KNX Database

KNX Heating Act. REG-K/6x24/230/0.16A MTN6730-0001

Schneider Electric Industries SAS · Order number MTN6730-0001 · 7.1 Heating/Single Room Thermostat › 7.1.2 Heating/Switch actuator

MTN6730-0001

Download .knxprod Switch PWM 2068/1.0 1.0 · 205 KB

Product

ManufacturerSchneider Electric Industries SAS
Product nameKNX Heating Act. REG-K/6x24/230/0.16A
Order numberMTN6730-0001
HardwareHeizungsaktor 6fach
MediumTwisted Pair
Bus current (mA)10
Rail mountedYes
Width (mm)72
RegistrationCertified
Languagesen-US, de-DE, fr-FR, da-DK, nl-NL, it-IT, sv-SE, es-ES
Catalog entryM-0064_H-100.20.2F.2F.20MTN6730.2D0001-0-O000A_HP-2068-10-3988-O000A_CI-MTN6730.2D0001-1
Fingerprint3988
SHA-2560be33fd6700d7fb5104c27edffec350ad4de0e05f21bda776d5b95a51e9d823a
First seen2026-11-25
Markets59 markets

Application program: Switch PWM 2068/1.0 1.0

Application number$2068
Version1.0
Mask versionMV-07B0 (System B)
KNX Data SecureNo
Minimum ETS version3.0d
Parameters775
Group objects136
Group objects (136)
NoNameFunctionSizeDPTFlags
1Valve outputs - OutputFailure of operating voltage1 BitDPT.1CRTU
2Pump - outputSwitch pump1 Bit1.1 switchCRTU
3Pump - inputExternal pump control1 Bit1.1 switchCWU
4Valve outputs - OutputLargest command value1 Byte5.1 percentage (0..100%)CRTU
5Valve outputs - InputExternal largest command value1 Byte5.1 percentage (0..100%)CWU
6Valve outputs - OutputHeat requirement1 Bit1.2 booleanCRTU
7Valve outputs - InputExternal heat requirement1 Bit1.2 booleanCWU
8Operating mode - inputSummer / winter change-over1 Bit1.2 booleanCWU
9Valve outputs - InputReset short-circuit / overload1 BitDPT.1CWU
10Valve outputs - OutputCollective feedback status4 BytesCTU
10Valve outputs - OutputCollective feedback status4 BytesCRU
11Energy saving mode - InputActivate / deactivate1 Bit1.3 enableCWU
12Service mode - inputActivate / deactivate2 Bit2.1 switch controlCWU
13Service mode - outputStatus active / inactive1 Bit1.2 booleanCRTU
14Manual operation - inputDisabling1 Bit1.3 enableCWU
15Manual operation - outputStatus1 Bit1.2 booleanCRTU
20Valve output 1 - InputCommand value1 Bit1.1 switchCWU
21Valve output 1 - InputCommand value1 Byte5.1 percentage (0..100%)CWU
22Valve output 1 - OutputFeedback valve command value1 Bit1.1 switchCRU
22Valve output 1 - OutputFeedback valve command value1 Bit1.1 switchCTU
23Valve output 1 - OutputFeedback valve command value1 Byte5.1 percentage (0..100%)CTU
23Valve output 1 - OutputFeedback valve command value1 Byte5.1 percentage (0..100%)CRU
24Valve output 1 - InputForced position1 Bit1.3 enableCWU
25Valve output 1 - OutputCommand value fault1 BitDPT.1CRTU
26Valve output 1 - InputCommand value limit1 Bit1.2 booleanCWU
27Valve output 1 - InputValve rinsing start / stop1 Bit1.3 enableCWU
27Valve output 1 - InputValve rinsing start1 Bit1.3 enableCWU
28Valve output 1 - OutputValve rinsing status1 Bit1.2 booleanCRTU
29Valve output 1 - OutputSignal short-circuit /overload1 BitDPT.1CRTU
30Valve output 1 - OutputFeedback combined valve status1 ByteCTU
30Valve output 1 - OutputFeedback combined valve status1 ByteCRU
31Valve output 1 - InputOp. hours counter limit value2 BytesDPT.7CWU
31Valve output 1 - InputOp. hours counter start value2 BytesDPT.7CWU
32Valve output 1 - InputReset operating hours counter1 BitDPT.1CWU
33Valve output 1 - OutputValue operating hours counter2 BytesDPT.7CRTU
34Valve output 1 - OutputOp. hours counter elapsed1 Bit1.2 booleanCRTU
70Valve output 2 - InputCommand value1 Bit1.1 switchCWU
71Valve output 2 - InputCommand value1 Byte5.1 percentage (0..100%)CWU
