Analogue input REG-K/4-gang 682191
Merten · Order number 682191 · 2.8 Analogue Input › 2.8.01 DIN rail mounted REG-K
682191
Download .knxprod Analogue output floating point/value B007/1.3 1.3 · 106 KB
Product
| Manufacturer | Merten |
|---|---|
| Product name | Analogue input REG-K/4-gang |
| Order number | 682191 |
| Hardware | Analogeingang REG-K/4-fach |
| Medium | Twisted Pair |
| Rail mounted | Yes |
| Width (mm) | 70 |
| Registration | Registered |
| Languages | en-US, de-DE |
| Catalog entry | M-000C_H-682191-1-O00F4_HP-B007-13-0A51-O00F4_CI-682191-1 |
| Fingerprint | 0A51 |
| SHA-256 | 0cf1483e81e505637317779034122f9b00130091c94059a1f454a3116482aaf9 |
| First seen | 2026-11-25 |
| Markets | Argentina, Australia, Austria, Germany, Uruguay |
Application program: Analogue output floating point/value B007/1.3 1.3
| Application number | $B007 |
|---|---|
| Version | 1.3 |
| Mask version | MV-0701 (7.1) |
| KNX Data Secure | No |
| Parameters | 517 |
| Group objects | 74 |
Group objects (74)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Alarm object | Analogue input | 1 Bit | CTU | |
| 1 | Measured value input 1 | Analogue input | 2 Bytes | CTU | |
| 1 | Measured value input 1 | Analogue input | 1 Byte | CTU | |
| 2 | Measured value input 2 | Analogue input | 2 Bytes | CTU | |
| 2 | Measured value input 2 | Analogue input | 1 Byte | CTU | |
| 3 | Measured value input 3 | Analogue input | 2 Bytes | CTU | |
| 3 | Measured value input 3 | Analogue input | 1 Byte | CTU | |
| 4 | Measured value input 4 | Analogue input | 2 Bytes | CTU | |
| 4 | Measured value input 4 | Analogue input | 1 Byte | CTU | |
| 5 | Limit value 1 input 1 | Analogue input | 1 Bit | CTU | |
| 6 | Limit value 2 input 1 | Analogue input | 1 Bit | CTU | |
| 7 | Limit value 1 input 2 | Analogue input | 1 Bit | CTU | |
| 8 | Limit value 2 input 2 | Analogue input | 1 Bit | CTU | |
| 9 | Limit value 1 input 3 | Analogue input | 1 Bit | CTU | |
| 10 | Limit value 2 input 3 | Analogue input | 1 Bit | CTU | |
| 11 | Limit value 1 input 4 | Analogue input | 1 Bit | CTU | |
| 12 | Limit value 2 input 4 | Analogue input | 1 Bit | CTU | |
| 13 | External limit value 1 input 1 | Analogue input | 1 Byte | CWU | |
| 13 | External limit value 1 input 1 | Analogue input | 2 Bytes | CWU | |
| 14 | External limit value 2 input 1 | Analogue input | 2 Bytes | CWU | |
| 14 | External limit value 2 input 1 | Analogue input | 1 Byte | CWU | |
| 15 | External limit value 1 input 2 | Analogue input | 1 Byte | CWU | |
| 15 | External limit value 1 input 2 | Analogue input | 2 Bytes | CWU | |
| 16 | External limit value 2 input 2 | Analogue input | 2 Bytes | CWU | |
| 16 | External limit value 2 input 2 | Analogue input | 1 Byte | CWU | |
| 17 | External limit value 1 input 3 | Analogue input | 1 Byte | CWU | |
| 17 | External limit value 1 input 3 | Analogue input | 2 Bytes | CWU | |
| 18 | External limit value 2 input 3 | Analogue input | 2 Bytes | CWU | |
| 18 | External limit value 2 input 3 | Analogue input | 1 Byte | CWU | |
| 19 | External limit value 1 input 4 | Analogue input | 1 Byte | CWU | |
| 19 | External limit value 1 input 4 | Analogue input | 2 Bytes | CWU | |
| 20 | External limit value 2 input 4 | Analogue input | 2 Bytes | CWU | |
| 20 | External limit value 2 input 4 | Analogue input | 1 Byte | CWU | |
| 21 | Wire break input 1 | Analogue input | 1 Bit | CTU | |
| 22 | Wire break input 2 | Analogue input | 1 Bit | CTU | |
| 23 | Wire break input 3 | Analogue input | 1 Bit | CTU | |
| 24 | Wire break input 4 | Analogue input | 1 Bit | CTU | |
| 25 | Alarm object | Extension module | 1 Bit | CTU | |
| 26 | Measured value input 5 | Extension module | 2 Bytes | CTU | |
| 26 | Measured value input 5 | Extension module | 1 Byte | CTU | |
| 27 | Measured value input 6 | Extension module | 2 Bytes | CTU | |
| 27 | Measured value input 6 | Extension module | 1 Byte | CTU | |
| 28 | Measured value input 7 | Extension module | 2 Bytes | CTU | |
