KNX Database
Panasonic WRKT3300XXX/WRKT3400XXX Thermostat STD

Thermostat STD WRKT3300XXX/WRKT3400XXX

Panasonic · Order number WRKT3300XXX/WRKT3400XXX · HVAC › Thermostat

Room Thermostat - Standart

Download .knxprod Thermostat STD 1.2 · 76 KB

Product

ManufacturerPanasonic
Product nameThermostat STD
Order numberWRKT3300XXX/WRKT3400XXX
HardwareHW Thermostat STD
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationCertified · 2016-08-12
Languagesen-US, de-DE
Catalog entryM-008B_H-805431.2DP-1_HP-0203-12-677C_CI-WRKT3300XXX.2FWRKT3400XXX.20-1
Fingerprint677C
SHA-256a930bba04219465543ee9b784840cc2691da41b4f16126c1be7d1379eeb49743
First seen2026-11-25
Markets59 markets

Application program: Thermostat STD 1.2

Application number$0203
Version1.2
Mask versionMV-0701 (7.1)
KNX Data SecureNo
Minimum ETS version4.0
Parameters54
Group objects32
Group objects (32)
NoNameFunctionSizeDPTFlags
0Actual temperature valueTransmit actual value2 Bytes9.1 temperature (°C)CRT
1Current operation modeIndicate operation mode1 Byte20.102 HVAC modeCRWT
2Presence InputInput for presence signal1 Bit1.1 switchCRW
3Window StateInput for window contact1 Bit1.1 switchCRW
4Heating base setpointDefine set point value2 Bytes9.1 temperature (°C)CRW
5Cooling base setpointDefine set point value2 Bytes9.1 temperature (°C)CRW
6Current SetpointIndicate/adjust set point2 Bytes9.1 temperature (°C)CRWT
7Heating Switching Control Value Transmit actuating value1 Bit1.1 switchCRT
7Heating Continuous Control ValueTransmit actuating value1 Byte5.1 percentage (0..100%)CRT
8Cooling Switching Control ValueTransmit actuating value1 Bit1.1 switchCRT
8Cooling Continuous Control Value Transmit actuating value1 Byte5.1 percentage (0..100%)CRT
9Switchover between heating and coolingheating=1, cooling=01 Bit1.1 switchCRWT
9Report heating or cooling modeheating=1 cooling=01 Bit1.1 switchCRT
10Reset manual operationsReset=11 Bit1.1 switchCRW
11Fan mode (manual/auto)1=manual, 0=auto1 Bit1.1 switchCRWT
11Fan mode (manual/auto)0=manual, 1=auto1 Bit1.1 switchCRWT
12Fan levelsend/receive fan level 0-100 %1 Byte5.1 percentage (0..100%)CRWTU
12Fan levelsend/receive fan level 0-31 Byte5.1 percentage (0..100%)CRWTU
13LCD backlighton/off backlight1 Bit1.1 switchCRW
14TimeReceive time3 Bytes10.1 time of dayCRW
15Time queryRequest for time1 Bit1.2 booleanCRT
16DateReceive date3 Bytes11.1 dateCRW
17Date queryRequest for date1 Bit1.2 booleanCRT
18Switching program lockLock=11 Bit1.1 switchCRW
19Heating PWM Control Value Transmit actuating value1 Bit1.1 switchCRT
20Cooling PWM Control ValueTransmit actuating value1 Bit1.1 switchCRT
21Fan levelsend/receive fan level 11 Bit1.1 switchCRWTU
22Fan levelsend/receive fan level 21 Bit1.1 switchCRWTU
23Fan levelsend/receive fan level 31 Bit1.1 switchCRWTU
24Fan unitsend on/off1 Bit1.1 switchCT
29Object 29debug 11 Byte5.10 counter pulses (0..255)CRWTU
30Object 30debug 21 Byte5.10 counter pulses (0..255)CRWTU
Parameters (53)
ParameterTypeDefault
Operation mode after resetlistStandby
Control functionlistHeating
Control function after ETS downloadlistHeating
Transmit actual temperature at changelistinactive
Transmit actual temperature cyclicallylistnot cyclically, only at change
Heating setpoint baseunsignedInt 15…3220
Heating reduction standbyunsignedInt 1…103
Heating reduction nightunsignedInt 1…105
Heating setpoint frost protectionunsignedInt 1…155
Cooling setpoint baseunsignedInt 15…3220
Cooling increase standbyunsignedInt 1…103
Cooling increase nightunsignedInt 1…105
Cooling setpoint heat protectionunsignedInt 30…4037
Minimum distance between heating and coolinglist1K
Transmit current setpoint cyclicallylistnot cyclically, only at change
Heating trasmit control value cyclicallylistnot cyclically, only at change
Heating controller typelist2 Step
Heating hysteresislist0.2K
Heating control value invertlistyes
Heating PI parameter typelistVia type of system
Heating type of the systemlistWarm water heating
Heating PWM cyclic time (Min)unsignedInt 1…601
Heating propotional bandlist4.0K
Transmit control value at change oflist1%
Cooling integral reset timeunsignedInt 0…2500
Cooling propotional bandlist4.0K
Cooling PWM cyclic time (Min)unsignedInt 1…601
Cooling type of the systemlistCool ceiling
Cooling PI parameter typelistVia type of system
Cooling control value invertlistyes
Cooling hysteresislist0.2K
Cooling controller typelist2 Step
Cooling transmit control value cyclicallylistnot cyclically, only at change
Settings menu on devicelistDisable
Fan controllistDisable
Transmit operation mode and fan steplistnot cyclically, only at change
Switching program after resetlistNo program
Language after downloadlistEnglish
Switchover between heating and coolinglistAutomatically
Offset for temperature sensor 0.1K Steps ( -50..50 )signedInt -50…500
Maximum allowed setpoint offsetlistmanual adjustment not allowed
Value for fan level 1unsignedInt 0…2000
Value for fan level 2unsignedInt 0…2000
Value for fan level 3unsignedInt 0…2000
Switchover fan auto and manual modelistVia object "Fan auto/manual", auto is 0
Heating integral reset timeunsignedInt 0…2500
Show extra objectslistno
Ets data loadedlistyes
Heating transmit control value cyclicallylistnot cyclically, only at change
Select date-time objectlistTime object only
Fan level object typelist1-Byte object, percentage value 0-100 %
Use heating control objectlistNo ( 4 pipe system )
( with 2 step control cooling and heating hystereses is add to value )text

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Thermostat STD 1.2 latest$0203677C2026-11-2576 KBDownload
Thermostat STD 0.1$0203A98B2026-11-2573 KBDownload

About this file

This is the official ETS product database for the Panasonic Thermostat STD (WRKT3300XXX/WRKT3400XXX), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.