV-0701 (7.1)
KNX Data SecureNo
Parameters901
Group objects118
Group objects (118)
NoNameFunctionSizeDPTFlags
0GPS datesend3 BytesCRWT
1GPS timesend3 BytesCRWT
2GPS date and timequery1 BitCRW
3Datereceive3 BytesCRWTU
4Timereceive3 BytesCRWTU
58-bit scenerecall1 ByteCRT
6Wind sensor, FailureOn / Off1 BitCRT
7Wind speedActual value2 BytesCRT
8Max. wind speedsend8 BytesCRT
9Current max. wind speedquery1 BitCRW
10Wind, Limit value 1set2 BytesCRWTU
11Wind alarmOn / Off1 BitCRT
12Wind, Limit value 2set2 BytesCRWTU
13Wind, Message LV 2On / Off1 BitCRT
14Wind, Limit value 3set2 BytesCRWTU
15Wind, Message LV 3On / Off1 BitCRT
16BrightnessActual value2 BytesCRT
17Max. brightnesssend8 BytesCRT
18Current max. brightnessquery1 BitCRW
19Brightness, Limit value 1set2 BytesCRWTU
20SunshineOn / Off1 BitCRT
21Brightness, Limit value 2set2 BytesCRWTU
22Brightness, Message LV 2On / Off1 BitCRT
23Brightness, Limit value 3set2 BytesCRWTU
24Brightness, Message LV 3On / Off1 BitCRT
25Twilight, Limit value 1set2 BytesCRWTU
26DarknessOn / Off1 BitCRT
27Twilight, Limit value 2set2 BytesCRWTU
28Twilight, Message LV 2On / Off1 BitCRT
29Twilight, Limit value 3set2 BytesCRWTU
30Twilight, Message LV 3On / Off1 BitCRT
31Precipitation alarmOn / Off1 BitCRT
32Outside temperature sensor, FailureOn / Off1 BitCRT
33Outside temperatureActual value2 BytesCRT
34Min. outside temperaturesend8 BytesCRT
35Max. outside temperaturesend8 BytesCRT
36Current min. / max. outside temperaturequery1 BitCRW
37Temperature, Limit value 1set2 BytesCRWTU
38Frost alarmOn / Off1 BitCRT
39Temperature, Limit value 2set2 BytesCRWTU
40Temperature, Message LV 2On / Off1 BitCRT
41Temperature, Limit value 3set2 BytesCRWTU
42Temperature, Message LV 3On / Off1 BitCRT
43External alarm 1On / Off1 BitCRW
44SafetyOn / Off1 BitCRT
45Azimuthsend4 BytesCRT
46Elevationsend4 BytesCRT
47Façade 1, Controldisable =1 / enable =01 BitCRW
48Façade 1, SunshineOn / Off1 BitCRT
49Façade 1, Blind centrally UP / DOWNUp / Down1 BitCT
50Façade 1, Blind centrally DOWN1Down11 BitCT
51Façade 1, Blind centrally STEPUp / Down1 BitCT
52Façade 1, Blind position in %approach1 ByteCT
53Façade 1, Slats position in %approach1 ByteCT
54Façade 2, Controldisable =1 / enable =01 BitCRW
55Façade 2, SunshineOn / Off1 BitCRT
56Façade 2, Blind centrally UP / DOWNUp / Down1 BitCT
57Façade 2, Blind centrally DOWN1Down11 BitCT
58Façade 2, Blind centrally STEPUp / Down1 BitCT
59Façade 2, Blind position in %approach1 ByteCT
60Façade 2, Slats position in %approach1 ByteCT
61Façade 3, Controldisable =1 / enable =01 BitCRW
62Façade 3, SunshineOn / Off1 BitCRT
63Façade 3, Blind centrally UP / DOWNUp / Down1 BitCT
64Façade 3, Blind centrally DOWN1Down11 BitCT
65Façade 3, Blind centrally STEPUp / Down1 BitCT
66Façade 3, Blind position in %approach1 ByteCT
67Façade 3, Slats position in %approach1 ByteCT
68Façade 4, Controldisable =1 / enable =01 BitCRW
69Façade 4, SunshineOn / Off1 BitCRT
70Façade 4, Blind centrally UP / DOWNUp / Down1 BitCT
71Façade 4, Blind centrally DOWN1Down11 BitCT
