Dual Sensor AP 254/02, Brightness/Temp./Switch 5WG1 254-3EY02
Siemens · Order number 5WG1 254-3EY02 · Physical sensors › Brightness and Temperature
Download .knxprod 21 S2 Brightness and Temperature 909712 1.2 · 135 KB
Product
| Manufacturer | Siemens |
|---|---|
| Product name | Dual Sensor AP 254/02, Brightness/Temp./Switch |
| Order number | 5WG1 254-3EY02 |
| Product text | Dual Sensor AP 254/02 |
| Hardware | #Kombisensor AP 254/02 |
| Medium | Twisted Pair |
| Bus current (mA) | 10 |
| Rail mounted | No |
| Registration | Registered |
| Languages | en-US, de-DE |
| Catalog entry | M-0001_H-hp.5F00229-1-O0048_HP-9097-12-44E4-O0048_CI-5WG1.20254.2D3EY02-1 |
| Fingerprint | 44E4 |
| SHA-256 | a6e15e301e04db3f34d75fdd560745d20b6a862ce939d16e1849024f80b77a06 |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: 21 S2 Brightness and Temperature 909712 1.2
| Application number | $9097 |
|---|---|
| Version | 1.2 |
| Mask version | MV-0021 (2.1) |
| KNX Data Secure | No |
| Parameters | 348 |
| Group objects | 121 |
Group objects (121)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Brightness value | Lux value (EIS 5) | 2 Bytes | CRT | |
| 1 | Temperature value | °C value (EIS 5) | 2 Bytes | CRT | |
| 2 | Wind speed | Lux value (EIS 5) | 2 Bytes | CRT | |
| 3 | Rain sensor | Rain / no rain | 1 Bit | CRT | |
| 4 | Channel A.1 universal channel | forced control | 2 Bit | CRT | |
| 4 | Channel A.1 universal channel | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 4 | Channel A.1 universal channel | On / Off | 1 Bit | CRT | |
| 4 | Channel A.1 brightness threshold | forced control | 2 Bit | CRT | |
| 4 | Channel A.1 brightness threshold | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 4 | Channel A.1 brightness threshold | On / Off | 1 Bit | CRT | |
| 4 | Channel A safety | send | 1 Bit | CRT | |
| 4 | Channel A.1 temperature threshold | forced control | 2 Bit | CRT | |
| 4 | Channel A.1 temperature threshold | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 4 | Channel A.1 temperature threshold | On / Off | 1 Bit | CRT | |
| 5 | Channel A.2 brightness threshold | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 5 | Channel A.2 brightness threshold | forced control | 2 Bit | CRT | |
| 5 | Channel A.2 brightness threshold | On / Off | 1 Bit | CRT | |
| 5 | Channel A.2 universal channel | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 5 | Channel A.2 universal channel | forced control | 2 Bit | CRT | |
| 5 | Channel A.2 universal channel | On / Off | 1 Bit | CRT | |
| 5 | Channel A.2 temperature threshold | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 5 | Channel A.2 temperature threshold | forced control | 2 Bit | CRT | |
| 5 | Channel A.2 temperature threshold | On / Off | 1 Bit | CRT | |
| 6 | Channel A lock | 0=unlocked / 1=locked | 1 Bit | CRW | |
| 7 | Channel A brightness threshold | 0=unlocked / 1=locked | 1 Byte | CRW | |
| 8 | Channel B.1 universal channel | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 8 | Channel B.1 universal channel | forced control | 2 Bit | CRT | |
| 8 | Channel B.1 universal channel | On / Off | 1 Bit | CRT | |
| 8 | Channel B.1 brightness threshold | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 8 | Channel B.1 brightness threshold | forced control | 2 Bit | CRT | |
| 8 | Channel B.1 brightness threshold | On / Off | 1 Bit | CRT | |
| 8 | Channel B.1 temperature threshold | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 8 | Channel B.1 temperature threshold | forced control | 2 Bit | CRT | |
| 8 | Channel B.1 temperature threshold | On / Off | 1 Bit | CRT | |
| 8 | Channel B safety | send | 1 Bit | CRT | |
| 9 | Channel B.2 universal channel | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 9 | Channel B.2 universal channel | forced control | 2 Bit | CRT | |
| 9 | Channel B.2 universal channel | On / Off | 1 Bit | CRT | |
| 9 | Channel B.2 brightness threshold | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 9 | Channel B.2 brightness threshold | forced control | 2 Bit | CRT | |
| 9 | Channel B.2 brightness threshold | On / Off | 1 Bit | CRT | |