72Valve output 2 - OutputFeedback valve command value1 Bit1.1 switchCRU
72Valve output 2 - OutputFeedback valve command value1 Bit1.1 switchCTU
73Valve output 2 - OutputFeedback valve command value1 Byte5.1 percentage (0..100%)CRU
73Valve output 2 - OutputFeedback valve command value1 Byte5.1 percentage (0..100%)CTU
74Valve output 2 - InputForced position1 Bit1.3 enableCWU
75Valve output 2 - OutputCommand value fault1 BitDPT.1CRTU
76Valve output 2 - InputCommand value limit1 Bit1.2 booleanCWU
77Valve output 2 - InputValve rinsing start / stop1 Bit1.3 enableCWU
77Valve output 2 - InputValve rinsing start1 Bit1.3 enableCWU
78Valve output 2 - OutputValve rinsing status1 Bit1.2 booleanCRTU
79Valve output 2 - OutputSignal short-circuit /overload1 BitDPT.1CRTU
80Valve output 2 - OutputFeedback combined valve status1 ByteCTU
80Valve output 2 - OutputFeedback combined valve status1 ByteCRU
81Valve output 2 - InputOp. hours counter limit value2 BytesDPT.7CWU
81Valve output 2 - InputOp. hours counter start value2 BytesDPT.7CWU
82Valve output 2 - InputReset operating hours counter1 BitDPT.1CWU
83Valve output 2 - OutputValue operating hours counter2 BytesDPT.7CRTU
84Valve output 2 - OutputOp. hours counter elapsed1 Bit1.2 booleanCRTU
120Valve output 3 - InputCommand value1 Bit1.1 switchCWU
121Valve output 3 - InputCommand value1 Byte5.1 percentage (0..100%)CWU
122Valve output 3 - OutputFeedback valve command value1 Bit1.1 switchCRU
122Valve output 3 - OutputFeedback valve command value1 Bit1.1 switchCTU
123Valve output 3 - OutputFeedback valve command value1 Byte5.1 percentage (0..100%)CRU
123Valve output 3 - OutputFeedback valve command value1 Byte5.1 percentage (0..100%)CTU
124Valve output 3 - InputForced position1 Bit1.3 enableCWU
125Valve output 3 - OutputCommand value fault1 BitDPT.1CRTU
126Valve output 3 - InputCommand value limit1 Bit1.2 booleanCWU
127Valve output 3 - InputValve rinsing start / stop1 Bit1.3 enableCWU
127Valve output 3 - InputValve rinsing start1 Bit1.3 enableCWU
128Valve output 3 - OutputValve rinsing status1 Bit1.2 booleanCRTU
129Valve output 3 - OutputSignal short-circuit /overload1 BitDPT.1CRTU
130Valve output 3 - OutputFeedback combined valve status1 ByteCTU
130Valve output 3 - OutputFeedback combined valve status1 ByteCRU
131Valve output 3 - InputOp. hours counter limit value2 BytesDPT.7CWU
131Valve output 3 - InputOp. hours counter start value2 BytesDPT.7CWU
132Valve output 3 - InputReset operating hours counter1 BitDPT.1CWU
133Valve output 3 - OutputValue operating hours counter2 BytesDPT.7CRTU
134Valve output 3 - OutputOp. hours counter elapsed1 Bit1.2 booleanCRTU
170Valve output 4 - InputCommand value1 Bit1.1 switchCWU
171Valve output 4 - InputCommand value1 Byte5.1 percentage (0..100%)CWU
172Valve output 4 - OutputFeedback valve command value1 Bit1.1 switchCRU
172Valve output 4 - OutputFeedback valve command value1 Bit1.1 switchCTU
173Valve output 4 - OutputFeedback valve command value1 Byte5.1 percentage (0..100%)CRU
173Valve output 4 - OutputFeedback valve command value1 Byte5.1 percentage (0..100%)CTU
174Valve output 4 - InputForced position1 Bit1.3 enableCWU
175Valve output 4 - OutputCommand value fault1 BitDPT.1CRTU
176Valve output 4 - InputCommand value limit1 Bit1.2 booleanCWU
177Valve output 4 - InputValve rinsing start / stop1 Bit1.3 enableCWU
177Valve output 4 - InputValve rinsing start1 Bit1.3 enableCWU
178Valve output 4 - OutputValve rinsing status1 Bit1.2 booleanCRTU
