Thermostat MD WRKT3310XXX
Panasonic · Order number WRKT3310XXX · HVAC › Thermostat
Room Thermostat - Modular
Download .knxprod Thermostat MD 1.0 · 73 KB
Product
| Manufacturer | Panasonic |
|---|---|
| Product name | Thermostat MD |
| Order number | WRKT3310XXX |
| Hardware | HW THERMOSTAT MD |
| Medium | Twisted Pair |
| Bus current (mA) | 10 |
| Rail mounted | No |
| Registration | Certified |
| Catalog entry | M-008B_H-805422.2DP-1_HP-0106-10-2100_CI-WRKT3310XXX-2 |
| Fingerprint | 2100 |
| SHA-256 | 5b772c119f6587642355c1d7a7c6eaf5123635cbdd91cfb6775f56c1b7643dd4 |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: Thermostat MD 1.0
| Application number | $0106 |
|---|---|
| Version | 1.0 |
| Mask version | MV-0701 (7.1) |
| KNX Data Secure | No |
| Minimum ETS version | 3.0f |
| Parameters | 64 |
| Group objects | 32 |
Group objects (32)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Actual temperature value | Transmit actual value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 1 | Current operation mode | Indicate operation mode | 1 Byte | CRWT | |
| 2 | Presence Input | Input for presence signal | 1 Bit | 1.1 switch | CRW |
| 3 | Window State | Input for window contact | 1 Bit | 1.1 switch | CRW |
| 4 | Heating base setpoint | Define set point value | 2 Bytes | 9.1 temperature (°C) | CRW |
| 5 | Cooling base setpoint | Define set point value | 2 Bytes | 9.1 temperature (°C) | CRW |
| 6 | Current Setpoint | Indicate/adjust set point | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 7 | Heating Switching Control Value | Transmit actuating value | 1 Bit | 1.1 switch | CRT |
| 7 | Heating Continuous Control Value | Transmit actuating value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 8 | Cooling Switching Control Value | Transmit actuating value | 1 Bit | 1.1 switch | CRT |
| 8 | Cooling Continuous Control Value | Transmit actuating value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 9 | Switchover between heating and cooling | heating=1, cooling=0 | 1 Bit | 1.1 switch | CRWT |
| 9 | Report heating or cooling mode | heating=1 cooling=0 | 1 Bit | 1.1 switch | CRT |
| 10 | Reset manual operations | Reset=1 | 1 Bit | 1.1 switch | CRW |
| 11 | Fan mode (manual/auto) | 1=manual, 0=auto | 1 Bit | 1.1 switch | CRWT |
| 11 | Fan mode (manual/auto) | 0=manual, 1=auto | 1 Bit | 1.1 switch | CRWT |
| 12 | Fan level | send/receive fan level 0-100 % | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 12 | Fan level | send/receive fan level 0-3 | 1 Byte | 5.10 counter pulses (0..255) | CRWTU |
| 13 | LCD backlight | on/off backlight | 1 Bit | 1.1 switch | CRW |
| 14 | Time | Receive time | 3 Bytes | 10.1 time of day | CRW |
| 15 | Time query | Request for time | 1 Bit | 1.2 boolean | CRT |
| 16 | Date | Receive date | 3 Bytes | 11.1 date | CRW |
| 17 | Date query | Request for date | 1 Bit | 1.2 boolean | CRT |
| 18 | Switching program lock | Lock=1 | 1 Bit | 1.1 switch | CRW |
| 19 | Heating PWM Control Value | Transmit actuating value | 1 Bit | 1.1 switch | CRT |
| 20 | Cooling PWM Control Value | Transmit actuating value | 1 Bit | 1.1 switch | CRT |
| 21 | Fan level | send/receive fan level 1 | 1 Bit | 1.1 switch | CRWTU |
| 22 | Fan level | send/receive fan level 2 | 1 Bit | 1.1 switch | CRWTU |
| 23 | Fan level | send/receive fan level 3 | 1 Bit | 1.1 switch | CRWTU |
| 24 | Fan unit | send on/off | 1 Bit | 1.1 switch | CT |
| 29 | Object 29 | debug 1 | 1 Byte | 5.10 counter pulses (0..255) | CRWTU |
| 30 | Object 30 | debug 2 | 1 Byte | 5.10 counter pulses (0..255) | CRWTU |
Parameters (51)
| Parameter | Type | Default |
