RAx07-KNX V4 Luftqualität Kombi-Sensor & Bedienung RAx07-KNX V4
sensortec AG · Order number RAx07-KNX V4 · KNX Room Sensor & Control Options (V5.0) › ED/EL/SD.KNX Air quality combination sensor & control
Luftqualität Kombi-Sensor & Bedienung
Download .knxprod RAx07-KNX_V4 Luftqualität Kombi-Sensor & Bedienoptionen (V4.1) 1.1 · 116 KB
Product
| Manufacturer | sensortec AG |
|---|---|
| Product name | RAx07-KNX V4 Luftqualität Kombi-Sensor & Bedienung |
| Order number | RAx07-KNX V4 |
| Hardware | Hardware |
| Medium | Twisted Pair |
| Bus current (mA) | 10 |
| Rail mounted | No |
| Registration | Registered · 2025-01-16 |
| Languages | de-DE, fr-FR |
| Catalog entry | M-0231_H--41_HP-0001-11-2364_CI-RAx07.2DKNX.20V4-1 |
| Fingerprint | 2364 |
| SHA-256 | e3f5f8695e36ee9291d54b17af5adfc1391edc7ee971eedb2cdda12addfac861 |
| First seen | 2026-11-25 |
| Markets | Switzerland |
Application program: RAx07-KNX_V4 Luftqualität Kombi-Sensor & Bedienoptionen (V4.1) 1.1
| Application number | $0001 |
|---|---|
| Version | 1.1 |
| Mask version | MV-07B0 (System B) |
| KNX Data Secure | No |
| Minimum ETS version | 5.0 |
| Parameters | 86 |
| Group objects | 18 |
Group objects (18)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | Temperatur | DPT 9 | 2 Bytes | DPT.9 | CRT |
| 2 | Feuchte | DPT 9 | 2 Bytes | DPT.9 | CRT |
| 3 | Sollwert | DPT 9 | 2 Bytes | DPT.9 | CRT |
| 3 | Temperaturdifferenz | DPT 9 | 2 Bytes | DPT.9 | CRT |
| 3 | Sollwert | DPT 5 | 1 Byte | DPT.5 | CRT |
| 4 | Taste | DPT 1 | 1 Bit | DPT.1 | CRT |
| 5 | Luftqualität eTVOC ppb | DPT 9 | 2 Bytes | CRT | |
| 6 | Luftqualität eCO2 ppm | DPT 9 | 2 Bytes | DPT.9 | CRT |
| 7 | Luftqualität Prozent | DPT 9 | 2 Bytes | DPT.9 | CRT |
| 8 | CO2 ppm | DPT 9 | 2 Bytes | DPT.9 | CRWT |
| 9 | Auto/Manuell | DPT 1 | 1 Bit | DPT.1 | CRWT |
| 10 | Lüfterstufe 0 | DPT 1 | 1 Bit | DPT.1 | CRWT |
| 11 | Lüfterstufe 1 | DPT 1 | 1 Bit | DPT.1 | CRWT |
| 12 | Lüfterstufe 2 | DPT 1 | 1 Bit | DPT.1 | CRWT |
| 13 | Lüfterstufe 3 | DPT 1 | 1 Bit | DPT.1 | CRWT |
| 14 | Lüfterstufe Wert (Bit) | DPT 5 | 1 Byte | DPT.5 | CRWT |
| 14 | Lüfterstufe Wert (Prozent) | DPT 5 | 1 Byte | DPT.5 | CRWT |
| 15 | Optionen | DPT 16 | 14 Bytes | DPT.16 | CRT |
Parameters (43)
| Parameter | Type | Default |
|---|---|---|
| Gerätename | text | RAx07-KNX |
| PAR_SEND_INDICATION | list | Aktiviert |
| PAR_DP_DESC_SIZE_HI | unsignedInt 0…255 | 0 |
| PAR_DP_DESC_SIZE_LO | unsignedInt 0…255 | 0 |
| Sendebedingung | list | Nur lesen |
| Änderung | list | 1.0 °C |
| Zeitbasis | list | Minuten |
| Zykluszeit | unsignedInt 1…250 | 10 |
| Sendebedingung | list | Nicht benutzt |
| Änderung | list | 5% |
| DPT_TEMPERTURE | unsignedInt 0…255 | 9 |
| DPT_HUMIDITY | unsignedInt 0…255 | 9 |
| Typ | list | Temperatur °C |
| Temperatur min. [°C] | unsignedInt 5…32 | 5 |
| Temperatur max. [°C] | unsignedInt 5…32 | 32 |
| Temperaturdifferenz min. [K] | list | -5 K |
| Temperaturdifferenz max. [K] | list | 5 K |
| DPT_VALUE_TEMP | unsignedInt 0…255 | 9 |
| DPT_VALUE_DELTA | unsignedInt 0…255 | 9 |
| DPT_VALUE_PERC | unsignedInt 0…255 | 5 |
| DPT_BUTTON | unsignedInt 0…255 | 1 |
| Änderung [ppb] | unsignedInt 10…50 | 10 |
| DPT_TVOC_PPB | unsignedInt 0…255 | 9 |
| Änderung [ppm] | unsignedInt 20…100 | 20 |
| DPT_QUALITY_PPM | unsignedInt 0…255 | 9 |
| DPT_QUALITY_PERC | unsignedInt 0…255 | 9 |
| DPT_CO2_PPM | unsignedInt 0…255 | 9 |
| DPT_AUTOMATIC | unsignedInt 0…255 | 1 |
| DPT_FAN_LEVEL_1 | unsignedInt 0…255 | 1 |
| DPT_FAN_LEVEL_2 | unsignedInt 0…255 | 1 |
| DPT_FAN_LEVEL_3 | unsignedInt 0…255 | 1 |
| DPT_FAN_LEVEL_VAL | unsignedInt 0…255 | 5 |
| Typ Lüfter Wert | list | Bitfeld |
| Lüfter Wert Auto (%) | unsignedInt 0…100 | 10 |
| Fan Wert 0 (%) | unsignedInt 0…100 | 0 |
| Lüfter Wert 1 (%) | unsignedInt 0…100 | 25 |
| Lüfter Wert 2 (%) | unsignedInt 0…100 | 50 |
| DPT_OPTIONS | unsignedInt 0…255 | 16 |
| Lüfter Wert 3 (%) | unsignedInt 0…100 | 75 |
| Temperatur Offset [ 0.1 °C] | signedInt -50…50 | 0 |
| HARDWARE_TYPE | list | RAxE07-KNX_V4 |
| Ausschaltezeit Led (S10) [Sek.] | unsignedInt 0…255 | 0 |
| DPT_FAN_LEVEL_0 | unsignedInt 0…255 | 1 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| RAx07-KNX_V4 Luftqualität Kombi-Sensor & Bedienoptionen (V4.1) 1.1 latest | $0001 | 2364 | 2026-11-25 | 116 KB | Download |
About this file
This is the official ETS product database for the sensortec AG RAx07-KNX V4 Luftqualität Kombi-Sensor & Bedienung (RAx07-KNX V4), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from sensortec AG
- KNX Air quality Combi Sensor & Control (V5.0) EL/ED/SD-xxxx-KNX