KNX Database
Satel sp. z o.o. KNX-SA41 KNX-SA41.230.16.1

KNX-SA41.230.16.1 KNX-SA41

Satel sp. z o.o. · Order number KNX-SA41 · Switch Actuator

Download .knxprod Universal Switch Actuator 4CH 1.3 · 205 KB

Product

ManufacturerSatel sp. z o.o.
Product nameKNX-SA41.230.16.1
Order numberKNX-SA41
Hardwareknx-sa41_hw
MediumTwisted Pair
Bus current (mA)10
Rail mountedYes
Width (mm)720
RegistrationCertified · 2016-08-11
Languagespl-PL, en-US, de-DE, it-IT, nl-NL, ru-RU, sk-SK
Catalog entryM-0144_H-2-1_HP-0002-13-8206_CI-KNX.2DSA41-2
Fingerprint8206
SHA-2564dcf31920b5e3a6192ee0f95d2034f1586e8ea186e99dabe6b74935a207b5b7c
First seen2026-11-25
Markets35 markets

Application program: Universal Switch Actuator 4CH 1.3

Application number$0002
Version1.3
Mask versionMV-07B0 (System B)
KNX Data SecureNo
Minimum ETS version5.0
Parameters352
Group objects81
Group objects (81)
NoNameFunctionSizeDPTFlags
1GeneralDevice operation status1 Bit1.1 switchCRT
2CentralSwitch function1 Bit1.1 switchCW
3SafetySafety priority 11 Bit1.1 switchCW
4SafetySafety priority 21 Bit1.1 switchCW
5SafetySafety priority 31 Bit1.1 switchCW
6Channel A Switch1 Bit1.1 switchCW
7Channel AChannel status1 Bit1.1 switchCRT
8Channel ALogic 11 Bit1.2 booleanCW
9Channel ALogic 21 Bit1.2 booleanCW
10Channel ALogic 31 Bit1.2 booleanCW
11Channel ADisable time functions1 Bit1.3 enableCW
12Channel AStaircase duration2 Bytes7.5 time (s)CW
13Channel AStaircase warning1 Bit1.1 switchCRT
14Channel AScene1 Byte18.1 scene controlCW
15Channel AInput for threshold value1 Byte5.10 counter pulses (0..255)CW
15Channel AInput for threshold value2 Bytes7.1 pulsesCW
16Channel ASet value for threshold 11 Byte5.10 counter pulses (0..255)CW
16Channel ASet value for threshold 12 Bytes7.1 pulsesCW
17Channel ASet value for threshold 21 Byte5.10 counter pulses (0..255)CW
17Channel ASet value for threshold 22 Bytes7.1 pulsesCW
18Channel ACall scene 1-bit1 Bit1.1 switchCW
19Channel ASet scene 1-bit1 Bit1.1 switchCW
20Channel AForced state 11 Bit1.1 switchCW
21Channel AForced state 21 Bit1.1 switchCW
22Channel BSwitch1 Bit1.1 switchCW
23Channel BChannel status1 Bit1.1 switchCRT
24Channel BLogic 11 Bit1.2 booleanCW
25Channel BLogic 21 Bit1.2 booleanCW
26Channel BLogic 31 Bit1.2 booleanCW
27Channel BDisable time functions1 Bit1.3 enableCW
28Channel BStaircase duration2 Bytes7.5 time (s)CW
29Channel BStaircase warning1 Bit1.1 switchCRT
30Channel BScene1 Byte18.1 scene controlCW
31Channel BInput for threshold value1 Byte5.10 counter pulses (0..255)CW
31Channel BInput for threshold value2 Bytes7.1 pulsesCW
32Channel BSet value for threshold 11 Byte5.10 counter pulses (0..255)CW
32Channel BSet value for threshold 12 Bytes7.1 pulsesCW
33Channel BSet value for threshold 21 Byte5.10 counter pulses (0..255)CW
33Channel BSet value for threshold 22 Bytes7.1 pulsesCW
34Channel BCall scene 1-bit1 Bit1.1 switchCW
35Channel BSet scene 1-bit1 Bit1.1 switchCW
36Channel BForced state 11 Bit1.1 switchCW
37Channel BForced state 21 Bit1.1 switchCW
38Channel CSwitch1 Bit1.1 switchCW
39Channel CChannel status1 Bit1.1 switchCRT
40Channel CLogic 11 Bit1.2 booleanCW
41Channel CLogic 21 Bit1.2 booleanCW
42Channel CLogic 31 Bit1.2 booleanCW
43Channel CDisable time functions1 Bit1.3 enableCW
44Channel CStaircase duration2 Bytes7.5 time (s)CW
45Channel CStaircase warning1 Bit1.1 switchCRT
46Channel CScene1 Byte18.1 scene controlCW
47Channel CInput for threshold value1 Byte5.10 counter pulses (0..255)CW
47Channel CInput for threshold value2 Bytes7.1 pulsesCW
48Channel CSet value for threshold 11 Byte5.10 counter pulses (0..255)CW
48Channel CSet value for threshold 12 Bytes7.1 pulsesCW
49Channel CSet value for threshold 21 Byte5.10 counter pulses (0..255)CW
49Channel CSet value for threshold 22 Bytes7.1 pulsesCW
50Channel CCall scene 1-bit1 Bit1.1 switchCW
51Channel CSet scene 1-bit1 Bit1.1 switchCW
52Channel CForced state 11 Bit1.1 switchCW
53Channel CForced state 21 Bit1.1 switchCW
54Channel DSwitch1 Bit1.1 switchCW
55Channel D Channel status1 Bit1.1 switchCRT
56Channel DLogic 11 Bit1.2 booleanCW
