Room Temperature and Relative Humidity Controller SATION-PM1421.8601

SATION · Order number SATION-PM1421.8601 · Heating, air-con., ventilation › Thermostat

FanCoil Display Operate Control/1.2

Download .knxprod Room Temperature and Relative Humidity Controller 1.3 · 118 KB

Product

ManufacturerSATION
Product nameRoom Temperature and Relative Humidity Controller
Order numberSATION-PM1421.8601
HardwareRoom temperature controller
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationRegistered · 2017-12-07
Languagesen-US, zh-CN
Catalog entryM-017A_H-07.2F6138-1_HP-6138-13-F737-O017A_CI-SATION.2DPM1421.2E8601-1
FingerprintF737
SHA-256deb2fb646df9fb03878c634b4eca9ebe5618c4ac0c8d37ee9c511b8519acc69f
First seen2026-11-25
Markets65 markets

Application program: Room Temperature and Relative Humidity Controller 1.3

Application number$6138
Version1.3
Mask versionMV-0701 (7.1)
KNX Data SecureNo
Minimum ETS version4.0
Parameters240
Group objects74
Group objects (74)
NoNameFunctionSizeDPTFlags
0In OperationGeneral1 Bit1.11 stateCT
0GeneralIn Operation1 Bit1.11 stateCT
1GeneralUnit On/Off1 Bit1.1 switchCRWT
2GeneralSwitch °C/°F display unit1 Bit1.1 switchCRW
3GeneralIllumination On/Off1 Bit1.1 switchCW
4ControlFrost/heat protection1 Bit1.1 switchCRW
5ControlActivate night mode1 Bit1.1 switchCRW
6ControlUser absent1 Bit1.1 switchCRWT
7ControlOperating mode switchover1 Byte20.102 HVAC modeCRWT
8ControlOperating mode switchover requ1 Byte20.102 HVAC modeCRW
9Temperature sensorSend actual value2 Bytes9.1 temperature (°C)CRT
10Temperature recordingInput current exterior tempera2 Bytes9.1 temperature (°C)CW
11Temperature recordingInput exterior temperature2 Bytes9.1 temperature (°C)CW
12ControlCurrent setpoint cooling2 Bytes9.1 temperature (°C)CRWT
13ControlCurrent setpoint heating2 Bytes9.1 temperature (°C)CRWT
14ControlBase setpoint2 Bytes9.1 temperature (°C)CRW
15ControlHeating setpoint comfort2 Bytes9.1 temperature (°C)CRW
16ControlHeating setpoint standby2 Bytes9.1 temperature (°C)CRW
17ControlHeating setpoint night mode2 Bytes9.1 temperature (°C)CRW
18ControlSetpoint frost protection2 Bytes9.1 temperature (°C)CRW
19ControlCooling setpoint comfort2 Bytes9.1 temperature (°C)CRW
20ControlCooling setpoint standby2 Bytes9.1 temperature (°C)CRW
21ControlCooling setpoint night mode2 Bytes9.1 temperature (°C)CRW
22ControlSetpoint heat protection2 Bytes9.1 temperature (°C)CRW
23ControlReset of local operation1 Bit1.15 resetCW
24Control valueControl value heating1 Byte21.2 device controlCRT
24Control valueControl value heating1 Bit1.1 switchCRT
24Control valueControl value heat/cool1 Bit1.1 switchCRT
24Control valueControl value heat/cool1 Byte21.2 device controlCRT
24Control valueControl value heating1 Byte21.2 device controlCW
24Control valueControl value heating1 Bit1.1 switchCW
24Control valueControl value heat/cool1 Bit1.1 switchCW
24Control valueControl value heat/cool1 Byte21.2 device controlCW
25Control valueControl value cooling1 Byte21.2 device controlCRT
25Control valueControl value cooling1 Bit1.1 switchCRT
25Control valueControl value cooling1 Byte21.2 device controlCW
25Control valueControl value cooling1 Bit1.1 switchCW
26Control valueContr. value add. heat. stage1 Bit1.1 switchCRT
26Control valueContr. value add. heat. stage1 Byte21.2 device controlCRT
27Control valueContr. value add. cool. stage1 Bit1.1 switchCRT
27Control valueContr. value add. cool. stage1 Byte21.2 device controlCRT
28Control valueStatus heat requirement1 Bit1.11 stateCRT
28Control valueStatus heat requirement1 Bit1.11 stateCW
29Control valueStatus cooling requirement1 Bit1.11 stateCRT
29Control valueStatus cooling requirement1 Bit1.11 stateCW
30Heat/CoolHeat/cool switchover1 Bit1.100 heating/coolingCRWT
30Heat/CoolHeat/cool switchover1 Bit1.100 heating/coolingCW
31Fan automatic / manualManual On/Off1 Bit1.3 enableCRWT
31Fan automatic / manualAutomatic On/Off1 Bit1.3 enableCRWT
32Fan manualFan stage manual 1 byte1 Byte5.1 percentage (0..100%)CRWT
