KNX Heating Act. REG-K/6x24/230/0.16A MTN6730-0001
Schneider Electric Industries SAS · Order number MTN6730-0001 · 7.1 Heating/Single Room Thermostat › 7.1.2 Heating/Switch actuator
MTN6730-0001
Download .knxprod Switch PWM 2068/1.0 1.0 · 205 KB
Product
| Manufacturer | Schneider Electric Industries SAS |
|---|---|
| Product name | KNX Heating Act. REG-K/6x24/230/0.16A |
| Order number | MTN6730-0001 |
| Hardware | Heizungsaktor 6fach |
| Medium | Twisted Pair |
| Bus current (mA) | 10 |
| Rail mounted | Yes |
| Width (mm) | 72 |
| Registration | Certified |
| Languages | en-US, de-DE, fr-FR, da-DK, nl-NL, it-IT, sv-SE, es-ES |
| Catalog entry | M-0064_H-100.20.2F.2F.20MTN6730.2D0001-0-O000A_HP-2068-10-3988-O000A_CI-MTN6730.2D0001-1 |
| Fingerprint | 3988 |
| SHA-256 | 0be33fd6700d7fb5104c27edffec350ad4de0e05f21bda776d5b95a51e9d823a |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: Switch PWM 2068/1.0 1.0
| Application number | $2068 |
|---|---|
| Version | 1.0 |
| Mask version | MV-07B0 (System B) |
| KNX Data Secure | No |
| Minimum ETS version | 3.0d |
| Parameters | 775 |
| Group objects | 136 |
Group objects (136)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | Valve outputs - Output | Failure of operating voltage | 1 Bit | DPT.1 | CRTU |
| 2 | Pump - output | Switch pump | 1 Bit | 1.1 switch | CRTU |
| 3 | Pump - input | External pump control | 1 Bit | 1.1 switch | CWU |
| 4 | Valve outputs - Output | Largest command value | 1 Byte | 5.1 percentage (0..100%) | CRTU |
| 5 | Valve outputs - Input | External largest command value | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 6 | Valve outputs - Output | Heat requirement | 1 Bit | 1.2 boolean | CRTU |
| 7 | Valve outputs - Input | External heat requirement | 1 Bit | 1.2 boolean | CWU |
| 8 | Operating mode - input | Summer / winter change-over | 1 Bit | 1.2 boolean | CWU |
| 9 | Valve outputs - Input | Reset short-circuit / overload | 1 Bit | DPT.1 | CWU |
| 10 | Valve outputs - Output | Collective feedback status | 4 Bytes | CTU | |
| 10 | Valve outputs - Output | Collective feedback status | 4 Bytes | CRU | |
| 11 | Energy saving mode - Input | Activate / deactivate | 1 Bit | 1.3 enable | CWU |
| 12 | Service mode - input | Activate / deactivate | 2 Bit | 2.1 switch control | CWU |
| 13 | Service mode - output | Status active / inactive | 1 Bit | 1.2 boolean | CRTU |
| 14 | Manual operation - input | Disabling | 1 Bit | 1.3 enable | CWU |
| 15 | Manual operation - output | Status | 1 Bit | 1.2 boolean | CRTU |
| 20 | Valve output 1 - Input | Command value | 1 Bit | 1.1 switch | CWU |
| 21 | Valve output 1 - Input | Command value | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 22 | Valve output 1 - Output | Feedback valve command value | 1 Bit | 1.1 switch | CRU |
| 22 | Valve output 1 - Output | Feedback valve command value | 1 Bit | 1.1 switch | CTU |
| 23 | Valve output 1 - Output | Feedback valve command value | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 23 | Valve output 1 - Output | Feedback valve command value | 1 Byte | 5.1 percentage (0..100%) | CRU |
| 24 | Valve output 1 - Input | Forced position | 1 Bit | 1.3 enable | CWU |
| 25 | Valve output 1 - Output | Command value fault | 1 Bit | DPT.1 | CRTU |
| 26 | Valve output 1 - Input | Command value limit | 1 Bit | 1.2 boolean | CWU |
| 27 | Valve output 1 - Input | Valve rinsing start / stop | 1 Bit | 1.3 enable | CWU |
| 27 | Valve output 1 - Input | Valve rinsing start | 1 Bit | 1.3 enable | CWU |
| 28 | Valve output 1 - Output | Valve rinsing status | 1 Bit | 1.2 boolean | CRTU |
| 29 | Valve output 1 - Output | Signal short-circuit /overload | 1 Bit | DPT.1 | CRTU |
| 30 | Valve output 1 - Output | Feedback combined valve status | 1 Byte | CTU | |