72Façade 4, Blind centrally STEPUp / Down1 BitCT
73Façade 4, Blind position in %approach1 ByteCT
74Façade 4, Slats position in %approach1 ByteCT
75Façade 5, Controldisable =1 / enable =01 BitCRW
76Façade 5, SunshineOn / Off1 BitCRT
77Façade 5, Blind centrally UP / DOWNUp / Down1 BitCT
78Façade 5, Blind centrally DOWN1Down11 BitCT
79Façade 5, Blind centrally STEPUp / Down1 BitCT
80Façade 5, Blind position in %approach1 ByteCT
81Façade 5, Slats position in %approach1 ByteCT
82Façade 6, Controldisable =1 / enable =01 BitCRW
83Façade 6, SunshineOn / Off1 BitCRT
84Façade 6, Blind centrally UP / DOWNUp / Down1 BitCT
85Façade 6, Blind centrally DOWN1Down11 BitCT
86Façade 6, Blind centrally STEPUp / Down1 BitCT
87Façade 6, Blind position in %approach1 ByteCT
88Façade 6, Slats position in %approach1 ByteCT
89Façade 7, Controldisable =1 / enable =01 BitCRW
90Façade 7, SunshineOn / Off1 BitCRT
91Façade 7, Blind centrally UP / DOWNUp / Down1 BitCT
92Façade 7, Blind centrally DOWN1Down11 BitCT
93Façade 7, Blind centrally STEPUp / Down1 BitCT
94Façade 7, Blind position in %approach1 ByteCT
95Façade 7, Slats position in %approach1 ByteCT
96Façade 8, Controldisable =1 / enable =01 BitCRW
97Façade 8, SunshineOn / Off1 BitCRT
98Façade 8, Blind centrally UP / DOWNUp / Down1 BitCT
99Façade 8, Blind centrally DOWN1Down11 BitCT
100Façade 8, Blind centrally STEPUp / Down1 BitCT
101Façade 8, Blind position in %approach1 ByteCT
102Façade 8, Slats position in %approach1 ByteCT
103Output AND logic operation 10/11 BitCRT
104Output AND logic operation 20/11 BitCRT
105Output AND logic operation 30/11 BitCRT
106Output AND logic operation 40/11 BitCRT
107Output OR logic operation 10/11 BitCRT
108Output OR logic operation 20/11 BitCRT
109Output OR logic operation 30/11 BitCRT
110Output OR logic operation 40/11 BitCRT
111Failure GPS receptiontransmit1 BitCRT
112external alarm 2On / Off1 BitCRW
113external alarm 3On / Off1 BitCRW
114external alarm 4On / Off1 BitCRW
115External alarm 5On / Off1 BitCRW
116External alarm 6On / Off1 BitCRW
117External alarm 7On / Off1 BitCRW
Parameters (270)
ParameterTypeDefault
Countrylistother countries
Definition of time zone according tolistStandard
Summer / winter clock change atlistST: Sun. after March 25th WT: Sun. after Oct.25th
Rule for summer / winter clock changetext03257:0200+0100/10257:0200UTC+0100
east. longitude [degree, -180...+180]signedInt -180…1800
LocationlistStuttgart
LocationlistAberdeen
east. longitude [minutes, -59...+59]signedInt -59…590
LocationlistAdana
LocationlistAntwerpen
LocationlistAngers
LocationlistAthina
LocationlistAgrigento
LocationlistLuxemburg
LocationlistAmsterdam
LocationlistBergen
LocationlistBad Gastein
LocationlistCoimbra
LocationlistGälve
LocationlistAndermatt
LocationlistAlbacete
north. latitude [degree, -90...+90]signedInt -90…900
north. latitude [minutes, -59...+59]signedInt -59…590
Cycle time for cyclic transmission of metered valueslist10 Min.
Cycle time for cyclic transmission of logic objectslist10 Min.