179Valve output 4 - OutputSignal short-circuit /overload1 BitDPT.1CRTU
180Valve output 4 - OutputFeedback combined valve status1 ByteCTU
180Valve output 4 - OutputFeedback combined valve status1 ByteCRU
181Valve output 4 - InputOp. hours counter limit value2 BytesDPT.7CWU
181Valve output 4 - InputOp. hours counter start value2 BytesDPT.7CWU
182Valve output 4 - InputReset operating hours counter1 BitDPT.1CWU
183Valve output 4 - OutputValue operating hours counter2 BytesDPT.7CRTU
184Valve output 4 - OutputOp. hours counter elapsed1 Bit1.2 booleanCRTU
220Valve output 5 - InputCommand value1 Bit1.1 switchCWU
221Valve output 5 - InputCommand value1 Byte5.1 percentage (0..100%)CWU
222Valve output 5 - OutputFeedback valve command value1 Bit1.1 switchCRU
222Valve output 5 - OutputFeedback valve command value1 Bit1.1 switchCTU
223Valve output 5 - OutputFeedback valve command value1 Byte5.1 percentage (0..100%)CRU
223Valve output 5 - OutputFeedback valve command value1 Byte5.1 percentage (0..100%)CTU
224Valve output 5 - InputForced position1 Bit1.3 enableCWU
225Valve output 5 - OutputCommand value fault1 BitDPT.1CRTU
226Valve output 5 - InputCommand value limit1 Bit1.2 booleanCWU
227Valve output 5 - InputValve rinsing start / stop1 Bit1.3 enableCWU
227Valve output 5 - InputValve rinsing start1 Bit1.3 enableCWU
228Valve output 5 - OutputValve rinsing status1 Bit1.2 booleanCRTU
229Valve output 5 - OutputSignal short-circuit /overload1 BitDPT.1CRTU
230Valve output 5 - OutputFeedback combined valve status1 ByteCTU
230Valve output 5 - OutputFeedback combined valve status1 ByteCRU
231Valve output 5 - InputOp. hours counter limit value2 BytesDPT.7CWU
231Valve output 5 - InputOp. hours counter start value2 BytesDPT.7CWU
232Valve output 5 - InputReset operating hours counter1 BitDPT.1CWU
233Valve output 5 - OutputValue operating hours counter2 BytesDPT.7CRTU
234Valve output 5 - OutputOp. hours counter elapsed1 Bit1.2 booleanCRTU
270Valve output 6 - InputCommand value1 Bit1.1 switchCWU
271Valve output 6 - InputCommand value1 Byte5.1 percentage (0..100%)CWU
272Valve output 6 - OutputFeedback valve command value1 Bit1.1 switchCRU
272Valve output 6 - OutputFeedback valve command value1 Bit1.1 switchCTU
273Valve output 6 - OutputFeedback valve command value1 Byte5.1 percentage (0..100%)CRU
273Valve output 6 - OutputFeedback valve command value1 Byte5.1 percentage (0..100%)CTU
274Valve output 6 - InputForced position1 Bit1.3 enableCWU
275Valve output 6 - OutputCommand value fault1 BitDPT.1CRTU
276Valve output 6 - InputCommand value limit1 Bit1.2 booleanCWU
277Valve output 6 - InputValve rinsing start / stop1 Bit1.3 enableCWU
277Valve output 6 - InputValve rinsing start1 Bit1.3 enableCWU
278Valve output 6 - OutputValve rinsing status1 Bit1.2 booleanCRTU
279Valve output 6 - OutputSignal short-circuit /overload1 BitDPT.1CRTU
280Valve output 6 - OutputFeedback combined valve status1 ByteCTU
280Valve output 6 - OutputFeedback combined valve status1 ByteCRU
281Valve output 6 - InputOp. hours counter limit value2 BytesDPT.7CWU
281Valve output 6 - InputOp. hours counter start value2 BytesDPT.7CWU
282Valve output 6 - InputReset operating hours counter1 BitDPT.1CWU
283Valve output 6 - OutputValue operating hours counter2 BytesDPT.7CRTU
284Valve output 6 - OutputOp. hours counter elapsed1 Bit1.2 booleanCRTU
Parameters (126)
ParameterTypeDefault
Application Header Bytes 1...4unsignedInt 0…42949672951467630958
Application Header Bytes 5...8unsignedInt 0…4294967295100728832
Application Header Bytes 9...10unsignedInt 0…655350