| 30 | Valve output 1 - Output | Feedback combined valve status | 1 Byte | CRU | |
| 31 | Valve output 1 - Input | Op. hours counter limit value | 2 Bytes | DPT.7 | CWU |
| 31 | Valve output 1 - Input | Op. hours counter start value | 2 Bytes | DPT.7 | CWU |
| 32 | Valve output 1 - Input | Reset operating hours counter | 1 Bit | DPT.1 | CWU |
| 33 | Valve output 1 - Output | Value operating hours counter | 2 Bytes | DPT.7 | CRTU |
| 34 | Valve output 1 - Output | Op. hours counter elapsed | 1 Bit | 1.2 boolean | CRTU |
| 70 | Valve output 2 - Input | Command value | 1 Bit | 1.1 switch | CWU |
| 71 | Valve output 2 - Input | Command value | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 72 | Valve output 2 - Output | Feedback valve command value | 1 Bit | 1.1 switch | CRU |
| 72 | Valve output 2 - Output | Feedback valve command value | 1 Bit | 1.1 switch | CTU |
| 73 | Valve output 2 - Output | Feedback valve command value | 1 Byte | 5.1 percentage (0..100%) | CRU |
| 73 | Valve output 2 - Output | Feedback valve command value | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 74 | Valve output 2 - Input | Forced position | 1 Bit | 1.3 enable | CWU |
| 75 | Valve output 2 - Output | Command value fault | 1 Bit | DPT.1 | CRTU |
| 76 | Valve output 2 - Input | Command value limit | 1 Bit | 1.2 boolean | CWU |
| 77 | Valve output 2 - Input | Valve rinsing start / stop | 1 Bit | 1.3 enable | CWU |
| 77 | Valve output 2 - Input | Valve rinsing start | 1 Bit | 1.3 enable | CWU |
| 78 | Valve output 2 - Output | Valve rinsing status | 1 Bit | 1.2 boolean | CRTU |
| 79 | Valve output 2 - Output | Signal short-circuit /overload | 1 Bit | DPT.1 | CRTU |
| 80 | Valve output 2 - Output | Feedback combined valve status | 1 Byte | CTU | |
| 80 | Valve output 2 - Output | Feedback combined valve status | 1 Byte | CRU | |
| 81 | Valve output 2 - Input | Op. hours counter limit value | 2 Bytes | DPT.7 | CWU |
| 81 | Valve output 2 - Input | Op. hours counter start value | 2 Bytes | DPT.7 | CWU |
| 82 | Valve output 2 - Input | Reset operating hours counter | 1 Bit | DPT.1 | CWU |
| 83 | Valve output 2 - Output | Value operating hours counter | 2 Bytes | DPT.7 | CRTU |
| 84 | Valve output 2 - Output | Op. hours counter elapsed | 1 Bit | 1.2 boolean | CRTU |
| 120 | Valve output 3 - Input | Command value | 1 Bit | 1.1 switch | CWU |
| 121 | Valve output 3 - Input | Command value | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 122 | Valve output 3 - Output | Feedback valve command value | 1 Bit | 1.1 switch | CRU |
| 122 | Valve output 3 - Output | Feedback valve command value | 1 Bit | 1.1 switch | CTU |
| 123 | Valve output 3 - Output | Feedback valve command value | 1 Byte | 5.1 percentage (0..100%) | CRU |
| 123 | Valve output 3 - Output | Feedback valve command value | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 124 | Valve output 3 - Input | Forced position | 1 Bit | 1.3 enable | CWU |
| 125 | Valve output 3 - Output | Command value fault | 1 Bit | DPT.1 | CRTU |
| 126 | Valve output 3 - Input | Command value limit | 1 Bit | 1.2 boolean | CWU |
| 127 | Valve output 3 - Input | Valve rinsing start / stop | 1 Bit | 1.3 enable | CWU |
| 127 | Valve output 3 - Input | Valve rinsing start | 1 Bit | 1.3 enable | CWU |
| 128 | Valve output 3 - Output | Valve rinsing status | 1 Bit | 1.2 boolean | CRTU |
| 129 | Valve output 3 - Output | Signal short-circuit /overload | 1 Bit | DPT.1 | CRTU |
| 130 | Valve output 3 - Output | Feedback combined valve status | 1 Byte | CTU | |
| 130 | Valve output 3 - Output | Feedback combined valve status | 1 Byte | CRU | |
| 131 | Valve output 3 - Input | Op. hours counter limit value | 2 Bytes | DPT.7 | CWU |