Transmission delay time after bus and mains voltage recovery [in s]unsignedInt 1…105
Max. telegram rate [telegrams per second]unsignedInt 1…105
Date, timelistreceive via GPS
Send date / time cyclicallylistNo
Send GPS date and time upon requestlistat once
Failure GPS receptionlistdo not transmit
Wind speedlistexclude
Brightnesslistexclude
Twilightlistexclude
Precipitation alarmlistexclude
Outside temperaturelistexclude
SafetylistNo
Send position of the sunlistNo
Send azimuth and elevationliston change of value
Send after change by degreeunsignedInt 1…153
Façade controllistNo
Logic functionslistNo
Send metered value with dimensionlistm/s
Metering range, dimensionlist0 ... 125 km/h
Send metered valuelistNo
Metering range, dimensionlist0 ... 35 m/s
Send after change by %list5
Detection and storage of max. wind speedlistNo
Application of limit value 1listNo
Application of limit value 2listNo
Application of limit value 3listNo
Limit value adjustment vialistparameter
Dummy receipt of LVunsignedInt 0…101
Limit value 1 (in 0,1 m/s)unsignedInt 1…35070
Hysteresis 1 (in 0,1 m/s)unsignedInt 1…35030
ON delay (in seconds) if MV > LVunsignedInt 0…103
Action 1 after ON delaylistWind alarm = ON
Action 2 after ON delaylistnot to be applied
Scene numberunsignedInt 1…641
OFF delay (in minutes) if MV <= LV - Hyst.list15
Action 1 after OFF delaylistWind alarm = OFF
Action 2 after OFF delaylistnot to be applied
Send Wind alarmliston change of value
Cycle time Wind alarm (in minutes)unsignedInt 3…157
Limit value 2 (in 0,1 m/s)unsignedInt 1…35070
Hysteresis 2 (in 0,1 m/s)unsignedInt 1…35030
Action 1 after ON delaylistWind, Message LV 2 = ON
Action 1 after OFF delaylistWind, Message LV 2 = OFF
Send Wind, Message LV 2liston change of value
Cycle time Wind, Message LV 2 (in minutes)unsignedInt 3…157
Limit value 3 (in 0,1 m/s)unsignedInt 1…35070
Hysteresis 3 (in 0,1 m/s)unsignedInt 1…35030
Action 1 after ON delaylistWind, Message LV 3 = ON
Action 1 after OFF delaylistWind, Message LV 3 = OFF
Send Wind, Message LV 3liston change of value
Cycle time Wind, Message LV 3 (in minutes)unsignedInt 3…157
Metering range, dimensionlist0 ... 150 kLux
Detection and storage of max. brightnesslistNo
Limit value 1 (in kLux)unsignedInt 1…9970
Hysteresis 1 (in kLux)unsignedInt 1…9910
ON delay if MV > LVlist30 s
Action 1 after ON delaylistSunshine = ON
OFF delay 1 (in minutes) if MV <= LV - Hyst.unsignedInt 1…155
Action 1 after OFF delay 1listSunshine = OFF
Action 2 after OFF delay 1listnot to be applied
Send Sunshineliston change of value
Cycle time Sunshine (in minutes)unsignedInt 3…157
Limit value 2 (in kLux)unsignedInt 1…9970
Hysteresis 2 (in kLux)unsignedInt 1…9910
Action 1 after ON delaylistBrightness, Message LV 2 = ON
Action 1 after OFF delay 1listBrightness, Message LV 2 = OFF
Brightness, send Message LV 2liston change of value
Cycle time Brightness, Message LV 2 (in minutes)unsignedInt 3…157
Limit value 3 (in kLux)unsignedInt 1…9970
Hysteresis 3 (in kLux)unsignedInt 1…9910
Action 1 after ON delaylistBrightness, Message LV 3 = ON
Action 1 after OFF delay 1listBrightness, Message LV 3 = OFF
Brightness, send Message LV 3liston change of value
Cycle time Brightness, Message LV 3 (in minutes)unsignedInt 3…157
Limit value 1 (in Lux)signedInt 1…1000200
Hysteresis 1 (in Lux)unsignedInt 1…9910
ON delay if MV < LVlist5 Min.