Hardware Typelist$00 0A 00 00 00 6E
Setting the parameters of the outputslisteach output individual
Delay after bus voltage return Minutes (0...59)unsignedInt 0…590
Seconds (0...59)unsignedInt 0…5917
Time for cycl trans of feedbk telegrams Hours (0...23)unsignedInt 0…230
Minutes (0...59)unsignedInt 0…592
Seconds (10...59)unsignedInt 10…5910
Time for cyclic transm. of operat hours Hours (0...23)unsignedInt 0…2323
Minutes (0...59)unsignedInt 0…590
Switchover of Summer/winter mode ?listno
Object polarity "Summer / Winter switch-over"list1 = Winter / 0 = Summer
Operating mode after ETS programminglistno change (saved operating mode)
Use service mode ?listno
Behaviour at the end of the service modelistTrack states
Collect. feedbk status of value outputs (opened / closed) ?listno
Type of centralised feedbacklistactive signalling object
Time delay for feedback telegram after bus voltage return?listno
Cyclical transmission of the feedback ?listno
Report operating voltage failure of the valves ?listno
Object polarity "Failure of operating voltage"list0 = Voltage present / 1 = Voltage failed
Send feedback after bus voltage return ?listno
Time delay for feedback telegram after bus voltage return?listno
Cyclical transmission of the feedback if no voltage present ?listno
Global reset of all messages "short-circuit / overload" ?listno
Activate function "heat requirement" ?listno
Object polarity "Heat requirement"list0 = no heat requirement / 1 = heat requirement
Record external heat requirement ?listno
Limiting value minimum command value for heating requirement (0...100 %)unsignedInt 0…1000
Hysteresis for minimum command value (1...20 %)unsignedInt 1…2010
Delay heat requirement ACTIVE hours (0...23)unsignedInt 0…230
Minutes (0...59)unsignedInt 0…595
Seconds (0...59)unsignedInt 0…590
Delay heat requirement INACTIVE hours (0...23)unsignedInt 0…230
Activate function "Largest command value" ?listno
Transmission of the largest command valuelistonly on change
Send on change bylist3%
Record external largest command value ?listno
Activate function "Pump control" ?listno
Object polarity "Pump control"list0 = Switch off pump / 1 = Switch on pump
Record external pump control ?listno
Limiting value minimum command value for pump (0...100 %)unsignedInt 0…1000
Hysteresis for minimum command value (1...20 %)unsignedInt 1…201
Delay pump ACTIVE minutes (0...59)unsignedInt 0…590
Seconds (0...59)unsignedInt 0…5910
Delay pump INACTIVE hours (0...23)unsignedInt 0…230
Minutes (0...59)unsignedInt 0…5910
Activate anti-sticking protection ?listno
Time for cyclical switching on of the pump (1...26 weeks)unsignedInt 1…261
Switch-on time of the pump (1...15 minutes)unsignedInt 1…155
Einschaltzeit der Pumpe (0...15 Minuten)unsignedInt 0…150
Manual control in case of bus voltage failurelistenabled
Manual control during bus operationlistenabled
Disabling function ?listno
Polarity of disable objectlist0 = enabled; 1 = disabled
Transmit status ?listno
Function and polarity Status objectlist0 = inactive; 1 = Manual operation active
Behaviour at the end of permanent manual control during bus operationlistno change
Behaviour of the manual operation on bus voltage returnlistDo not exit manual operation
Disable bus control of individual outputs during bus operation?listno
Cycle time during manual operationlist20 minutes (recommended)
PWM in manual operation (5...100 %)unsignedInt 5…10050
Energiesparmoduslistdisabled
Object polarity "Energy saving mode"list0 = deactivate; 1 = activate
Behaviour after bus voltage returnlistState as before bus voltage failure
