KNX weather station basic MTN663990
Schneider Electric Industries SAS · Order number MTN663990 · 2.9 Physical Sensors › 2.9.01 Weather station
MTN663990
Download .knxprod Weather station 2420/1.2 1.2 · 209 KB
Product
| Manufacturer | Schneider Electric Industries SAS |
|---|---|
| Product name | KNX weather station basic |
| Order number | MTN663990 |
| Hardware | KNX Wetterstation Basic |
| Medium | Twisted Pair |
| Rail mounted | No |
| Registration | Certified |
| Languages | en-US, de-DE, fr-FR, da-DK, nl-NL, it-IT, sv-SE, es-ES |
| Catalog entry | M-0064_H-663990-1-O0048_HP-2420-12-493D-O0048_CI-MTN663990-1 |
| Fingerprint | 493D |
| SHA-256 | 331fa29bf8a456690f6e89b5d39a87873a5b58720e9ac26058dccecb196a05b3 |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: Weather station 2420/1.2 1.2
| Application number | $2420 |
|---|---|
| Version | 1.2 |
| Mask version | MV-0021 (2.1) |
| KNX Data Secure | No |
| Parameters | 348 |
| Group objects | 121 |
Group objects (121)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Brightness value | Physical value | 2 Bytes | CRT | |
| 1 | Temperature value | Physical value | 2 Bytes | CRT | |
| 2 | Wind speed | Physical value | 2 Bytes | CRT | |
| 3 | Rain sensor | Rain / no rain | 1 Bit | CRT | |
| 4 | C1.1 Universal channel | Priority | 2 Bit | CRT | |
| 4 | C1.1 Universal channel | value | 1 Byte | CRT | |
| 4 | C1.1 Universal channel | switch | 1 Bit | CRT | |
| 4 | C1.1 Brightness threshold | Priority | 2 Bit | CRT | |
| 4 | C1.1 Brightness threshold | value | 1 Byte | CRT | |
| 4 | C1.1 Brightness threshold | switch | 1 Bit | CRT | |
| 4 | C1 Safety | send | 1 Bit | CRT | |
| 4 | C1.1 Temperature threshold | Priority | 2 Bit | CRT | |
| 4 | C1.1 Temperature threshold | value | 1 Byte | CRT | |
| 4 | C1.1 Temperature threshold | switch | 1 Bit | CRT | |
| 5 | C1.2 Brightness threshold | value | 1 Byte | CRT | |
| 5 | C1.2 Brightness threshold | Priority | 2 Bit | CRT | |
| 5 | C1.2 Brightness threshold | switch | 1 Bit | CRT | |
| 5 | C1.2 Universal channel | value | 1 Byte | CRT | |
| 5 | C1.2 Universal channel | Priority | 2 Bit | CRT | |
| 5 | C1.2 Universal channel | switch | 1 Bit | CRT | |
| 5 | C1.2 Temperature threshold | value | 1 Byte | CRT | |
| 5 | C1.2 Temperature threshold | Priority | 2 Bit | CRT | |
| 5 | C1.2 Temperature threshold | switch | 1 Bit | CRT | |
| 6 | C1 lock | Input | 1 Bit | CRW | |
| 7 | C1 set brightn. threshold | Input | 1 Byte | CRW | |
| 8 | C2.1 Universal channel | value | 1 Byte | CRT | |
| 8 | C2.1 Universal channel | Priority | 2 Bit | CRT | |
| 8 | C2.1 Universal channel | switch | 1 Bit | CRT | |
| 8 | C2.1 Brightness threshold | value | 1 Byte | CRT | |
| 8 | C2.1 Brightness threshold | Priority | 2 Bit | CRT | |
| 8 | C2.1 Brightness threshold | switch | 1 Bit | CRT | |
| 8 | C2.1 Temperature threshold | value | 1 Byte | CRT | |
| 8 | C2.1 Temperature threshold | Priority | 2 Bit | CRT | |
| 8 | C2.1 Temperature threshold | switch | 1 Bit | CRT | |
| 8 | C2 Safety | send | 1 Bit | CRT | |
| 9 | C2.2 Universal channel | value | 1 Byte | CRT | |
| 9 | C2.2 Universal channel | Priority | 2 Bit | CRT | |
| 9 | C2.2 Universal channel | switch | 1 Bit | CRT | |
| 9 | C2.2 Brightness threshold | value | 1 Byte | CRT | |
| 9 | C2.2 Brightness threshold | Priority | 2 Bit | CRT | |
| 9 | C2.2 Brightness threshold | switch | 1 Bit | CRT | |
| 9 | C2.2 Temperature threshold | value | 1 Byte | CRT | |
| 9 | C2.2 Temperature threshold | Priority | 2 Bit | CRT | |
| 9 | C2.2 Temperature threshold | switch | 1 Bit | CRT | |
| 10 | C2 lock | Input | 1 Bit | CRW | |
| 11 | C2 set brightn. threshold | Input | 1 Byte | CRW | |
