KNX CO2, Humidity and Temperature Sensor MTN6005-0001
Schneider Electric Industries SAS · Order number MTN6005-0001 · 2.9 Physical Sensors › 2.9.05 Carbon Dioxide
MTN6005-0001
Download .knxprod CO2-,Humidity-&Temp.Sensor 4216/1.2 1.2 · 110 KB
Product
| Manufacturer | Schneider Electric Industries SAS |
|---|---|
| Product name | KNX CO2, Humidity and Temperature Sensor |
| Order number | MTN6005-0001 |
| Hardware | KNX CO2-, Humidity- and Temperature Sensor |
| Medium | Twisted Pair |
| Bus current (mA) | 12 |
| Rail mounted | No |
| Registration | Registered |
| Languages | en-US, de-DE, fr-FR, da-DK, nl-NL, it-IT, sv-SE, es-ES |
| Catalog entry | M-0064_H-MTN6005.2D0001-1-O0048_HP-FF21-12-CFCD-O0048_CI-MTN6005.2D0001-1 |
| Fingerprint | CFCD |
| SHA-256 | 084e5541bf963d0c55d640cbcd6cb79c676706fab460295e9cc28f65e2169368 |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: CO2-,Humidity-&Temp.Sensor 4216/1.2 1.2
| Application number | $FF21 |
|---|---|
| Version | 1.2 |
| Mask version | MV-0701 (7.1) |
| KNX Data Secure | No |
| Parameters | 179 |
| Group objects | 45 |
Group objects (45)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | CO2 Value | Physical value | 2 Bytes | CRT | |
| 1 | Rel. humidity value | Physical value | 1 Byte | CRT | |
| 2 | Temperature value | Physical value | 2 Bytes | CRT | |
| 3 | Threshold 1 CO2 | Value | 1 Byte | CRT | |
| 3 | Threshold 1 CO2 | Switch | 1 Bit | CRT | |
| 3 | Threshold 1 CO2 | Priority | 2 Bit | CRT | |
| 4 | Lock threshold 1 CO2 | Input | 1 Bit | CRW | |
| 5 | Threshold 2 CO2 | Value | 1 Byte | CRT | |
| 5 | Threshold 2 CO2 | Switch | 1 Bit | CRT | |
| 5 | Threshold 2 CO2 | Priority | 2 Bit | CRT | |
| 5 | Threshold 1 CO2 | Value | 1 Byte | CRT | |
| 6 | Lock threshold 2 CO2 | Input | 1 Bit | CRW | |
| 7 | Threshold 3 CO2 | Value | 1 Byte | CRT | |
| 7 | Threshold 3 CO2 | Switch | 1 Bit | CRT | |
| 7 | Threshold 3 CO2 | Priority | 2 Bit | CRT | |
| 7 | Threshold 1 CO2 | Value | 1 Byte | CRT | |
| 8 | Lock threshold 3 CO2 | Input | 1 Bit | CRW | |
| 9 | Ventilation CO2 | Value for ventilation-actuator | 1 Byte | CRT | |
| 10 | Lock ventilation CO2 | Input | 1 Bit | CRW | |
| 11 | Scenes CO2 | Scene Control | 1 Byte | CRT | |
| 12 | Lock CO2 scenes | Input | 1 Bit | CRW | |
| 13 | Threshold 1 humidity | Value | 1 Byte | CRT | |
| 13 | Threshold 1 humidity | Switch | 1 Bit | CRT | |
| 13 | Threshold 1 humidity | Priority | 2 Bit | CRT | |
| 14 | Lock threshold 1 humidity | Input | 1 Bit | CRW | |
| 15 | Threshold 2 humidity | Value | 1 Byte | CRT | |
| 15 | Threshold 2 humidity | Switch | 1 Bit | CRT | |
| 15 | Threshold 2 humidity | Priority | 2 Bit | CRT | |
| 15 | Threshold 1 humidity | Value | 1 Byte | CRT | |
| 16 | Lock threshold 2 humidity | Input | 1 Bit | CRW | |
| 17 | Threshold 3 humidity | Value | 1 Byte | CRT | |
| 17 | Threshold 3 humidity | Switch | 1 Bit | CRT | |
| 17 | Threshold 3 humidity | Priority | 2 Bit | CRT | |
| 17 | Threshold 1 humidity | Value | 1 Byte | CRT | |
| 18 | Lock threshold 3 humidity | Input | 1 Bit | CRW | |
| 19 | Ventilation rel. humidity | Value for ventilation-actuator | 1 Byte | CRT | |
| 20 | Lock ventilation rel. humidity | Input | 1 Bit | CRW | |
| 21 | Scenes rel. humidity | Scene Control | 1 Byte | CRT | |