| 131 | Valve output 3 - Input | Op. hours counter start value | 2 Bytes | DPT.7 | CWU |
| 132 | Valve output 3 - Input | Reset operating hours counter | 1 Bit | DPT.1 | CWU |
| 133 | Valve output 3 - Output | Value operating hours counter | 2 Bytes | DPT.7 | CRTU |
| 134 | Valve output 3 - Output | Op. hours counter elapsed | 1 Bit | 1.2 boolean | CRTU |
| 170 | Valve output 4 - Input | Command value | 1 Bit | 1.1 switch | CWU |
| 171 | Valve output 4 - Input | Command value | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 172 | Valve output 4 - Output | Feedback valve command value | 1 Bit | 1.1 switch | CRU |
| 172 | Valve output 4 - Output | Feedback valve command value | 1 Bit | 1.1 switch | CTU |
| 173 | Valve output 4 - Output | Feedback valve command value | 1 Byte | 5.1 percentage (0..100%) | CRU |
| 173 | Valve output 4 - Output | Feedback valve command value | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 174 | Valve output 4 - Input | Forced position | 1 Bit | 1.3 enable | CWU |
| 175 | Valve output 4 - Output | Command value fault | 1 Bit | DPT.1 | CRTU |
| 176 | Valve output 4 - Input | Command value limit | 1 Bit | 1.2 boolean | CWU |
| 177 | Valve output 4 - Input | Valve rinsing start / stop | 1 Bit | 1.3 enable | CWU |
| 177 | Valve output 4 - Input | Valve rinsing start | 1 Bit | 1.3 enable | CWU |
| 178 | Valve output 4 - Output | Valve rinsing status | 1 Bit | 1.2 boolean | CRTU |
| 179 | Valve output 4 - Output | Signal short-circuit /overload | 1 Bit | DPT.1 | CRTU |
| 180 | Valve output 4 - Output | Feedback combined valve status | 1 Byte | CTU | |
| 180 | Valve output 4 - Output | Feedback combined valve status | 1 Byte | CRU | |
| 181 | Valve output 4 - Input | Op. hours counter limit value | 2 Bytes | DPT.7 | CWU |
| 181 | Valve output 4 - Input | Op. hours counter start value | 2 Bytes | DPT.7 | CWU |
| 182 | Valve output 4 - Input | Reset operating hours counter | 1 Bit | DPT.1 | CWU |
| 183 | Valve output 4 - Output | Value operating hours counter | 2 Bytes | DPT.7 | CRTU |
| 184 | Valve output 4 - Output | Op. hours counter elapsed | 1 Bit | 1.2 boolean | CRTU |
| 220 | Valve output 5 - Input | Command value | 1 Bit | 1.1 switch | CWU |
| 221 | Valve output 5 - Input | Command value | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 222 | Valve output 5 - Output | Feedback valve command value | 1 Bit | 1.1 switch | CRU |
| 222 | Valve output 5 - Output | Feedback valve command value | 1 Bit | 1.1 switch | CTU |
| 223 | Valve output 5 - Output | Feedback valve command value | 1 Byte | 5.1 percentage (0..100%) | CRU |
| 223 | Valve output 5 - Output | Feedback valve command value | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 224 | Valve output 5 - Input | Forced position | 1 Bit | 1.3 enable | CWU |
| 225 | Valve output 5 - Output | Command value fault | 1 Bit | DPT.1 | CRTU |
| 226 | Valve output 5 - Input | Command value limit | 1 Bit | 1.2 boolean | CWU |
| 227 | Valve output 5 - Input | Valve rinsing start / stop | 1 Bit | 1.3 enable | CWU |
| 227 | Valve output 5 - Input | Valve rinsing start | 1 Bit | 1.3 enable | CWU |
| 228 | Valve output 5 - Output | Valve rinsing status | 1 Bit | 1.2 boolean | CRTU |
| 229 | Valve output 5 - Output | Signal short-circuit /overload | 1 Bit | DPT.1 | CRTU |
| 230 | Valve output 5 - Output | Feedback combined valve status | 1 Byte | CTU | |
| 230 | Valve output 5 - Output | Feedback combined valve status | 1 Byte | CRU | |
| 231 | Valve output 5 - Input | Op. hours counter limit value | 2 Bytes | DPT.7 | CWU |
| 231 | Valve output 5 - Input | Op. hours counter start value | 2 Bytes | DPT.7 | CWU |
| 232 | Valve output 5 - Input | Reset operating hours counter | 1 Bit | DPT.1 | CWU |