Action 1 after ON delaylistDarkness = ON
OFF delay (in minutes) if MV >= LV + Hyst.unsignedInt 1…1515
Action 1 after OFF delaylistDarkness = OFF
Send Darknessliston change of value
Cycle time Darkness (in minutes)unsignedInt 3…157
Limit value 2 (in Lux)signedInt 1…1000200
Hysteresis 2 (in Lux)unsignedInt 1…9910
Action 1 after ON delaylistTwilight, Message LV 2 = ON
Action 1 after OFF delaylistTwilight, Message LV 2 = OFF
Send Twilight, Message LV 2liston change of value
Cycle time Twilight, Message LV 2 (in minutes)unsignedInt 3…157
Limit value 3 (in Lux)signedInt 1…1000200
Hysteresis 3 (in Lux)unsignedInt 1…9910
Action 1 after ON delaylistTwilight, Message LV 3 = ON
Action 1 after OFF delaylistTwilight, Message LV 3 = OFF
Send Twilight, Message LV 3liston change of value
Send precipitation alarm ON / OFFliston change of value
Cycle time precipitation alarm (in minutes)unsignedInt 3…157
Action if precipitation alarm = ONlistnot to be applied
Action if precipitation alarm = OFFlistnot to be applied
Send metered value with dimensionlist°C
Metering range, dimensionlist-22 ... +122 °F
Metering range, dimensionlist-30 ... +50 °C
Temperature offset (in 0.1 K)signedInt -50…500
Send after change bylist1,0 K
Detection and storage of min. / max. temperaturelistNo
Limit value 1 (in 0,5 K)signedInt -60…1002
Hysteresis 1 (in 0,5 K)unsignedInt 1…206
Frost alarmlistON if MV<LV / OFF if MV>=LV+Hyst.
ON-delaylist10 Min.
Action if Frost alarm = ONlistnot to be applied
OFF-delaylist10 Min.
Action if Frost alarm = OFFlistnot to be applied
Send Frost alarmliston change of value
Cycle time Frost alarm (in minutes)unsignedInt 3…157
Limit value 2 (in 0,5 K)signedInt -60…1002
Hysteresis 2 (in 0,5 K)unsignedInt 1…206
Temperature, Message LV 2listON if MV<LV / OFF if MV>=LV+Hyst.
Action if Temperature, message LV 2 = ONlistnot to be applied
Action if Temperature, message LV 2 = OFFlistnot to be applied
Send Temperature, Message LV 2liston change of value
Cycle time Temperature, Message LV 2 (in minutes)unsignedInt 3…157
Limit value 3 (in 0,5 K)signedInt -60…1002
Hysteresis 3 (in 0,5 K)unsignedInt 1…206
Temperature, Message LV 3listON if MV<LV / OFF if MV>=LV+Hyst.
Action if Temperature, message LV 3 = ONlistnot to be applied
Action if Temperature, message LV 3 = OFFlistnot to be applied
Cycle time Temperature, Message LV 3 (in minutes)unsignedInt 3…157
Add object External alarmlist1
If:listWind alarm = ON
ORlistnot to be applied
ORlistPrecipitation alarm = ON
ORlistFrost alarm = ON
then:listSafety = ON
Send Safetyliston change of value
Cycle time Safety (in minutes)unsignedInt 3…157
Façade 1listto be used
Façade 2listto be used
Façade 3listto be used
Façade 4listto be used
Façade 5listnot to be used
Façade 6listnot to be used
Façade 7listnot to be used
Façade 8listnot to be used
Orientation (North=0°, E=90°, S=180°, W=270°)signedInt 0…3590
Inclination (against base point of vertical)signedInt -89…600
Blind angle horizontalunsignedInt 2…252
Blind angle verticalunsignedInt 2…452
Shading control vialistBrightness, Limit value 1 (Sunshine)
OFF delay 2 in minutes if Brightness, Message LV = OFFunsignedInt 1…1510
Shadow edge trackinglistNo
Height of window in cm:signedInt 1…1000150
Sunshine range inside the room at bottom of window in cm:unsignedInt 1…5020
min. variation in cm:unsignedInt 1…5010
Sun tracking control of slatslistNo
Type of slatslistHorizontal slats
Width of slats in mm:signedInt 1…100050
Interspace between slats in mm:signedInt 1…100050
Slats angle in degrees after position command 100%unsignedInt 0…1800
Slats angle in degrees after position command 0%unsignedInt 0…18090
min. variation of angle in degrees for transmission of a new slats positiunsignedInt 1…9020
Façade 1, send Sunshineliston change of value
Cycle time façade 1 in minutes:unsignedInt 5…6015
Action 1listFaçade 1, Sunshine = ON
Action 2listSend Slats position in %
Action 2listSend blind position in %
Action 2listSend blind + slats position in %
Send slats postion in %liston change of value
Action 2listnot to be applied
