KNX Database
Satel sp. z o.o. KNX-BSA12L KNX-BSA12.24.6.1

KNX-BSA12.24.6.1 KNX-BSA12L

Satel sp. z o.o. · Order number KNX-BSA12L · Blind actuator

Universal two-channel blind actuator (24 V DC)

Download .knxprod Universal two-channel blind actuator (24 V DC) 1.2 · 194 KB

Product

ManufacturerSatel sp. z o.o.
Product nameKNX-BSA12.24.6.1
Order numberKNX-BSA12L
Hardwareknx-bsa12l
MediumTwisted Pair
Bus current (mA)40
Rail mountedYes
Width (mm)720
RegistrationCertified · 2018-07-10
Languagespl-PL, en-US, de-DE, it-IT, nl-NL, ru-RU, sk-SK
Catalog entryM-0144_H-5-1_HP-0005-12-DDD9_CI-KNX.2DBSA12L-5
FingerprintDDD9
SHA-25685f88a93c912f25c4cefd02819334405b5ca4690f869322b7b48199c395beeba
First seen2026-11-25
Markets35 markets

Application program: Universal two-channel blind actuator (24 V DC) 1.2

Application number$0005
Version1.2
Mask versionMV-07B0 (System B)
KNX Data SecureNo
Minimum ETS version5.0
Parameters243
Group objects47
Group objects (47)
NoNameFunctionSizeDPTFlags
1GeneralDevice operation status1 Bit1.1 switchCRT
2SafetyWind alarm1 Bit1.5 alarmCW
3SafetyRain alarm1 Bit1.5 alarmCW
4SafetyFrost alarm1 Bit1.5 alarmCW
5CentralMove up/down1 Bit1.8 up/downCW
6CentralSet absolute position percentage1 Byte5.1 percentage (0..100%)CW
7CentralSet absolute position slats percentage 1 Byte5.1 percentage (0..100%)CW
8CentralDedicated stop1 Bit1.17 triggerCW
9GeneralDevice error alarm1 Bit1.11 stateCRT
17Channel AMove up/down1 Bit1.8 up/downCW
18Channel AStop/step up/down1 Bit1.7 stepCW
18Channel AStop/step up/down4 Bit3.8 blind controlCW
19Channel ADedicated stop1 Bit1.17 triggerCW
20Channel ASet absolute position percentage1 Byte5.1 percentage (0..100%)CW
21Channel ASet absolute position slats percentage 1 Byte5.1 percentage (0..100%)CW
22Channel ACurrent absolute position percentage1 Byte5.1 percentage (0..100%)CRT
23Channel ACurrent absolute position slats percentage1 Byte5.1 percentage (0..100%)CRT
24Channel AScene1 Byte18.1 scene controlCW
25Channel ACall scene 1-bit (1/2)1 Bit1.22 sceneCW
26Channel ACall scene 1-bit (3/4)1 Bit1.22 sceneCW
27Channel ACall scene 1-bit (5/6)1 Bit1.22 sceneCW
28Channel ACall scene 1-bit (7/8)1 Bit1.22 sceneCW
29Channel ASet scene 1-bit (1/2)1 Bit1.22 sceneCW
30Channel ASet scene 1-bit (3/4)1 Bit1.22 sceneCW
31Channel ASet scene 1-bit (5/6)1 Bit1.22 sceneCW
32Channel ASet scene 1-bit (7/8)1 Bit1.22 sceneCW
33Channel AForced position1 Bit1.1 switchCW
34Channel AChannel error alarm1 Bit1.11 stateCRT
39Channel BMove up/down1 Bit1.8 up/downCW
40Channel BStop/step up/down1 Bit1.7 stepCW
40Channel BStop/step up/down4 Bit3.8 blind controlCW
41Channel BDedicated stop1 Bit1.17 triggerCW
42Channel BSet absolute position percentage1 Byte5.1 percentage (0..100%)CW
43Channel BSet absolute position slats percentage1 Byte5.1 percentage (0..100%)CW
44Channel BCurrent absolute position percentage1 Byte5.1 percentage (0..100%)CRT
45Channel BCurrent absolute position slats percentage1 Byte5.1 percentage (0..100%)CRT
46Channel BScene1 Byte18.1 scene controlCW
47Channel BCall scene 1-bit (1/2)1 Bit1.22 sceneCW
48Channel BCall scene 1-bit (3/4)1 Bit1.22 sceneCW
49Channel BCall scene 1-bit (5/6)1 Bit1.22 sceneCW
50Channel BCall scene 1-bit (7/8)1 Bit1.22 sceneCW
51Channel BSet scene 1-bit (1/2)1 Bit1.22 sceneCW
52Channel BSet scene 1-bit (3/4)1 Bit1.22 sceneCW
53Channel BSet scene 1-bit (5/6)1 Bit1.22 sceneCW
54Channel BSet scene 1-bit (7/8)1 Bit1.22 sceneCW
55Channel BForced position1 Bit1.1 switchCW
56Channel BChannel error alarm1 Bit1.11 stateCRT
Parameters (95)
ParameterTypeDefault