| 9 | Channel B.2 temperature threshold | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 9 | Channel B.2 temperature threshold | forced control | 2 Bit | CRT | |
| 9 | Channel B.2 temperature threshold | On / Off | 1 Bit | CRT | |
| 10 | Channel B lock | 0=unlocked / 1=locked | 1 Bit | CRW | |
| 11 | Channel B brightness threshold | 0=unlocked / 1=locked | 1 Byte | CRW | |
| 12 | Channel C solar protection | up / down | 1 Bit | CT | |
| 13 | Channel C Blinds | Height | 1 Byte | CRT | |
| 13 | Channel C Shutter | Height | 1 Byte | CRT | |
| 13 | Channel C send value | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 13 | Channel C Scene 1+2 | send | 1 Bit | CRT | |
| 14 | Channel C Slats | Position | 1 Byte | CRT | |
| 14 | Channel C Scene 3+4 | send | 1 Bit | CRT | |
| 15 | Channel C Sun control | Morning=1 / Evening=0 | 1 Bit | CRW | |
| 16 | Channel C safety | 0=unlocked / 1=locked | 1 Bit | CRW | |
| 17 | Channel C brightness thresholds | 0=unlocked / 1=locked | 1 Byte | CW | |
| 18 | Channel D.1 universal channel | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 18 | Channel D.1 universal channel | forced control | 2 Bit | CRT | |
| 18 | Channel D.1 universal channel | On / Off | 1 Bit | CRT | |
| 18 | Channel D.1 brightness threshold | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 18 | Channel D.1 brightness threshold | forced control | 2 Bit | CRT | |
| 18 | Channel D.1 brightness threshold | On / Off | 1 Bit | CRT | |
| 18 | Channel D.1 temperature threshold | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 18 | Channel D.1 temperature threshold | forced control | 2 Bit | CRT | |
| 18 | Channel D.1 temperature threshold | On / Off | 1 Bit | CRT | |
| 18 | Channel D safety | send | 1 Bit | CRWT | |
| 19 | Channel D.2 universal channel | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 19 | Channel D.2 universal channel | forced control | 2 Bit | CRT | |
| 19 | Channel D.2 universal channel | On / Off | 1 Bit | CRT | |
| 19 | Channel D.2 brightness threshold | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 19 | Channel D.2 brightness threshold | forced control | 2 Bit | CRT | |
| 19 | Channel D.2 brightness threshold | On / Off | 1 Bit | CRT | |
| 19 | Channel D.2 temperature threshold | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 19 | Channel D.2 temperature threshold | forced control | 2 Bit | CRT | |
| 19 | Channel D.2 temperature threshold | On / Off | 1 Bit | CRT | |
| 20 | Channel D lock | 0=unlocked / 1=locked | 1 Bit | CRW | |
| 21 | Channel D brightness threshold | 0=unlocked / 1=locked | 1 Byte | CRW | |
| 22 | Channel E.1 universal channel | forced control | 2 Bit | CRT | |
| 22 | Channel E.1 universal channel | On / Off | 1 Bit | CRT | |
| 22 | Channel E.1 universal channel | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 22 | Channel E.1 brightness threshold | forced control | 2 Bit | CRT | |
| 22 | Channel E.1 brightness threshold | On / Off | 1 Bit | CRT | |
| 22 | Channel E.1 brightness threshold | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 22 | Channel E.1 temperature threshold | forced control | 2 Bit | CRT | |
| 22 | Channel E.1 temperature threshold | On / Off | 1 Bit | CRT | |
| 22 | Channel E.1 temperature threshold | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 22 | Channel E safety | send | 1 Bit | CRT | |
| 23 | Channel E.2 universal channel | forced control | 2 Bit | CRT | |
| 23 | Channel E.2 universal channel | On / Off | 1 Bit | CRT | |
| 23 | Channel E.2 universal channel | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 23 | Channel E.2 brightness threshold | forced control | 2 Bit | CRT | |
| 23 | Channel E.2 brightness threshold | On / Off | 1 Bit | CRT | |
| 23 | Channel E.2 brightness threshold | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 23 | Channel E.2 temperature threshold | forced control | 2 Bit | CRT | |
| 23 | Channel E.2 temperature threshold | On / Off | 1 Bit | CRT | |
| 23 | Channel E.2 temperature threshold | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 24 | Channel E lock | 0=unlocked / 1=locked | 1 Bit | CRW | |