Send blind position in %liston change of value
Send blind and slats positionliston change of value
Cycle time Slats position façade 1 in minutes:unsignedInt 5…6015
Blind position in %unsignedInt 50…100100
Cycle time Blind position façade 1 in minutes:unsignedInt 5…6015
Cycle time Blind / slats position façade 1 in minutes:unsignedInt 5…6015
Slats position in %unsignedInt 50…100100
Actionlistnot to be applied
Number of stepsunsignedInt 1…73
Slats position in %unsignedInt 0…500
Action 1listnot to be applied
Blind position in %unsignedInt 0…1000
Slats position in %unsignedInt 0…1000
Action 2listFaçade 1, Sunshine = OFF
Façade 2, send Sunshineliston change of value
Cycle time façade 2 in minutes:unsignedInt 5…6015
Action 1listFaçade 2, Sunshine = ON
Cycle time Blind / slats position façade 2 in minutes:unsignedInt 5…6015
Cycle time Slats position façade 2 in minutes:unsignedInt 5…6015
Cycle time Blind position façade 2 in minutes:unsignedInt 5…6015
Action 2listFaçade 2, Sunshine = OFF
Façade 3, send Sunshineliston change of value
Cycle time façade 3 in minutes:unsignedInt 5…6015
Action 1listFaçade 3, Sunshine = ON
Cycle time Slats position façade 3 in minutes:unsignedInt 5…6015
Cycle time Blind position façade 3 in minutes:unsignedInt 5…6015
Cycle time Blind / slats position façade 3 in minutes:unsignedInt 5…6015
Action 2listFaçade 3, Sunshine = OFF
Façade 4, send Sunshineliston change of value
Cycle time façade 4 in minutes:unsignedInt 5…6015
Action 1listFaçade 4, Sunshine = ON
Cycle time Slats position façade 4 in minutes:unsignedInt 5…6015
Cycle time Blind position façade 4 in minutes:unsignedInt 5…6015
Cycle time Blind / slats position façade 4 in minutes:unsignedInt 5…6015
Action 2listFaçade 4, Sunshine = OFF
Façade 5, send Sunshineliston change of value
Cycle time façade 5 in minutes:unsignedInt 5…6015
Action 1listFaçade 5, Sunshine = ON
Cycle time Slats position façade 5 in minutes:unsignedInt 5…6015
Cycle time Blind position façade 5 in minutes:unsignedInt 5…6015
Cycle time Blind / slats position façade 5 in minutes:unsignedInt 5…6015
Action 2listFaçade 5, Sunshine = OFF
Façade 6, send Sunshineliston change of value
Cycle time façade 6 in minutes:unsignedInt 5…6015
Action 1listFaçade 6, Sunshine = ON
Cycle time Slats position façade 6 in minutes:unsignedInt 5…6015
Cycle time Blind position façade 6 in minutes:unsignedInt 5…6015
Cycle time Blind / slats position façade 6 in minutes:unsignedInt 5…6015
Action 2listFaçade 6, Sunshine = OFF
Façade 7, send Sunshineliston change of value
Cycle time façade 7 in minutes:unsignedInt 5…6015
Action 1listFaçade 7, Sunshine = ON
Cycle time Slats position façade 7 in minutes:unsignedInt 5…6015
Cycle time Blind position façade 7 in minutes:unsignedInt 5…6015
Cycle time Blind / slats position façade 7 in minutes:unsignedInt 5…6015
Action 2listFaçade 7, Sunshine = OFF
Façade 8, send Sunshineliston change of value
Cycle time façade 8 in minutes:unsignedInt 5…6015
Action 1listFaçade 8, Sunshine = ON
Cycle time Slats position façade 8 in minutes:unsignedInt 5…6015
Cycle time Blind position façade 8 in minutes:unsignedInt 5…6015
Cycle time Blind / slats position façade 8 in minutes:unsignedInt 5…6015
Action 2listFaçade 8, Sunshine = OFF
AND logic operation 1listinactive
AND logic operation 2listinactive
AND logic operation 3listinactive
AND logic operation 4listinactive
OR logic operation 1listinactive
OR logic operation 2listinactive
OR logic operation 3listinactive
OR logic operation 4listinactive
1st inputlistnot used
2nd inputlistnot used
3rd inputlistnot used
4th inputlistnot used
Action 1: Object value =list1
Action 2:listnot to be applied
Action 1: Object value =list0
Send logic objectliston change of value

Version history

ApplicationApp noFingerprintFirst seenSizeFile
0701 CO Weather Station 914201 0.1 latest$9142327B2026-11-25162 KBDownload

About this file

This is the official ETS product database for the Siemens Weather Station GPS AP 257/22 (5WG1 257-3AB22), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from Siemens

All Siemens products