KNX Database

SATION-SS3001.1 PIR Presence Detector SATION-SS3001

SATION · Order number SATION-SS3001 · Presence Detector › Ceiling

Presence Detector 360° Ceiling 1 Sensor

Download .knxprod Presence Detector 360 Ceiling 0.2 · 93 KB

Product

ManufacturerSATION
Product nameSATION-SS3001.1 PIR Presence Detector
Order numberSATION-SS3001
HardwarePIR Presence Detector
MediumTwisted Pair
Bus current (mA)10
Rail mountedYes
Width (mm)80
RegistrationCertified · 2016-04-01
Languagesen-US
Catalog entryM-017A_H-3001-1_HP-3001-02-C429_CI-SATION.2DSS3001-1
FingerprintC429
SHA-25621044b029c8cf8ddafcc2fc7ae011d6466744d92b541db1dca79b7c0e3e31f8c
First seen2026-11-25
Markets65 markets

Application program: Presence Detector 360 Ceiling 0.2

Application number$3001
Version0.2
Mask versionMV-0701 (7.1)
KNX Data SecureNo
Minimum ETS version3.0d
Parameters138
Group objects35
Group objects (35)
NoNameFunctionSizeDPTFlags
0Output - light group 1Switching1 Bit1.1 switchCRT
0Output - light group 1Dimming absolute1 Byte5.1 percentage (0..100%)CRT
0Output - light group 1Scene1 Byte5.1 percentage (0..100%)CRT
1Output - light group 1 night modeSwitching1 Bit1.1 switchCRT
2External input - light group 1Switching1 Bit1.1 switchCW
3Input external movement - light group 1Switching1 Bit1.1 switchCW
4Input light group 1Lock1 Bit1.3 enableCW
4Input light group 1Force control2 Bit2.1 switch controlCW
5Input light group 1Lock object On1 Bit1.3 enableCW
6reserve object2 Bytes
7Output - climate (HCV)Switching1 Bit1.1 switchCRT
7Output - climate (HCV)Dimming absolute1 Byte5.1 percentage (0..100%)CRT
7Output - climate (HCV)Scene1 Byte5.1 percentage (0..100%)CRT
7Output - climate (HCV)Value1 Byte5.1 percentage (0..100%)CRT
8Output - climate (HCV) night modeSwitching1 Bit1.1 switchCRT
9External Input - climate (HCV)Switching1 Bit1.1 switchCW
10External movement - climate (HCV)Switching1 Bit1.1 switchCW
11Input - climate (HCV)Force control2 Bit2.1 switch controlCW
11Input - climate (HCV)Lock1 Bit1.3 enableCW
12Input - climate (HCV)Lock object On1 Bit1.3 enableCW
13reserve object1 ByteCW
14Input Day / Night Switching1 Bit1.2 booleanCWT
15Presence Switching1 Bit1.1 switchCRT
16Threshold switch brightnessSwitching1 Bit1.1 switchCRT
17Brightness valueBrightness value2 Bytes9.4 lux (Lux)CRT
18Input TeachInCalibration start1 Bit1.1 switchCW
19Input TeachInStatus absolute dimming value1 Byte5.1 percentage (0..100%)CW
20Output heartbeatStatus1 BitCRT
21Temperature valueTemperature value2 Bytes9.1 temperature (°C)CRT
22dummy 1 Bit
23dummy 1 Bit
24dummy 1 Bit
25dummy 1 Bit
26dummy 1 Bit
27dummy 1 Bit
Parameters (80)
ParameterTypeDefault
EinschaltverzögerungunsignedInt 0…2552
Day / Night objectlistused, read after reset
Day / Night object: value=0 / value=1listDay / Night
cyclical sending of presencelistnot used
presence info functionlistnot used
movement active sensitivity(1 = min,10 = max,def. = 5)list5
force control release timelistnot used
cyclical sending "heartbeat"listnot used
not visiblelist0
select groupslistOne light group
Anzahl der BeobachtungszeitfensterunsignedInt 0…2550
Länge des Beobachtungszeitfensters (s)unsignedInt 0…300000
operating mode of detectorlistfully automatic
LEDlistshow movement
follow-up timelist5 min
lower enable brightness thresholdlist2000 Lux (independent of brightness)
upper disable brightness thresholdlistnot used
force or lock objectlistforce control object
lock object value = 1listlock (actual state)
lock object value = 0listautomatic mode
object type for output - lightlistSwitching
object value for OnlistON
object value for OfflistOFF
switching object send atlistOn and Off
object value for Onlist100%
object value for Offlist0%
standby / orientationlightlistnot used
standby timelistno delay
standby dimming valuelist1%
object value for Onlistscene 1
object value for Offlistscene 2
cyclical sending of object value ONlistnot used
external input reacts onlistOn and Off
idle time after switch offlist10 s
LEDlistdisabled
object value on day for OnlistON
object value on day for OfflistOFF
number of monitoring time slotlist3
length of monitoring time slot (s)unsignedInt 0…3000030
object type for output - climate (HCV)listSwitching
object value on night for OnlistON
object value on night for OfflistOFF
object value on night for Onlist100%
object value on night for Offlist0%
standby / orientationlightlistused
standby time on daylistno delay
standby dimming value on daylist0%
standby time on nightlistno delay
standby dimming value on nightlist0%
object value for Onlistscene 5
object value for Offlistscene 6
object value on night for Onlistscene 7
object value on night for Offlistscene 8
use 2. switch object for nightlistNo
Sensor Aktivierung bei Unterschreitung vonlistnot used
send brightness on change oflist50 Lux
cyclical sending of light valuelistnot used
value for switching the threshold switchlist300 Lux
hysteresis of threshold switchlist30 Lux
send filterlistOn and Off
object value on day for Onlist100%
object value on day for Offlist0%
object value on night for Onlist50%
standby dimming value on daylist1%
standby dimming value on nightlist1%
object value on day for Onlistscene 1
object value on day for Offlistscene 2
object value on night for Onlistscene 3
object value on night for Offlistscene 4
LEDlistOff
object value on day for Onlistscene 5
object value on day for Offlistscene 6
send on day onlylistOn and Off
send on night onlylistOn and Off
offset brightness [Lux]signedInt -100…1000
room reflection factorlist0,4 medium
teachIn brightness value [Lux]unsignedInt 200…1000450
use teachIn value at application downloadlistuse factory default values
Anzahl der Messungen für MittelwertunsignedInt 0…2552
cyclical sending of temperaturelistnot used

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Presence Detector 360 Ceiling 0.2 latest$3001C4292026-11-2593 KBDownload

About this file

This is the official ETS product database for the SATION SATION-SS3001.1 PIR Presence Detector (SATION-SS3001), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from SATION