|---|---|---|
| Settings menu on device | list | Disable |
| Operation mode after reset | list | Standby |
| Fan control | list | Disable |
| Transmit operation mode and fan step | list | not cyclically, only at change |
| Switching program after reset | list | No program |
| Language after download | list | Türkçe |
| Select date-time object | list | Time object only |
| Show extra objects | list | no |
| Ets data loaded | list | yes |
| Control function | list | Heating |
| Switchover between heating and cooling | list | Automatically |
| Minimum distance between heating and cooling | list | 1K |
| Control function after ETS Download | list | Heating |
| Offset for temperature sensor 0.1K Steps ( -50..50 ) | signedInt -50…50 | 0 |
| Transmit actual temperature at change | list | inactive |
| Transmit actual temperature cyclically | list | not cyclically, only at change |
| Heating setpoint base | unsignedInt 15…32 | 23 |
| Heating reduction standby | unsignedInt 1…10 | 2 |
| Heating reduction night | unsignedInt 1…10 | 4 |
| Heating setpoint frost protection | unsignedInt 1…15 | 5 |
| Cooling setpoint base | unsignedInt 15…32 | 25 |
| Cooling increase standby | unsignedInt 1…10 | 2 |
| Cooling increase night | unsignedInt 1…10 | 4 |
| Cooling setpoint heat protection | unsignedInt 30…40 | 37 |
| Maximum allowed setpoint offset | list | +/- 2K |
| Transmit current setpoint cyclically | list | not cyclically, only at change |
| Heating controller type | list | 2 Step |
| Heating hysteresis | list | 0.2K |
| Heating control value invert | list | no |
| Heating PI parameter type | list | Via type of system |
| Heating type of the system | list | Warm water heating |
| Heating propotional band | list | 4.0K |
| Heating integral reset time | unsignedInt 0…250 | 0 |
| Heating PWM cyclic time (Min) | unsignedInt 1…60 | 1 |
| Transmit control value at change of | list | % 5 |
| Heating transmit control value cyclically | list | not cyclically, only at change |
| Cooling controller type | list | 2 Step |
| Cooling hysteresis | list | 0.2K |
| Cooling control value invert | list | no |
| Cooling PI parameter type | list | Via type of system |
| Cooling type of the system | list | Cool ceiling |
| Cooling propotional band | list | 4.0K |
| Cooling integral reset time | unsignedInt 0…250 | 0 |
| Cooling PWM cyclic time (Min) | unsignedInt 1…60 | 1 |
| Cooling transmit control value cyclically | list | not cyclically, only at change |
| System type | list | 4 pipe system |
| Fan level object type | list | 1-Byte object, percentage value 0-100 % |
| Value for fan level 1 | unsignedInt 0…100 | 10 |
| Value for fan level 2 | unsignedInt 0…100 | 60 |
| Value for fan level 3 | unsignedInt 0…100 | 100 |
| Switchover fan auto and manual mode | list | Via object "Fan auto/manual", auto is 0 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Thermostat MD 1.0 latest | $0106 | 2100 | 2026-11-25 | 73 KB | Download |
About this file
This is the official ETS product database for the Panasonic Thermostat MD (WRKT3310XXX), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Panasonic
- Thermostat STD WRKT3300XXX/WRKT3400XXX
- KNX POWER SUPPLY UNIT 320 mA WRKT20145NC
- KNX POWER SUPPLY UNIT 640 mA WRKT20275NC
- KNX Power Supply 320mA PS132 WRKT20305NC
- KNX Power Supply 640 mA PS164 WRKT20315NC
- KNX AREA/LINE COUPLER WRKT21015NC
- KNX AREA / LINE COUPLER WRKT21025NC
- KNX SECURE AREA/LINE COUPLER WZ WRKT21035NC
- KNX DALI GATEWAY GV 1/2 Channel WRKT22145/22155NC
- KNX IP INTERFACE WRKT23305NC
- KNX IP ROUTER WRKT23315NC
- KNX SECURE IP INTERFACE WZ WRKT23505NC