57Channel DLogic 21 Bit1.2 booleanCW
58Channel DLogic 31 Bit1.2 booleanCW
59Channel DDisable time functions1 Bit1.3 enableCW
60Channel DStaircase duration2 Bytes7.5 time (s)CW
61Channel DStaircase warning1 Bit1.1 switchCRT
62Channel DScene1 Byte18.1 scene controlCW
63Channel DInput for threshold value1 Byte5.10 counter pulses (0..255)CW
63Channel DInput for threshold value2 Bytes7.1 pulsesCW
64Channel DSet value for threshold 11 Byte5.10 counter pulses (0..255)CW
64Channel DSet value for threshold 12 Bytes7.1 pulsesCW
65Channel DSet value for threshold 21 Byte5.10 counter pulses (0..255)CW
65Channel DSet value for threshold 22 Bytes7.1 pulsesCW
66Channel DCall scene 1-bit1 Bit1.1 switchCW
67Channel DSet scene 1-bit1 Bit1.1 switchCW
68Channel DForced state 11 Bit1.1 switchCW
69Channel DForced state 21 Bit1.1 switchCW
Parameters (95)
ParameterTypeDefault
Central functionlistDisable
SafetylistDisable
Startup delaytime0
Interval of cyclic device status sendingtime0
Trigger for safety telegram 1liston
Monitoring time 1time0
Trigger for safety telegram 2liston
Monitoring time 2time0
Trigger for safety telegram 3liston
Monitoring time 3time0
Number of safety functionsunsignedInt 1…31
PolaritylistNO
Reaction to KNX bus failurelistlast set from bus
Reaction to KNX bus recoverylistlast set from bus
Reaction to supply mains recoverylistoff
Reaction on safety 1listno reaction
Reaction on safety 2listno reaction
Reaction on safety 3listno reaction
Reaction on centrallistno reaction
Interval of cyclic channel state sendingtime0
LogiclistDisable
TimelistDisable
ScenelistDisable
ThresholdlistDisable
Scene 1-bitlistDisable
State forcinglistDisable
Number of logic functionsunsignedInt 1…31
Logic 1: functionlistand
Logic 1: initial valuelistoff
Logic 2: functionlistand
Logic 2: initial valuelistoff
Logic 3: functionlistand
Logic 3: initial valuelistoff
FunctionlistStaircase
ControllistON=1; OFF not possible
Default durationtime0
Maximum number of repeatsunsignedInt 1…101
Duration set from buslistno
Duration valuelistdefault
Warning methodlistnone
Warning durationtime0
On delaytime0
Off delaytime0
Triggerliston & off
On durationtime0
Off durationtime0
Number of cyclesunsignedInt 1…1281
Channel state on completionlistinitial state
Learning scenes from buslistno
Initial valuelistdefault
Number of scenesunsignedInt 1…81
Scene 1: numberunsignedInt 1…641
Scene 1: valuelistoff
Scene 1: delaytime0
Scene 2: numberunsignedInt 1…641
Scene 2: valuelistoff
Scene 2: delaytime0
Scene 3: numberunsignedInt 1…641
Scene 3: valuelistoff
Scene 3: delaytime0
Scene 4: numberunsignedInt 1…641
Scene 4: valuelistoff
Scene 4: delaytime0
Scene 5: numberunsignedInt 1…641
Scene 5: valuelistoff
Scene 5: delaytime0
Scene 6: numberunsignedInt 1…641
Scene 6: valuelistoff
Scene 6: delaytime0
Scene 7: numberunsignedInt 1…641
Scene 7: valuelistoff
Scene 7: delaytime0
Scene 8: numberunsignedInt 1…641
Scene 8: valuelistoff
Scene 8: delaytime0
Object typelist1 byte
Object valuelistdefault
Object default valueunsignedInt 0…2550
Object default valueunsignedInt 0…655350
Threshold 1 value set from buslistno
Threshold 1 valuelistdefault
Threshold 1 default valueunsignedInt 0…2550
Threshold 1 default valueunsignedInt 0…655350
Threshold 2 value set from buslistno
Threshold 2 valuelistdefault
Threshold 2 default valueunsignedInt 0…2550
Threshold 2 default valueunsignedInt 0…655350
Channel reaction above upper thresholdlistoff
Channel reaction between thresholdslistoff
Channel reaction below lower thresholdlistoff
Reaction to scene 1 (tel.=0)listno change
Reaction to scene 2 (tel.=1)listoff
Learning 1-bit scenes from buslistno
Channel reaction to forced state 1listno reaction
Channel reaction to forced state 2listno reaction

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Universal Switch Actuator 4CH 1.3 latest$000282062026-11-25205 KBDownload

About this file

This is the official ETS product database for the Satel sp. z o.o. KNX-SA41.230.16.1 (KNX-SA41), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from Satel sp. z o.o.

All Satel sp. z o.o. products