| 12 | C3 up/down | drives up/down | 1 Bit | CT | |
| 13 | C3 Blinds | Height | 1 Byte | CRT | |
| 13 | C3 Shutter | Height | 1 Byte | CRT | |
| 13 | C3 send value | value | 1 Byte | CRT | |
| 13 | C3 Scene 1+2 | send | 1 Bit | CRT | |
| 14 | C3 Slats | Position | 1 Byte | CRT | |
| 14 | C3 Scene 3+4 | send | 1 Bit | CRT | |
| 15 | C3 Sun control | Morning=1 / Evening=0 | 1 Bit | CRW | |
| 16 | C3 Safety | Input | 1 Bit | CRW | |
| 17 | C3 Teach in | Input | 1 Byte | CW | |
| 18 | C4.1 Universal channel | value | 1 Byte | CRT | |
| 18 | C4.1 Universal channel | Priority | 2 Bit | CRT | |
| 18 | C4.1 Universal channel | switch | 1 Bit | CRT | |
| 18 | C4.1 Brightness threshold | value | 1 Byte | CRT | |
| 18 | C4.1 Brightness threshold | Priority | 2 Bit | CRT | |
| 18 | C4.1 Brightness threshold | switch | 1 Bit | CRT | |
| 18 | C4.1 Temperature threshold | value | 1 Byte | CRT | |
| 18 | C4.1 Temperature threshold | Priority | 2 Bit | CRT | |
| 18 | C4.1 Temperature threshold | switch | 1 Bit | CRT | |
| 18 | C4 Safety | send | 1 Bit | CRWT | |
| 19 | C4.2 Universal channel | value | 1 Byte | CRT | |
| 19 | C4.2 Universal channel | Priority | 2 Bit | CRT | |
| 19 | C4.2 Universal channel | Switch | 1 Bit | CRT | |
| 19 | C4.2 Brightness threshold | value | 1 Byte | CRT | |
| 19 | C4.2 Brightness threshold | Priority | 2 Bit | CRT | |
| 19 | C4.2 Brightness threshold | Switch | 1 Bit | CRT | |
| 19 | C4.2 Temperature threshold | value | 1 Byte | CRT | |
| 19 | C4.2 Temperature threshold | Priority | 2 Bit | CRT | |
| 19 | C4.2 Temperature threshold | Switch | 1 Bit | CRT | |
| 20 | C4 lock | Input | 1 Bit | CRW | |
| 21 | C4 set brightn. threshold | Input | 1 Byte | CRW | |
| 22 | C5.1 Universal channel | Priority | 2 Bit | CRT | |
| 22 | C5.1 Universal channel | Switch | 1 Bit | CRT | |
| 22 | C5.1 Universal channel | value | 1 Byte | CRT | |
| 22 | C5.1 Brightness threshold | Priority | 2 Bit | CRT | |
| 22 | C5.1 Brightness threshold | Switch | 1 Bit | CRT | |
| 22 | C5.1 Brightness threshold | value | 1 Byte | CRT | |
| 22 | C5.1 Temperature threshold | Priority | 2 Bit | CRT | |
| 22 | C5.1 Temperature threshold | Switch | 1 Bit | CRT | |
| 22 | C5.1 Temperature threshold | value | 1 Byte | CRT | |
| 22 | C5 Safety | send | 1 Bit | CRT | |
| 23 | C5.2 Universal channel | Priority | 2 Bit | CRT | |
| 23 | C5.2 Universal channel | Switch | 1 Bit | CRT | |
| 23 | C5.2 Universal channel | value | 1 Byte | CRT | |
| 23 | C5.2 Brightness threshold | Priority | 2 Bit | CRT | |
| 23 | C5.2 Brightness threshold | Switch | 1 Bit | CRT | |
| 23 | C5.2 Brightness threshold | value | 1 Byte | CRT | |
| 23 | C5.2 Temperature threshold | Priority | 2 Bit | CRT | |
| 23 | C5.2 Temperature threshold | Switch | 1 Bit | CRT | |
| 23 | C5.2 Temperature threshold | value | 1 Byte | CRT | |
| 24 | C5 lock | Input | 1 Bit | CRW | |
| 25 | C5 set brightn. threshold | Input | 1 Byte | CRW | |
| 26 | C6 up/down | drives up/down | 1 Bit | CT | |
| 27 | C6 Scene 1+2 | send | 1 Bit | CRT | |
| 27 | C6 Shutter | Height | 1 Byte | CRT | |
| 27 | C6 Value | value | 1 Byte | CRT | |
| 27 | C6 Blinds | Height | 1 Byte | CRT | |
| 28 | C6 Slats | Position | 1 Byte | CRT | |
| 28 | C6 Scene 3+4 | send | 1 Bit | CRT | |
| 29 | C6 Sun control | Morning=1 / Evening=0 | 1 Bit | CRW | |
| 30 | C6 Safety | Input | 1 Bit | CRW | |
| 31 | C6 remote brightn. Val. | Input | 2 Bytes | CRW | |
| 32 | C6 Teach in | Input | 1 Byte | CW | |
| 33 | C7 up/down | drives up/down | 1 Bit | CT | |
| 34 | C7 Scene 1+2 | send | 1 Bit | CRT | |
| 34 | C7 Value | value | 1 Byte | CRT | |
| 34 | C7 Shutter | Height | 1 Byte | CRT | |