| 233 | Valve output 5 - Output | Value operating hours counter | 2 Bytes | DPT.7 | CRTU |
| 234 | Valve output 5 - Output | Op. hours counter elapsed | 1 Bit | 1.2 boolean | CRTU |
| 270 | Valve output 6 - Input | Command value | 1 Bit | 1.1 switch | CWU |
| 271 | Valve output 6 - Input | Command value | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 272 | Valve output 6 - Output | Feedback valve command value | 1 Bit | 1.1 switch | CRU |
| 272 | Valve output 6 - Output | Feedback valve command value | 1 Bit | 1.1 switch | CTU |
| 273 | Valve output 6 - Output | Feedback valve command value | 1 Byte | 5.1 percentage (0..100%) | CRU |
| 273 | Valve output 6 - Output | Feedback valve command value | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 274 | Valve output 6 - Input | Forced position | 1 Bit | 1.3 enable | CWU |
| 275 | Valve output 6 - Output | Command value fault | 1 Bit | DPT.1 | CRTU |
| 276 | Valve output 6 - Input | Command value limit | 1 Bit | 1.2 boolean | CWU |
| 277 | Valve output 6 - Input | Valve rinsing start / stop | 1 Bit | 1.3 enable | CWU |
| 277 | Valve output 6 - Input | Valve rinsing start | 1 Bit | 1.3 enable | CWU |
| 278 | Valve output 6 - Output | Valve rinsing status | 1 Bit | 1.2 boolean | CRTU |
| 279 | Valve output 6 - Output | Signal short-circuit /overload | 1 Bit | DPT.1 | CRTU |
| 280 | Valve output 6 - Output | Feedback combined valve status | 1 Byte | CTU | |
| 280 | Valve output 6 - Output | Feedback combined valve status | 1 Byte | CRU | |
| 281 | Valve output 6 - Input | Op. hours counter limit value | 2 Bytes | DPT.7 | CWU |
| 281 | Valve output 6 - Input | Op. hours counter start value | 2 Bytes | DPT.7 | CWU |
| 282 | Valve output 6 - Input | Reset operating hours counter | 1 Bit | DPT.1 | CWU |
| 283 | Valve output 6 - Output | Value operating hours counter | 2 Bytes | DPT.7 | CRTU |
| 284 | Valve output 6 - Output | Op. hours counter elapsed | 1 Bit | 1.2 boolean | CRTU |
Parameters (126)
| Parameter | Type | Default |
|---|---|---|
| Application Header Bytes 1...4 | unsignedInt 0…4294967295 | 1467630958 |
| Application Header Bytes 5...8 | unsignedInt 0…4294967295 | 100728832 |
| Application Header Bytes 9...10 | unsignedInt 0…65535 | 0 |
| Hardware Type | list | $00 0A 00 00 00 6E |
| Setting the parameters of the outputs | list | each output individual |
| Delay after bus voltage return Minutes (0...59) | unsignedInt 0…59 | 0 |
| Seconds (0...59) | unsignedInt 0…59 | 17 |
| Time for cycl trans of feedbk telegrams Hours (0...23) | unsignedInt 0…23 | 0 |
| Minutes (0...59) | unsignedInt 0…59 | 2 |
| Seconds (10...59) | unsignedInt 10…59 | 10 |
| Time for cyclic transm. of operat hours Hours (0...23) | unsignedInt 0…23 | 23 |
| Minutes (0...59) | unsignedInt 0…59 | 0 |
| Switchover of Summer/winter mode ? | list | no |
| Object polarity "Summer / Winter switch-over" | list | 1 = Winter / 0 = Summer |
| Operating mode after ETS programming | list | no change (saved operating mode) |
| Use service mode ? | list | no |
| Behaviour at the end of the service mode | list | Track states |
| Collect. feedbk status of value outputs (opened / closed) ? | list | no |
| Type of centralised feedback | list | active signalling object |
| Time delay for feedback telegram after bus voltage return? | list | no |
| Cyclical transmission of the feedback ? | list | no |
| Report operating voltage failure of the valves ? | list | no |
| Object polarity "Failure of operating voltage" | list | 0 = Voltage present / 1 = Voltage failed |
| Send feedback after bus voltage return ? | list | no |
| Time delay for feedback telegram after bus voltage return? | list | no |
| Cyclical transmission of the feedback if no voltage present ? | list | no |