Interval of cyclic device status sendingtime0
Wind: monitoring timetime0
Rain: monitoring timetime0
Frost: monitoring timetime0
Channel Alistnot used
Reaction to KNX bus recoverylistno change
Switch-on delay when uptime100
Switch-off delaytime100
Travel time uptime0
Learning 1-bit scenes from buslistno
Scene 2: initial valuelistdefault
Scene 1: position of slatsunsignedInt 0…1000
Scene 2: position of slatsunsignedInt 0…1000
Scene 1-bitlistDisable
Scene 1: learninglistno
Scene 1: initial valuelistdefault
Scene 1: numberunsignedInt 1…641
Scene 1: positionunsignedInt 0…1000
Number of scenesunsignedInt 0…81
ScenelistDisable
Scene 2: learninglistno
Scene 2: numberunsignedInt 1…641
Scene 2: positionunsignedInt 0…1000
Scene 3: learninglistno
Scene 3: initial valuelistdefault
Scene 3: numberunsignedInt 1…641
Scene 3: positionunsignedInt 0…1000
Scene 3: position of slatsunsignedInt 0…1000
Scene 4: learninglistno
Scene 4: initial valuelistdefault
Scene 4: numberunsignedInt 1…641
Scene 4: positionunsignedInt 0…1000
Scene 4: position of slatsunsignedInt 0…1000
Scene 5: learninglistno
Scene 5: initial valuelistdefault
Scene 5: numberunsignedInt 1…641
Scene 5: positionunsignedInt 0…1000
Scene 5: position of slatsunsignedInt 0…1000
Scene 6: learninglistno
Scene 6: initial valuelistdefault
Scene 6: numberunsignedInt 1…641
Scene 6: positionunsignedInt 0…1000
Scene 6: position of slatsunsignedInt 0…1000
Scene 7: learninglistno
Scene 7: initial valuelistdefault
Scene 7: numberunsignedInt 1…641
Scene 7: positionunsignedInt 0…1000
Scene 7: position of slatsunsignedInt 0…1000
Scene 8: learninglistno
Scene 8: initial valuelistdefault
Scene 8: numberunsignedInt 1…641
Scene 8: positionunsignedInt 0…1000
Scene 8: position of slatsunsignedInt 0…1000
Wind: control schemelist0-reset monitoring time / 1-alarm
Rain: control schemelist0-reset monitoring time / 1-alarm
Frost: control schemelist0-reset monitoring time / 1-alarm
Startup delaytime0
Alarm prioritylist1: Frost; 2: Rain; 3: Wind
Reaction on wind alarmlistno reaction
Reaction on rain alarmlistno reaction
Reaction on frost alarmlistno reaction
Weather alarmslistDisable
Channel reaction to forced positionlistfully opened
Position forcinglistDisable
Travel time detectionlistAutomatic after programming
Time of slat adjustment when uptime0
Number of 1-bit scene pairsunsignedInt 1…41
Switch-on delay when downtime100
Travel time downtime0
PID_HARDWARElistKNX-BSA12L 1.0
Step: valueunsignedInt 1…10010
Scene 1: delaytime0
Scene 2: delaytime0
Scene 3: delaytime0
Scene 4: delaytime0
Scene 5: delaytime0
Scene 6: delaytime0
Scene 7: delaytime0
Scene 8: delaytime0
Learning scenes from buslistno
Step: object typelist1-bit
Central move up/downlistDisable
Central absolute positionlistDisable
Channel Blistnot used
Time of slat adjustmenttime0
Travel timetime0
Time of slat adjustment when downtime0
Travel time in two directionslistno
Additional travel to end positionunsignedInt 0…12525
Position toleranceunsignedInt 0…10010
Interval of cyclic device error (alarm) sendingtime0
Interval of cyclic channel error (alarm) sendingtime0
Interval of cyclic position sendingtime0
Interval of cyclic slats position sendingtime0
Central stoplistDisable

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Universal two-channel blind actuator (24 V DC) 1.2 latest$0005DDD92026-11-25194 KBDownload

About this file

This is the official ETS product database for the Satel sp. z o.o. KNX-BSA12.24.6.1 (KNX-BSA12L), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from Satel sp. z o.o.

All Satel sp. z o.o. products