| 34 | C7 Blinds | Height | 1 Byte | CRT | |
| 35 | C7 Slats | Position | 1 Byte | CRT | |
| 35 | C7 Scene 3+4 | send | 1 Bit | CRT | |
| 36 | C7 Sun control | Morning=1 / Evening=0 | 1 Bit | CRW | |
| 37 | C7 Safety | Input | 1 Bit | CRW | |
| 38 | C7 remote bright. Val. | Input | 2 Bytes | CRW | |
| 39 | C7 Teach in | Input | 1 Byte | CW | |
| 40 | Brightness thresholds | report | 2 Bytes | CT |
Parameters (116)
| Parameter | Type | Default |
|---|---|---|
| Send wind speed value on change of | list | 20 %, but at least 1 m/s |
| Send wind speed in | list | m/s |
| Send wind speed value cyclically | list | don´t send cyclically |
| Send brightness value on change of | list | 30 %, but at least 1 lx |
| Send brightness value cyclically | list | don´t send cyclically |
| Send temperature on change of | list | 1.0 °C |
| Send temperature cyclically | list | don´t send cyclically |
| Temperature offset in 1/10°C (-64 .. 64) | signedInt -64…64 | 0 |
| Send rain on change | list | yes |
| Send rain on change and | list | not cyclically |
| Delay after rain stop | list | 5 minutes |
| Function of C1 | list | Brightness sensor 2 .. 100,000 lx |
| Function of C2 | list | Temperature sensor |
| Function of C3 | list | Sun protection |
| Use more channels? | list | no |
| Function of C4 | list | Universal channel |
| Function of C5 | list | Safety |
| Function of C6 | list | Sun protection |
| Function of C7 | list | Sun protection |
| IF brightness: | list | above 10000 lx |
| Brightness condition: | list | above 10000 lx |
| Hysteresis light | list | 20 %, but at least 1 lx |
| Delay on increasing brightness | list | 3 minutes |
| Delay on decreasing brightness | list | 10 minutes |
| AND wind: | list | don´t care |
| Wind condition | list | don´t care |
| Safety telegram(ON) in the event of wind | list | above 5 m/s (18 km/h) |
| Off-delay wind | list | 3 minutes |
| AND temperature | list | above 18°C |
| Temperature condition | list | above 18°C |
| OR temperature | list | below 5°C |
| Hysteresis temperature | list | 1.0 °C |
| AND rain condition (off-delay fixed 1 min.) | list | no rain |
| Rain condition | list | no rain |
| OR rain condition | list | Rain |
| Delay rain | list | 1 minute |
| Telegram type C1.1 | list | Switching |
| If all conditions are met | list | Send following telegram once |
| If the condition is met | list | Send following telegram once |
| If safety condition is met | list | Send following telegram once |
| Telegram | list | Switch on |
| Telegram | list | Priority, ON (down) |
| Telegram | unsignedInt 0…255 | 255 |
| If not all conditions are met | list | Send following telegram once |
| If the condition is not met | list | Send following telegram once |
| If safety condition is not met | list | Send following telegram once |
| Telegram | list | Priority, OFF (up) |
| Telegram | list | Switch off |
| Telegram | unsignedInt 0…255 | 0 |
| Cycle time for C1 (if used) | list | Every 60 min. |
| Send safety telegram cyclically | list | Every 60 min. |
| Behaviour when setting the lock | list | Ignore lock |
| Behaviour when releasing the lock | list | Update channel |
| Should a second telegram be sent? | list | no |
| Telegram type C1.2 | list | Switching |
| If not all conditions are met | list | Send following telegram once |
| Wind condition: | list | don´t care |
| Safety telegram (ON) in the event of wind | list | above 5 m/s (18 km/h) |
| Rain condition (off-delay fixed 1 min.) | list | no rain |
| OR | list | Rain |
| Telegram type C2.1 | list | Switching |
| Cycle time (if used) | list | Every 60 min. |
| Should a second telegram be sent? | list | no |
| Telegram type C2.2 | list | Switching |