| Global reset of all messages "short-circuit / overload" ? | list | no |
| Activate function "heat requirement" ? | list | no |
| Object polarity "Heat requirement" | list | 0 = no heat requirement / 1 = heat requirement |
| Record external heat requirement ? | list | no |
| Limiting value minimum command value for heating requirement (0...100 %) | unsignedInt 0…100 | 0 |
| Hysteresis for minimum command value (1...20 %) | unsignedInt 1…20 | 10 |
| Delay heat requirement ACTIVE hours (0...23) | unsignedInt 0…23 | 0 |
| Minutes (0...59) | unsignedInt 0…59 | 5 |
| Seconds (0...59) | unsignedInt 0…59 | 0 |
| Delay heat requirement INACTIVE hours (0...23) | unsignedInt 0…23 | 0 |
| Activate function "Largest command value" ? | list | no |
| Transmission of the largest command value | list | only on change |
| Send on change by | list | 3% |
| Record external largest command value ? | list | no |
| Activate function "Pump control" ? | list | no |
| Object polarity "Pump control" | list | 0 = Switch off pump / 1 = Switch on pump |
| Record external pump control ? | list | no |
| Limiting value minimum command value for pump (0...100 %) | unsignedInt 0…100 | 0 |
| Hysteresis for minimum command value (1...20 %) | unsignedInt 1…20 | 1 |
| Delay pump ACTIVE minutes (0...59) | unsignedInt 0…59 | 0 |
| Seconds (0...59) | unsignedInt 0…59 | 10 |
| Delay pump INACTIVE hours (0...23) | unsignedInt 0…23 | 0 |
| Minutes (0...59) | unsignedInt 0…59 | 10 |
| Activate anti-sticking protection ? | list | no |
| Time for cyclical switching on of the pump (1...26 weeks) | unsignedInt 1…26 | 1 |
| Switch-on time of the pump (1...15 minutes) | unsignedInt 1…15 | 5 |
| Einschaltzeit der Pumpe (0...15 Minuten) | unsignedInt 0…15 | 0 |
| Manual control in case of bus voltage failure | list | enabled |
| Manual control during bus operation | list | enabled |
| Disabling function ? | list | no |
| Polarity of disable object | list | 0 = enabled; 1 = disabled |
| Transmit status ? | list | no |
| Function and polarity Status object | list | 0 = inactive; 1 = Manual operation active |
| Behaviour at the end of permanent manual control during bus operation | list | no change |
| Behaviour of the manual operation on bus voltage return | list | Do not exit manual operation |
| Disable bus control of individual outputs during bus operation? | list | no |
| Cycle time during manual operation | list | 20 minutes (recommended) |
| PWM in manual operation (5...100 %) | unsignedInt 5…100 | 50 |
| Energiesparmodus | list | disabled |
| Object polarity "Energy saving mode" | list | 0 = deactivate; 1 = activate |
| Behaviour after bus voltage return | list | State as before bus voltage failure |
| Valve rinsing after deactivation of energy saving mode ? | list | no |
| Switch on pump after deactivation of energy saving mode? | list | no |
| Setting of the parameters | list | individual |
| Valve in voltage-free state( Valve direction of action) | list | closed |
| Response to bus voltage failure | list | Activating command as for emergency operation |
| Command value in case of bus voltage failure | list | 0% |
| Behaviour after bus or mains voltage return | list | Specify command value |
| Command value after bus or mains voltage return | list | 0% |
| Behaviour after ETS programming | list | Specify command value |
| Command value after ETS programming | list | 0% |
| Data format of the command value input | list | Switching (1 bit) |
| Limiting value of the command value for opening the valve (1...100 %) | unsignedInt 1…100 | 10 |
| Hysteresis limiting value for closing the valve (1...10 %) | unsignedInt 1…10 | 5 |
| Cycle time for continuous command value on the valve output | list | 20 minutes |
| Activate command value monitoring ? | list | no |