33Status FanCoil operationStatus operating state of FanCoil1 Byte5.10 counter pulses (0..255)CW
34Fan manualSwitch FanCoil level 11 Bit1.1 switchCRWT
35Fan manualSwitch FanCoil level 21 Bit1.1 switchCRWT
36Fan manualSwitch FanCoil level 31 Bit1.1 switchCRWT
37Actuator monitoringReceive in operation1 Bit1.17 triggerCW
39Dew-point monitoringSignal dew point1 Bit1.17 triggerCW
40Monitoring of condensate tankSignal condensate tank1 Bit1.17 triggerCW
41Alarm temperatureReport failure of current temp1 Bit1.5 alarmCRT
42Alarm temperatureReport failure of ext. temp.1 Bit1.5 alarmCRT
43Status byteStatus byte RHCC status2 Bytes22.101 RHCC statusCRT
44Status byteStatus byte HVAC status1 Byte20.102 HVAC modeCRT
45ControlSummer compensation active1 Bit1.17 triggerCRT
46ControlWinter compensation active1 Bit1.17 triggerCRT
47Status FanCoil operationStatus stage 11 Bit1.11 stateCW
48Status FanCoil operationStatus stage 21 Bit1.11 stateCW
49Status FanCoil operationStatus stage 31 Bit1.11 stateCW
50Humidity sensor(2 bytes)Send actual value(2 bytes)2 Bytes9.7 humidity (%)CRT
51Humidity recordingInput current exterior humi.2 Bytes9.7 humidity (%)CWU
52Dehumidification controlDehumidification command1 Bit1.1 switchCRT
53Dehumidification controlDehumi. control disable1 Bit1.3 enableCW
54Dehumidification controlHumidity setpoint for dehumi.2 Bytes9.7 humidity (%)CRWTU
55Humidification controlHumidification command1 Bit1.1 switchCRT
56Humidification controlHumidification control disable1 Bit1.3 enableCW
57Humidification controlHumidity setpoint for humidi.2 Bytes9.7 humidity (%)CRWTU
Parameters (118)
ParameterTypeDefault
Send "In operation" objectlistNo
Send cycle time in s [1...65.535]unsignedInt 1…6553560
Display selection temperature °C/°F or humidity %listOnly temperature °C
Display during normal operationlistAbsolute setpoint temperature
Display in adjusting modelistAbsolute setpoint temperature
Display heat/cool is activelistWhen requesting heating or cooling
Display illuminationlist15 seconds recovery time
Operating mode switchoverlist1 Byte (2 x DPT_HVAC mode)
Enable switchover of comfort/standby via button On/OfflistNo
Operation mode after resetlistComfort operation
Offset for room temp. meas. (measured value change by (-128..127)x0.1 KsignedInt -128…1270
Send actual value if change is larger thanlistInactive
Send actual value cyclically (0 - inactive, min)unsignedInt 0…600
Measurement of room temperaturelistInterior
Weighting interior / exteriorlist50 % / 50 %
Monitoring temperature measurementlistNo
Control value at temp. measuring errorlistFinal value
Monitoring time exterior temperature (0 - inactive, min)unsignedInt 0…6010
Monitoring time external temperature (0 - inactive, min)unsignedInt 0…6010
Offset for ext. temp. meas. (measured value change by (-128..127)x0.1 KsignedInt -128…1270
Operating mode of unitlistNormal operation with control function
Used control functionslistHeat and cool
Switchover between heating and coolinglistAutomatic
Additional heating stage activelistNo
Additional cooling stage activelistNo
Condensate alarm activelistNo
Dew-point alarm activelistNo
Operation mode after resetlistHeating
Number of output channelslist2 channels (four-pipe system) for heat / cool
Status send heat requirementlistNo
Cycle time heating control value sending (0 - inactive, min)unsignedInt 0…600
Control modelistFanCoil
Hysteresislist1,0 K
Invert heatinglistNo
Control parameterlistAcc. to installation type
Type of heating systemlistSplit unit (4 K / 90 min)
Proportional range (Xp)list4,0 K
Readjust time (Tn)list90 min
Minimum control valuelist0%
Maximum control valuelist100%
Control value larger when sending changelist0%
Readjust timelist90 min
Cycle time PWM control value (min)unsignedInt 1…6015
PWM cycle is 0% up to control valuelist10%
PWM cycle is 100 % up to control valuelist90%
Status send cooling requirementlistNo
Cycle time cooling control value sending (0 - inactive, min)unsignedInt 0…600