| Light measurement through | list | internal sensor |
| Twilight threshold | list | 10 lx |
| How many brightness thresholds? | list | 3 thresholds |
| Brightness threshold 1 | list | 20000 lx |
| Brightness threshold 2 | list | 30000 lx |
| Brightness threshold 3 | list | 45000 lx |
| Delay when brightness increases | list | 3min. |
| Delay when brightness decreases | list | 15min. |
| Telegram type | list | Blinds |
| Activation of sun control | list | through object |
| Reaction to sun control ON | list | move up & sun control ON |
| Reaction to dawn | list | move up & sun control ON |
| Drive height from threshold 1 | list | 80% |
| Telegram between threshold 1 and 2 | list | Scene 2 |
| Telegram above threshold 1 | list | Scene 2 |
| Telegram between threshold 1 and 2 | unsignedInt 0…255 | 10 |
| Telegram above threshold 1 | unsignedInt 0…255 | 10 |
| Turn slats between threshold 1 and 2 | list | 40% |
| Turn slats above threshold 1 | list | 40% |
| Drive height between threshold 1 and 2 | list | 40% |
| Drive height above threshold 1 | list | 40% |
| Telegram between threshold 2 and 3 | list | Scene 3 |
| Telegram above threshold 2 | list | Scene 3 |
| Telegram between threshold 2 and 3 | unsignedInt 0…255 | 20 |
| Telegram above threshold 2 | unsignedInt 0…255 | 20 |
| Turn slats between threshold 2 and 3 | list | 60% |
| Turn slats above threshold 2 | list | 60% |
| Drive height between threshold 2 and 3 | list | 60% |
| Drive height above threshold 2 | list | 60% |
| Telegram above threshold 3 | list | Scene 4 |
| Telegram above threshold 3 | unsignedInt 0…255 | 30 |
| Turn slats above threshold 3 | list | 75% |
| Drive height above threshold 3 | list | 75% |
| Reaction to sun control OFF | list | Sun control OFF & move up |
| Reaction to dusk | list | Sun control OFF & move up |
| Safety check triggered by | list | through object safety |
| Reaction to safety beginning | list | no reaction |
| Reaction to safety end | list | Update position |
| Helligkeitsbedingung: | list | above 10000 lx |
| Telegram type C4.1 | list | Switching |
| Telegram type C4.2 | list | Switching |
| Telegram type C5.1 | list | Switching |
| Telegram type C5.2 | list | Switching |
| Drive height between threshold 1 and 2 | list | 30% |
| Drive height above threshold 1 | list | 30% |
| Turn slats between threshold 1 and 2 | list | 30% |
| Turn slats above threshold 1 | list | 30% |
| Drive height above threshold 3 | list | 80% |
| Turn slats above threshold 3 | list | 80% |
| Telegramm über Schwelle 1 | list | Scene 2 |
| Temperature limit heating resistance with +30K offset: 80 = 50°C | unsignedInt 40…80 | 70 |
| Value $AA, so that Controller recognises that Application had to be downloaded | unsignedInt 0…255 | 170 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Weather station 2420/1.2 1.2 latest | $2420 | 493D | 2026-11-25 | 209 KB | Download |
About this file
This is the official ETS product database for the Schneider Electric Industries SAS KNX weather station basic (MTN663990), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Schneider Electric Industries SAS
- KNX CO2, Humidity and Temperature Sensor MTN6005-0001
- Air Quality Multisensor MTN6005-0011
- KNX brightness and temperature sensor MTN663991
- KNX weather station basic V2 MTN6904-0001
- KNX FUGA Multif. push-button, display, RTCU, PI 507Dx042
- KNX FUGA Movement detector 180 507Dx350
- KNX FUGA Push-button 4 switch + LED 507Dx611
- KNX OPUS Multif. push-button, display, RTCU, PI 507Nx042
- KNX OPUS Movement detector 180 507Nx350
- KNX OPUS Push-button 4 switch + LED 507Nx611
- KNX Presence 507Z6352
- KNX Presence Basic 507Z6353