KNX Database

KNX Air quality Combi Sensor & Control (V5.0) EL/ED/SD-xxxx-KNX

sensortec AG · Order number EL/ED/SD-xxxx-KNX · KNX Room Sensor & Control Options (V5.0) › ED/EL/SD.KNX Air quality combination sensor & control

KNX Air quality Combi Sensor & Control (V5.0)

Download .knxprod KNX Room Sensor & Control Options 5.1 · 120 KB

Product

Manufacturersensortec AG
Product nameKNX Air quality Combi Sensor & Control (V5.0)
Order numberEL/ED/SD-xxxx-KNX
Product textKNX Room Sensor & Control Options (V5.0)
HardwareHardware
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationRegistered · 2026-06-10
Languagesde-DE, fr-FR, en-US
Catalog entryM-0231_H--41_HP-0001-51-138A_CI-EL.2FED.2FSD.2Dxxxx.2DKNX-1
Fingerprint138A
SHA-25679e9d64cbc09c72bf3a3923c4c2073800b55a3679d3ac9ffe206e34d28d40fa6
First seen2026-11-25
MarketsSwitzerland

Application program: KNX Room Sensor & Control Options 5.1

Application number$0001
Version5.1
Mask versionMV-07B0 (System B)
KNX Data SecureYes
Minimum ETS version5.0
Parameters94
Group objects22
Group objects (22)
NoNameFunctionSizeDPTFlags
1TemperatureDPT 9 Temperature2 BytesDPT.9CRT
2HumidityDPT 9 Humidity2 BytesDPT.9CRT
3SetpointDPT 9 Setpoint2 BytesDPT.9CRT
3SetpointDPT 5 Setpoint1 ByteDPT.5CRT
4Button/LedDPT 1 Button/Led1 BitDPT.1CRWT
5Air quality eTVOC ppbDPT 9 eTVOC2 BytesCRT
6Air quality eCO2 ppmDPT 9 eCO22 BytesDPT.9CRT
7Air quality index AQI-SDPT 7 AQI_S2 BytesCRT
8Air quality index AQI-UBADPT 5 AQI_UBA1 ByteCRT
9Air quality ProzentDPT 9 AQI2 BytesDPT.9CRT
10Air quality CO2DPT 9 CO22 Bytes9.8 parts/million (ppm)CRWT
11Air quality monitor greenDPT 1 AQM green1 BitDPT.1CRT
12Air quality monitor orangeDPT 1 AQM orange1 BitDPT.1CRT
13Air quality monitor redDPT 1 AQM red1 BitDPT.1CRT
14Fan stage Auto/ManualDPT 1 Fan Auto/Manual1 BitDPT.1CRWT
15Fan stage 0DPT 1 Fan stage 01 BitDPT.1CRWT
16Fan stage 1DPT 1 Fan stage 11 BitDPT.1CRWT
17Fan stage 2DPT 1 Fan stage 21 BitDPT.1CRWT
18Fan stage 3DPT 1 Fan stage 31 BitDPT.1CRWT
19Fan stage value (bit)DPT 5 Fan stage (bit)1 ByteDPT.5CRWT
19Fan stage value (percent)DPT 5 Fan stage (percent)1 ByteDPT.5CRWT
20OptionDPT 16 Option14 BytesDPT.16CRT
Parameters (41)
ParameterTypeDefault
Transimition conditionlistRead only
Changelist1.0 °C
TimebaselistMinutes
CycletimeunsignedInt 1…25010
Transimition conditionlistNot used
Changelist5%
TypelistTemperature °C
Temperature difference min. [K]list-5 K
Temperature difference max. [K]list5 K
Change [ppb]unsignedInt 10…5010
Change [ppm]unsignedInt 20…10020
Type Fan valuelistBitfield
Fan value stage Auto (%)unsignedInt 0…10010
Fan value (%)unsignedInt 0…1000
Fan value stage 1 (%)unsignedInt 0…10025
Fan value stage 2 (%)unsignedInt 0…10050
Fan value stage 3 (%)unsignedInt 0…10075
Temperature offset [ 0.1 °C]signedInt -50…500
Led switch off time (S10) [Sec.]unsignedInt 0…2550
Reset from level 0listNO
AQM limit TVOC orangeunsignedInt 0…65535100
AQM limit TVOC redunsignedInt 0…65535300
AQM limit CO2 orangeunsignedInt 0…655351000
AQM limit CO2 redunsignedInt 0…655351400
AQM HytereseunsignedInt 0…6553510
Reset from level AutolistNO
Reset to stagelistPosition A
Reset timeunsignedInt 1…25010
Type AQMlistOff
Reset from level 2listNO
Reset from level 3listNO
Reset from level 1listNO
ChangeunsignedInt 0…25510
Temperature min. [°C]unsignedInt 5…3218
Temperature max. [°C]unsignedInt 5…3232
Filter Averaging time temperaturelist2s (default)
Filter Averaging time humiditylist2s (default)
Filter Averaging time VOClist2min. (default)
Filter Averaging time CO2list1min. (default)
Humidity offset [%rH]signedInt -20…200
CO2 offset [ppm]signedInt -500…5000

Version history

ApplicationApp noFingerprintFirst seenSizeFile
KNX Room Sensor & Control Options 5.1 latest$0001138A2026-11-25120 KBDownload

About this file

This is the official ETS product database for the sensortec AG KNX Air quality Combi Sensor & Control (V5.0) (EL/ED/SD-xxxx-KNX), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from sensortec AG

All sensortec AG products