Siemens 5WG1 237-2KB_1 Room Temperature Controller UP237KB_1

Room Temperature Controller UP237KB_1 5WG1 237-2KB_1

Siemens · Order number 5WG1 237-2KB_1 · Heating, Air conditioning, Ventilation › Thermostat › Wall Mounted Devices › UP 254KB_3, UP237KB_1 DELTA style / i-system

For heating and cooling

Download .knxprod 0705 CO Room Temperature Controller H+C 803002 0.2 · 100 KB

Product

ManufacturerSiemens
Product nameRoom Temperature Controller UP237KB_1
Order number5WG1 237-2KB_1
Hardware#Raumtemperaturregler Heizen/Kühlen UP 2__KB
MediumTwisted Pair
Bus current (mA)14
Rail mountedNo
RegistrationRegistered · 2012-01-12
Languagesen-US, de-DE
Catalog entryM-0001_H-hp.5F00268-2_HP-8030-02-DF56_CI-5WG1.20237.2D2KB.5F1-1
FingerprintDF56
SHA-25614e3a5c31cb9efd0b1db926b12505ba3cf459af79606bed2f8616d3352c5de77
First seen2026-11-25
Markets59 markets

Application program: 0705 CO Room Temperature Controller H+C 803002 0.2

Application number$8030
Version0.2
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version3.0f
Parameters219
Group objects36
Group objects (36)
NoNameFunctionSizeDPTFlags
0Temperature, actual value internal sensor (°C)send2 Bytes9.1 temperature (°C)CRWTU
1Temperature, actual value internal sensor (°C)receive / send2 Bytes9.1 temperature (°C)CRWTU
2Temperature, actual value ext. sensor (°C)send2 Bytes9.1 temperature (°C)CRTU
3Base setpoint (°C)receive / send2 Bytes9.1 temperature (°C)CRWTU
4Setpoint adjustment (Kelvin)receive / send2 Bytes9.1 temperature (°C)CRWTU
5Temperature, setpoint value (°C)send2 Bytes9.1 temperature (°C)CRTU
6Comfort modeOn / Off1 Bit1.1 switchCRWTU
7Pre-comfort modeOn / Off1 Bit1.1 switchCRWTU
8Economy modeOn / Off1 Bit1.1 switchCRWTU
9Protection modeOn / Off1 Bit1.1 switchCRWTU
10Permanent protection modeOn / Off1 Bit1.1 switchCRWTU
11AutomaticOn / Off1 Bit1.1 switchCRWTU
12ThermostatOn / Off1 Bit1.1 switchCRWTU
13Heating / cooling1= heating / 0 = cooling1 Bit1.1 switchCRWTU
14Frost alarmOn / Off1 Bit1.1 switchCRTU
15Heat alarmOn / Off1 Bit1.1 switchCRTU
16Dew point alarmOn / Off1 Bit1.1 switchCRWTU
17Window 11= open / 0 = close1 Bit1.1 switchCRWTU
18Window 21= open / 0 = close1 Bit1.1 switchCRWTU
19Window 31= open / 0 = close1 Bit1.1 switchCRWTU
20Window 41= open / 0 = close1 Bit1.1 switchCRWTU
21PresenceOn / Off1 Bit1.1 switchCRWTU
22Status extended comfort modeOn / Off1 Bit1.1 switchCRTU
23Room mode1... 41 ByteCWTU
24Status room mode1... 41 ByteCRT
25Controller-Status (Eberle)8-bit Status1 ByteCRWTU
26Controller-Status (RHCC)16-bit Status2 BytesCRWTU
27Heating / cooling, control value switchingOn / Off1 Bit1.1 switchCRT
27Heating / cooling, control value continuous0 ... 100%1 Byte5.1 percentage (0..100%)CRT
27Heating, control value switchingOn / Off1 Bit1.1 switchCRT
27Heating, control value continuous0 ... 100%1 Byte5.1 percentage (0..100%)CRT
28Heating, control value sequence 20 ... 100%1 Byte5.1 percentage (0..100%)CRT
29Cooling, control value switchingOn / Off1 Bit1.1 switchCRT
29Cooling, control value continuous0 ... 100%1 Byte5.1 percentage (0..100%)CRT
30Cooling, control value sequence 20 ... 100%1 Byte5.1 percentage (0..100%)CRT
31Control value0 ... 100%1 Byte5.1 percentage (0..100%)CRWT
Parameters (82)
ParameterTypeDefault
Internal sensor, offset to measured valuelistno offset
ETS download flagunsignedInt 0…255255
$first start flagunsignedInt 0…2550
>> Testlist$disable
$>> Test: value inlist$enable
$>> Test: direction of control valuelist$out
$>> Test: repetition timelistoff
Setpoint value settinglistvia setpoint value shift
Setpoint value settinglistdirectly in °C
Setpoint value shift rangelist5.0 °C / 41 F
Rotary locklistdisabled