| 22 | Lock scenes rel. humidity | Input | 1 Bit | CRW | |
| 23 | Temperature threshold | Value | 1 Byte | CRT | |
| 23 | Temperature threshold | Priority | 2 Bit | CRT | |
| 23 | Temperature threshold | Switch | 1 Bit | CRT | |
| 24 | Lock temperature threshold | Input | 1 Bit | CRW | |
| 25 | Highest active value ventilation | Value for ventilation-actuator | 1 Byte | CRT | |
| 26 | LEDs for CO2 and humidity | On / Off | 1 Bit | CRW |
Parameters (89)
| Parameter | Type | Default |
|---|---|---|
| LEDs for CO2 and humidity | list | always on |
| Send CO2 concentration on change of | list | 200 ppm |
| Send CO2 concentration cyclically | list | don´t send cyclically |
| Send humidity value on change of | list | 2 % |
| Send humidity value cyclically | list | don´t send cyclically |
| Send temperature on change of | list | 0.5 °C |
| Send temperature cyclically | list | don´t send cyclically |
| Temperature offset in 0.1°C (-64..64) | signedInt -64…64 | 0 |
| Threshold CO2 | list | Threshold 1 < Threshold 2 < Threshold 3 |
| ! Conditions for thresholds | list | Threshold 1 < Threshold 2 < Threshold 3 |
| Threshold 1 CO2 (in 10 ppm) | unsignedInt 50…255 | 50 |
| Hysteresis | list | 200 ppm |
| Threshold 2 CO2 (in 10 ppm) | unsignedInt 50…255 | 120 |
| Threshold 3 CO2 (in 10 ppm) | unsignedInt 50…255 | 200 |
| Telegram type for threshold 1 CO2 | list | switching |
| If threshold 1 CO2 is exceeded | list | send following telegram once |
| Telegram | list | ON (down) |
| Telegram | unsignedInt 0…255 | 85 |
| Telegram | list | switch on |
| Telegram | list | 35 % |
| If threshold 1 CO2 is underrun | list | send following telegram once |
| Telegram | list | OFF (up) |
| Telegram | unsignedInt 0…255 | 0 |
| Telegram | list | switch off |
| Telegram | list | 0 % |
| Cycle time for threshold 1 CO2 (if used) | list | every 60 min. |
| Behaviour when setting the lock | list | ignore lock |
| Behaviour when releasing the lock | list | update |
| Telegram type for threshold 2 CO2 | list | switching |
| If threshold 2 CO2 is exceeded | list | send following telegram once |
| Telegram | unsignedInt 0…255 | 170 |
| Telegram | list | 70 % |
| If threshold 2 CO2 is underrun | list | send following telegram once |
| Cycle time for threshold 2 CO2 (if used) | list | every 60 min. |
| Telegram type for threshold 3 CO2 | list | switching |
| If threshold 3 CO2 is exceeded | list | send following telegram once |
| Telegram | unsignedInt 0…255 | 255 |
| Telegram | list | 100 % |
| If threshold 3 CO2 is underrun | list | send following telegram once |
| Cycle time for threshold 3 CO2 (if used) | list | every 60 min. |
| Send given Value | list | (Input in percent) |
| if CO2 below threshold 1 | list | 0 % |
| if CO2 below threshold 1 | unsignedInt 0…255 | 0 |
| if CO2 between thresholds 1 and 2 | list | 35 % |
| if CO2 between thresholds 1 and 2 | unsignedInt 0…255 | 85 |
| if CO2 between thresholds 2 and 3 | list | 70 % |
| if CO2 between thresholds 2 and 3 | unsignedInt 0…255 | 170 |
| if CO2 above threshold 3 | list | 100 % |
| if CO2 above threshold 3 | unsignedInt 0…255 | 255 |
| Value if locked (0-255) | unsignedInt 0…255 | 0 |
| Value if locked | list | 0 % |
| CO2 below threshold 1 | list | Scene 1 |
| CO2 between threshold 1 and 2 | list | Scene 2 |