Invert coolinglistNo
Type of cooling systemlistSplit unit (blower convector 4 K / 90 min)
Cycle time PWM control value(min)unsignedInt 1…6015
Type of control valuelistSwitching (1 Bit)
Invert control valuelistNo
Hysteresis (one-sided)list1,0 K
Cycle time for sending of control value (0 - inactive, min)unsignedInt 0…600
Interval of additional level (value change by (0..127)x0.1 KunsignedInt 0…12730
Setpoint larger when sending changelistInactive
Cyclic sending of setpoint (0 - inactive, min)unsignedInt 0…600
Cycle time sending of setpoint (0 - inactive, min)unsignedInt 0…600
Select base setpointlistDependent setpoints
Reference base setpointlistSetpoint heating
Manual setpoint adjustment at reset of change from night / to nightlistYes
Manual setpoint adjustmentlistActive
Maximum manual setpoint increaseunsignedInt 0…103
Maximum manual setpoint reductionunsignedInt 0…103
Object reset manual setpoint adjustment activelistNo
When receiving base setpointlistRetain manual setpoint adjustment
Range manual setpoint adjustmentlist0,5 K
Long press of button to enable change of setpoint heating / coolinglistNo
Heating setpoint comfort modelist21,0 °C
Heating setpoint standby modelist19,0 °C
Heating setpoint night modelist15,0 °C
Cooling setpoint comfort modelist23,0 °C
Cooling setpoint standby modelist25,0 °C
Cooling setpoint night modelist27,0 °C
Setpoint frost protectionlist7 °C
Setpoint heat protectionlistCooling disabled
Minimum distance between heating setpoint and cooling setpointlist2,0 K
Heating setpoint reduction standbylist2,0 K
Heating setpoint reduction night operationlist4,0 K
Cooling setpoint increase standbylist2,0 K
Cooling setpoint increase night modelist4,0 K
Number of fan levelslist3 levels
Manual operation of fan stage is signaled to the actuator vialistObject "Automatic ON/OFF"
Object manual fan stage send hat has the following codelist1-Byte object as counting value 0-3
Evaluate status byte fan stagelistNo
Evaluate status byte operationlistNo
Send cycle time of actuator in s [1...65.535]unsignedInt 1…65535120
Stage of fan after resetlistAutomatic
Stage limit in night modelistNo limit
Automatic return from manual adjustment (0 - inactive, min)unsignedInt 0…600
Return inactive a fan stage off and automatic return not 0listYes
Threshold value stage 1unsignedInt 1…10010
Threshold value stage 2unsignedInt 1…10040
Threshold value stage 3unsignedInt 1…10070
Summer compensation activelistNo
Summer compensation lower exterior temp. valuelist20 °C
Summer compensation upper exterior temp. valuelist32 °C
Summer compensation lower setpoint offsetlist0 K
Summer compensation upper setpoint offsetlist4 K
Winter compensation activelistNo
Winter compensation lower exterior temp. valuelist0 °C
Winter compensation upper exterior temp. valuelist10 °C
Winter compensation lower setpoint offsetlist4 K
Winter compensation upper setpoint offsetlist0 K
Offset for room humi. meas. (measured value change by (-128..127)x0.1 %signedInt -128…1270
Measurement of room relative humiditylistInterior
Offset for ext. humi. meas. (measured value change by (-128..127)x0.1 %signedInt -128…1270
Display humidity in normal modelistCurrent actual value
Manual setpoint adjustmentlistDisabled
Range manual setpoint adjustmentlist3.0 %
Dehumidification functionlistdisabled
Humidity setpointunsignedInt 20…8055
Humidity hysteresislist0.8 %
Cyclic sending of control value (0 - inactive,min)unsignedInt 0…600
Disable dehumid. control from buslistNo
Humidification functionlistdisabled
Humidity setpointunsignedInt 20…8035
Disable humidification control from buslistNo

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Room Temperature and Relative Humidity Controller 1.3 latest$6138F7372026-11-25118 KBDownload

About this file

This is the official ETS product database for the SATION Room Temperature and Relative Humidity Controller (SATION-PM1421.8601), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.