| 25 | Channel E brightness threshold | 0=unlocked / 1=locked | 1 Byte | CRW | |
| 26 | C6 up / down | drives up / down | 1 Bit | CT | |
| 27 | C6 Scene 1+2 | send | 1 Bit | CRT | |
| 27 | C6 Shutter | Height | 1 Byte | CRT | |
| 27 | C6 Value | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 27 | C6 Blinds | Height | 1 Byte | CRT | |
| 28 | C6 Slats | Position | 1 Byte | CRT | |
| 28 | C6 Scene 3+4 | send | 1 Bit | CRT | |
| 29 | C6 Sun control | Morning=1 / Evening=0 | 1 Bit | CRW | |
| 30 | C6 Safety | 0=unlocked / 1=locked | 1 Bit | CRW | |
| 31 | C6 remote brightness Val. | 0=unlocked / 1=locked | 2 Bytes | CRW | |
| 32 | C6 Teach in | 0=unlocked / 1=locked | 1 Byte | CW | |
| 33 | C7 up / down | drives up / down | 1 Bit | CT | |
| 34 | C7 Scene 1+2 | send | 1 Bit | CRT | |
| 34 | C7 Value | 8-bit value (EIS 6) | 1 Byte | CRT | |
| 34 | C7 Shutter | Height | 1 Byte | CRT | |
| 34 | C7 Blinds | Height | 1 Byte | CRT | |
| 35 | C7 Slats | Position | 1 Byte | CRT | |
| 35 | C7 Scene 3+4 | send | 1 Bit | CRT | |
| 36 | C7 Sun control | Morning=1 / Evening=0 | 1 Bit | CRW | |
| 37 | C7 Safety | 0=unlocked / 1=locked | 1 Bit | CRW | |
| 38 | C7 remote bright. Val. | 0=unlocked / 1=locked | 2 Bytes | CRW | |
| 39 | C7 Teach in | 0=unlocked / 1=locked | 1 Byte | CW | |
| 40 | Brightness thresholds | report | 2 Bytes | CT |
Parameters (108)
| Parameter | Type | Default |
|---|---|---|
| Send wind speed value on change of | list | not due to a change |
| Send wind speed in | list | m/s |
| Send wind speed value cyclically | list | don't send cyclically |
| Send brightness value on change of | list | 30 %, but at least 1 Lux |
| Send brightness value cyclically | list | don't send cyclically |
| Send temperature on change of | list | 1.0 °C |
| Send temperature cyclically | list | don't send cyclically |
| Temperature offset in 1/10°C (-64 .. 64) | signedInt -64…64 | 0 |
| Send rain on change and | list | no |
| Send rain cyclically | list | not cyclically |
| Delay after rain stop | list | 5 minutes |
| Function of channel A | list | brightness sensor 2 .. 100 000 Lux |
| Function of channel B | list | temperature sensor |
| Function of channel C | list | sun protection |
| Use more channels? | list | no |
| Function of channel D | list | universal channel |
| Function of channel E | list | universal channel |
| Function of C6 | list | sun protection |
| Function of C7 | list | sun protection |
| Brightness condition | list | above 10000 Lux |
| Hysteresis light | list | 20 %, but at least 1 Lux |
| Delay on increasing brightness | list | 3 minutes |
| Delay on decreasing brightness | list | 10 minutes |
| AND wind | list | don't care |
| Wind condition | list | don't care |
| Safety telegram (ON) in the event of wind | list | above 5 m/s (18 km/h) |
| Off-delay wind | list | 3 minutes |
| AND temperature | list | above 18°C |
| Temperature condition | list | above 18°C |
| OR temperature | list | below 5°C |
| Hysteresis temperature | list | 1.0 °C |
| AND rain condition (off-delay fixed 1 min.) | list | no rain |
| Rain condition | list | no rain |
| OR rain condition | list | rain |
| Delay rain | list | 1 minute |
| Telegram type channel A.1 | list | switching |
| If all conditions are met | list | send following telegram once |
| If the condition is met | list | send following telegram once |
| If safety condition is met | list | send following telegram once |
| Telegram | list | switch on |
| Telegram | list | forced ON (down) |
| Telegram | unsignedInt 0…255 | 255 |
| If not all conditions are met | list | send following telegram once |
| If the condition is not met | list | send following telegram once |
| If safety condition is not met | list | send following telegram once |
| Telegram | list | forced OFF (up) |
| Telegram | list | switch off |
| Telegram | unsignedInt 0…255 | 0 |
| Cycle time for channel A (if used) | list | every 60 min. |
| Send safety telegram cyclically | list | every 60 min. |
| Behaviour when setting the lock | list | ignore lock |