| Monitoring time minutes (0...59) | unsignedInt 0…59 | 10 |
| Object polarity "Command value fault" | list | 0 = No fault / 1 = Fault. |
| Cyclic transmission in case of faulty command value ? | list | no |
| Use command value limit ? | list | no |
| Activation of the command value limit | list | by object "command value limit" |
| Activate command value limit after bus voltage return ? | list | no |
| Activate command value limit after ETS programming? | list | no |
| Minimum command value | list | 0% |
| Maximum command value | list | 100% |
| Cmd value if active emergency operation summer | list | 30% |
| Command value if active emergency operation | list | 30% |
| Cmd value if active emergency operation winter | list | 70% |
| Command value if active forced position summer | list | 30% |
| Command value if active forced position | list | 30% |
| Command value if active forced position winter | list | 70% |
| Use object for the forced position ? | list | no |
| Object polarity "Forced position" | list | 0 = no forced pos / 1 = forced pos active |
| Feed back valve command value ? | list | no |
| Type of feedback | list | active signalling object |
| Feed back combined valve status ? | list | no |
| Type of combined status feedback | list | active signalling object |
| Signalling short-circuit / overload ? | list | no |
| Object polarity "Short-circ / overload" | list | 0 = no short-cir, overld. / 1 = short-cir, overld. |
| Use function "Valve rinsing" ? | list | no |
| Length of the valve rinsing (1...59 minutes) | unsignedInt 1…59 | 5 |
| Activate cyclical valve rinsing? | list | yes |
| Cycle time (1...26 weeks) | unsignedInt 1…26 | 1 |
| Use intelligent valve rinsing ? | list | no |
| Limiting value min. command value (10...100 %) | unsignedInt 10…100 | 50 |
| Valve rinsing externally controllable ? | list | no |
| Object polarity "Valve rinsing Start / Stop" | list | 0 = Stop / 1 = Start |
| Use operating hours counter ? | list | no |
| Type of counter | list | Up-counter |
| Limiting value specification ? | list | no |
| Limiting value (1...65535 h) | unsignedInt 1…65535 | 65535 |
| Start value preset ? | list | no |
| Start value (1...65535 h) | unsignedInt 1…65535 | 65535 |
| Automatic transmission of the counting value | list | after change by interval value |
| Counting value interval (1…65535 h) | unsignedInt 1…65535 | 1 |
| Assignment to the function "Pump control" ? | list | no |
| Assignment to the function "Heating requirement" ? | list | yes |
| Assignment to the function "Largest command value" ? | list | no |
| Assignment to the service mode ? | list | yes |
| Assignment to the function "Pump control" ? | list | yes |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Switch PWM 2068/1.0 1.0 latest | $2068 | 3988 | 2026-11-25 | 205 KB | Download |
About this file
This is the official ETS product database for the Schneider Electric Industries SAS KNX Heating Act. REG-K/6x24/230/0.16A (MTN6730-0001), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Schneider Electric Industries SAS
- Room temperature control unit with display ALB4x154
- Room temperature control unit with display MGU3.534.xx
- Room temperature control unit with display MGU5.534.xx
- Room temperature control unit with display MGU50.534.xx
- KNX Heating Act. FM w.3 Inputs MTN6003-0005
- Room temperature control unit for properties MTN6221-03xx
- Room temperature control unit for properties MTN6221-04xx
- Room temperature control unit with display MTN6241-03xx
- Room temperature control unit with display MTN6241-04xx
- Room temperature control unit with display MTN6241-40xx
- Room temperature control unit with display MTN6241-41xx
- KNX Fan coil actuator REG-K MTN645094