Push buttonlistenabled
Time for long pressinglist1.0 s
$DummyunsignedInt 0…2553
Presence objectlistno
Permanent protection mode objectlistno
Number of window contactslist0
Reaction upon an open windowlistat once
8-bit objects room mode / room mode statuslistno
8-bit object controller status (Eberle)listno
16-bit object controller status (RHCC)listno
Operating mode controllerlistheating + cooling
Control value outputliston separate object
HeatinglistPI-control
Sequence controllistwithout sequence control
CoolinglistPI-control
Dead zone between heating und coolinglist±1,50 K
active modesunsignedInt 0…25518
Room modeslistcomfort/pre-comfort/economy/protection mode
Duration for extended comfort modelist30 minutes
Status object for extended comfort modelistno
Raum-Betriebsart nach Downloadlistprotection mode
Room mode after bus voltage recoverylistas before bus voltage failure
Basic setpoint value and actual value of external sensor on restartlist22 °C / 71.6 F
Send status objects on initialisationlistdelayed after 5s
External temperature sensorlistno
Cycle time for polling of external temperature sensorlist10 minutes
External sensor, offset to measured valuelistno offset
External / internal weightinglistonly internal sensor
Change of actual temperature value for automatic sendinglist0.5 K
Cycle time for automatic sending of the actual temperature valuelist10 minutes
Reduction heating pre-comfort modelist2 K
Reduction heating economy modelist4 K
Increase cooling pre-comfort modelist2 K
Increase cooling economy modelist4 K
Setpoint frost protection for heatinglist7 °C / 44.6 F
Setpoint heat protection for coolinglist35 °C / 95 F
Threshold for frost alarmlist0.5 °C / 32.9 F
Threshold for heating alarmlist40 °C / 104 F
Cycle time for sending frost-/heat alarmlist10 minutes
Operating mode heatingunsignedInt 0…2551
Operating mode coolingunsignedInt 0…2551
Hysteresislist-1,00 K
Proportional rangelist3.0 °C / 37.4 F
Double hysteresis in economy/ protection modelistyes
Integration timelist30 minutes
Cycle time, 2 level controllist5 minutes
$DummyunsignedInt 0…2551
Maximum control valuelist100%
Minimum control valuelist0%
Direction / scaling of control valuelist+100 % (normal)
Valve always open, if positioning value is above [in %]list100%
Valve always closed, if positioning value is below [in %]list1%
Hysteresislist+1,00 K
Type of control value output heating / coolinglistcontinuous (8-bit)
Type of control value outputlistcontinuous (8-bit)
Change of control value for automatic sendinglist5%
Cycle time for cyclical sending of the control valuelist15 minutes
valve typeunsignedInt 0…2551
Direction of the control valuelistnormal
Pulse width modulation period timelist10 minutes
Number of valvesunsignedInt 0…2551
$Heat / Cool als enableunsignedInt 0…255185
$Heat / Cool als statusunsignedInt 0…2550
Value for heating, sequence 2 starts from [in %]unsignedInt 0…255100
Value for heating, sequence 2 starts from [in %]unsignedInt 5…9550
Sequence 2, change of control value for automatic sendinglist5%
Sequence 2 cycle time for automatic sendinglist15 minutes
Value for cooling, sequence 2 starts from [in %]unsignedInt 0…255100
Value for cooling, sequence 2 starts from [in %]unsignedInt 5…9550
Setpoint value shift rangelist15 minutes
Deadzone between heating and coolingunsignedInt 0…5000

Version history

ApplicationApp noFingerprintFirst seenSizeFile
0705 CO Room Temperature Controller H+C 803002 0.2 latest$8030DF562026-11-25100 KBDownload

About this file

This is the official ETS product database for the Siemens Room Temperature Controller UP237KB_1 (5WG1 237-2KB_1), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.