| CO2 between threshold 2 and 3 | list | Scene 3 |
| CO2 above threshold 3 | list | Scene 4 |
| Scene if locked | list | Scene 1 |
| Threshold 1 relative humidity (in %) | unsignedInt 0…100 | 45 |
| Hysteresis | list | 1 % |
| Threshold 2 relative humidity (in %) | unsignedInt 0…100 | 55 |
| Threshold 3 relative humidity (in %) | unsignedInt 0…100 | 70 |
| Telegram type for threshold 1 humidity | list | switching |
| If threshold 1 humidity is exceeded | list | send following telegram once |
| If threshold 1 humidity is underrun | list | send following telegram once |
| Cycle time for threshold 1 humidity (if used) | list | every 60 min. |
| Telegram type for threshold 2 humidity | list | switching |
| If threshold 2 humidity is exceeded | list | send following telegram once |
| If threshold 2 humidity is underrun | list | send following telegram once |
| Cycle time for threshold 2 humidity (if used) | list | every 60 min. |
| If threshold 3 humidity is exceeded | list | send following telegram once |
| If threshold 3 humidity is underrun | list | send following telegram once |
| Cycle time for threshold 3 humidity (if used) | list | every 60 min. |
| if relative humidity below threshold 1 | list | 0 % |
| if relative humidity below threshold 1 | unsignedInt 0…255 | 0 |
| if relative humidity between threshold 1 and 2 | list | 35 % |
| if relative humidity between threshold 1 and 2 | unsignedInt 0…255 | 85 |
| if relative humidity between threshold 2 and 3 | list | 70 % |
| if relative humidity between threshold 2 and 3 | unsignedInt 0…255 | 170 |
| if rel. humidity above threshold 3 | list | 100 % |
| if rel. humidity above threshold 3 | unsignedInt 0…255 | 255 |
| rel. humidity below threshold 1 | list | Scene 1 |
| rel. humidity between threshold 1 and 2 | list | Scene 2 |
| rel. humidity between threshold 2 and 3 | list | Scene 3 |
| rel. humidity above threshold 3 | list | Scene 4 |
| Temperature threshold | list | 15 °C |
| Hysteresis | list | 1.5 °C |
| Telegram type for temperature-threshold | list | switching |
| If temperature-threshold is exceeded | list | send following telegram once |
| If temperature-threshold is underrun | list | send following telegram once |
| Cycle time for temperature threshold (if used) | list | every 60 min. |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| CO2-,Humidity-&Temp.Sensor 4216/1.2 1.2 latest | $FF21 | CFCD | 2026-11-25 | 110 KB | Download |
| CO2-,Humidity-&Temp.Sensor 4216/1.2 1.2 | $FF21 | CFCD | 2026-11-25 | 110 KB | Download |
About this file
This is the official ETS product database for the Schneider Electric Industries SAS KNX CO2, Humidity and Temperature Sensor (MTN6005-0001), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Schneider Electric Industries SAS
- Air Quality Multisensor MTN6005-0011
- KNX weather station basic MTN663990
- KNX brightness and temperature sensor MTN663991
- KNX weather station basic V2 MTN6904-0001
- KNX FUGA Multif. push-button, display, RTCU, PI 507Dx042
- KNX FUGA Movement detector 180 507Dx350
- KNX FUGA Push-button 4 switch + LED 507Dx611
- KNX OPUS Multif. push-button, display, RTCU, PI 507Nx042
- KNX OPUS Movement detector 180 507Nx350
- KNX OPUS Push-button 4 switch + LED 507Nx611
- KNX Presence 507Z6352
- KNX Presence Basic 507Z6353