| Behaviour when releasing the lock | list | update channel |
| Should a second telegram be sent | list | no |
| Telegram type channel A.2 | list | switching |
| Telegram type channel B.1 | list | switching |
| Cycle time (if used) | list | every 60 min. |
| Telegram type channel B.2 | list | switching |
| Light measurement through | list | internal sensor |
| Twilight threshold | list | 10 Lux |
| How many brightness thresholds | list | 3 thresholds |
| Brightness threshold 1 | list | 20000 Lux |
| Brightness threshold 2 | list | 30000 Lux |
| Brightness threshold 3 | list | 45000 Lux |
| Delay when brightness increases | list | 3 minutes |
| Delay when brightness decreases | list | 15 minutes |
| Telegram type | list | blinds |
| Activation of sun control | list | through object |
| Reaction to sun control ON | list | move up & sun control ON |
| Reaction to dawn | list | move up & sun control ON |
| Solar protection height from threshold 1 | list | 80% |
| Telegram between threshold 1 and 2 | list | Scene 2 |
| Telegram above threshold 1 | list | Scene 2 |
| Telegram between threshold 1 and 2 | unsignedInt 0…255 | 10 |
| Telegram above threshold 1 | unsignedInt 0…255 | 10 |
| Turn slats between threshold 1 and 2 | list | 40% |
| Turn slats above threshold 1 | list | 40% |
| Solar protection height between threshold 1 and 2 | list | 40% |
| Solar protection height above threshold 1 | list | 40% |
| Telegram between threshold 2 and 3 | list | Scene 3 |
| Telegram above threshold 2 | list | Scene 3 |
| Telegram between threshold 2 and 3 | unsignedInt 0…255 | 20 |
| Telegram above threshold 2 | unsignedInt 0…255 | 20 |
| Turn slats between threshold 2 and 3 | list | 60% |
| Turn slats above threshold 2 | list | 60% |
| Solar protection height between threshold 2 and 3 | list | 60% |
| Solar protection height above threshold 2 | list | 60% |
| Telegram above threshold 3 | list | Scene 4 |
| Telegram above threshold 3 | unsignedInt 0…255 | 30 |
| Turn slats above threshold 3 | list | 75% |
| Solar protection height above threshold 3 | list | 75% |
| Reaction to sun control OFF | list | sun control OFF & move up |
| Reaction to dusk | list | sun control OFF & move up |
| Safety check triggered by | list | through object safety |
| Reaction to safety beginning | list | no reaction |
| Reaction to safety end | list | update position |
| Telegram type channel D.1 | list | switching |
| Telegram type channel D.2 | list | switching |
| Telegram type channel E.1 | list | switching |
| Telegram type channel E.2 | list | switching |
| Telegram type | list | shutters / textile sun protection |
| Solar protection height between threshold 1 and 2 | list | 30% |
| Solar protection height above threshold 1 | list | 30% |
| Turn slats between threshold 1 and 2 | list | 30% |
| Turn slats above threshold 1 | list | 30% |
| Solar protection height above threshold 3 | list | 80% |
| Turn slats above threshold 3 | list | 80% |
| Temperature limit heating resistance with +30K offset 80 = 50°C | unsignedInt 40…80 | 70 |
| Value $AA, so that Controller recognises that Application was downloaded | unsignedInt 0…255 | 170 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| 21 S2 Brightness and Temperature 909712 1.2 latest | $9097 | 44E4 | 2026-11-25 | 135 KB | Download |
About this file
This is the official ETS product database for the Siemens Dual Sensor AP 254/02, Brightness/Temp./Switch (5WG1 254-3EY02), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Siemens
- Brightness Controller UP 255D21 5WG1 255-2DB21
- Weather Station GPS AP 257/22 5WG1 257-3AB22
- Weather station AP 257/51 5WG1 257-3AB51
- Weather station GPS AP 257/61 5WG1 257-3AB61
- Presence Detector, Brightness Sensor UP 258D12 5WG1 258-2DB12
- Presence Detector WIDE UP 258D31 5WG1 258-2DB31
- Presence Detector WIDE pro UP 258D41 5WG1 258-2DB41
- Presence Detector WIDE multi UP 258D51 5WG1 258-2DB51
- Presence Detector WIDE DualTech UP 258D61 5WG1 258-2DB61
- Presence Detector, Constant Controller UP 258E22 5WG1 258-2EB22
- Motion sensor WALL UP 251/11 5WG1251-2AB11
- Bus Transceiver Module UP 117/12 5WG1 117-2AB12