Valve rinsing after deactivation of energy saving mode ?listno
Switch on pump after deactivation of energy saving mode?listno
Setting of the parameterslistindividual
Valve in voltage-free state( Valve direction of action)listclosed
Response to bus voltage failurelistActivating command as for emergency operation
Command value in case of bus voltage failurelist0%
Behaviour after bus or mains voltage returnlistSpecify command value
Command value after bus or mains voltage returnlist0%
Behaviour after ETS programminglistSpecify command value
Command value after ETS programminglist0%
Data format of the command value inputlistSwitching (1 bit)
Limiting value of the command value for opening the valve (1...100 %)unsignedInt 1…10010
Hysteresis limiting value for closing the valve (1...10 %)unsignedInt 1…105
Cycle time for continuous command value on the valve outputlist20 minutes
Activate command value monitoring ?listno
Monitoring time minutes (0...59)unsignedInt 0…5910
Object polarity "Command value fault"list0 = No fault / 1 = Fault.
Cyclic transmission in case of faulty command value ?listno
Use command value limit ?listno
Activation of the command value limitlistby object "command value limit"
Activate command value limit after bus voltage return ?listno
Activate command value limit after ETS programming?listno
Minimum command valuelist0%
Maximum command valuelist100%
Cmd value if active emergency operation summerlist30%
Command value if active emergency operationlist30%
Cmd value if active emergency operation winterlist70%
Command value if active forced position summerlist30%
Command value if active forced positionlist30%
Command value if active forced position winterlist70%
Use object for the forced position ?listno
Object polarity "Forced position"list0 = no forced pos / 1 = forced pos active
Feed back valve command value ?listno
Type of feedbacklistactive signalling object
Feed back combined valve status ?listno
Type of combined status feedbacklistactive signalling object
Signalling short-circuit / overload ?listno
Object polarity "Short-circ / overload"list0 = no short-cir, overld. / 1 = short-cir, overld.
Use function "Valve rinsing" ?listno
Length of the valve rinsing (1...59 minutes)unsignedInt 1…595
Activate cyclical valve rinsing?listyes
Cycle time (1...26 weeks)unsignedInt 1…261
Use intelligent valve rinsing ?listno
Limiting value min. command value (10...100 %)unsignedInt 10…10050
Valve rinsing externally controllable ?listno
Object polarity "Valve rinsing Start / Stop"list0 = Stop / 1 = Start
Use operating hours counter ?listno
Type of counterlistUp-counter
Limiting value specification ?listno
Limiting value (1...65535 h)unsignedInt 1…6553565535
Start value preset ?listno
Start value (1...65535 h)unsignedInt 1…6553565535
Automatic transmission of the counting valuelistafter change by interval value
Counting value interval (1…65535 h)unsignedInt 1…655351
Assignment to the function "Pump control" ?listno
Assignment to the function "Heating requirement" ?listyes
Assignment to the function "Largest command value" ?listno
Assignment to the service mode ?listyes
Assignment to the function "Pump control" ?listyes

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Switch PWM 2068/1.0 1.0 latest$206839882026-11-25205 KBDownload

About this file

This is the official ETS product database for the Schneider Electric Industries SAS KNX Heating Act. REG-K/6x24/230/0.16A (MTN6730-0001), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.