| 28 | Measured value input 7 | Extension module | 1 Byte | CTU | |
| 29 | Measured value input 8 | Extension module | 2 Bytes | CTU | |
| 29 | Measured value input 8 | Extension module | 1 Byte | CTU | |
| 30 | Limit value 1 input 5 | Extension module | 1 Bit | CTU | |
| 31 | Limit value 2 input 5 | Extension module | 1 Bit | CTU | |
| 32 | Limit value 1 input 6 | Extension module | 1 Bit | CTU | |
| 33 | Limit value 2 input 6 | Extension module | 1 Bit | CTU | |
| 34 | Limit value 1 input 7 | Extension module | 1 Bit | CTU | |
| 35 | Limit value 2 input 7 | Extension module | 1 Bit | CTU | |
| 36 | Limit value 1 input 8 | Extension module | 1 Bit | CTU | |
| 37 | Limit value 2 input 8 | Extension module | 1 Bit | CTU | |
| 38 | External limit value 1 input 5 | Extension module | 1 Byte | CWU | |
| 38 | External limit value 1 input 5 | Extension module | 2 Bytes | CWU | |
| 39 | External limit value 2 input 5 | Extension module | 2 Bytes | CWU | |
| 39 | External limit value 2 input 5 | Extension module | 1 Byte | CWU | |
| 40 | External limit value 1 input 6 | Extension module | 1 Byte | CWU | |
| 40 | External limit value 1 input 6 | Extension module | 2 Bytes | CWU | |
| 41 | External limit value 2 input 6 | Extension module | 2 Bytes | CWU | |
| 41 | External limit value 2 input 6 | Extension module | 1 Byte | CWU | |
| 42 | External limit value 1 input 7 | Extension module | 1 Byte | CWU | |
| 42 | External limit value 1 input 7 | Extension module | 2 Bytes | CWU | |
| 43 | External limit value 2 input 7 | Extension module | 2 Bytes | CWU | |
| 43 | External limit value 2 input 7 | Extension module | 1 Byte | CWU | |
| 44 | External limit value 1 input 8 | Extension module | 1 Byte | CWU | |
| 44 | External limit value 1 input 8 | Extension module | 2 Bytes | CWU | |
| 45 | External limit value 2 input 8 | Extension module | 2 Bytes | CWU | |
| 45 | External limit value 2 input 8 | Extension module | 1 Byte | CWU | |
| 46 | Wire break input 5 | Extension module | 1 Bit | CTU | |
| 47 | Wire break input 6 | Extension module | 1 Bit | CTU | |
| 48 | Wire break input 7 | Extension module | 1 Bit | CTU | |
| 49 | Wire break input 8 | Extension module | 1 Bit | CTU |
Parameters (60)
| Parameter | Type | Default |
|---|---|---|
| General parameters | list | no |
| Signal input 1 | list | No sensor |
| Wire break detection input 1 | list | no detection |
| Signal input 2 | list | No sensor |
| Wire break detection input 2 | list | no detection |
| Signal input 3 | list | No sensor |
| Wire break detection input 3 | list | no detection |
| Signal input 4 | list | No sensor |
| Wire break detection input 4 | list | no detection |
| Alarm analogue input | list | do not send |
| Extension module available | list | no |
| Extension module | list | no |
| Signal input 5 | list | No sensor |
| Wire break detection input 5 | list | no detection |
| Signal input 6 | list | No sensor |
| Wire break detection input 6 | list | no detection |
| Signal input 7 | list | No sensor |
| Wire break detection input 7 | list | no detection |
| Signal input 8 | list | No sensor |
| Wire break detection input 8 | list | no detection |
| Alarm extended module | list | do not send |
| Measured value 1 | list | no |
| Sending format of measured value | list | 16 bit EIS% |
| Measured value for 0% of the measuring s ignal(-32768...32767) | signedInt -32768…32767 | 0 |
| Measured value for 0% of the measuring s ignal(0...255) | signedInt 0…255 | 0 |
| Measured value for 100% of the measuring signal(-32768...32767) | signedInt -32768…32767 | 100 |
| Measured value for 100% of the measuring signal(0...255) | signedInt 0…255 | 255 |
| Factor of measuring range | list | * 0.01 |
| Send measured value if changed by | list | 3% |
| Factor for cycl. sending of measured value (base 10s, 0 = no cycl. sending) | unsignedInt 0…120 | 0 |
| Measured value 2 | list | no |
| Measured value for 100% of the measuring signal(-32768...32767) | signedInt -32768…32767 | 1000 |
| Measured value 3 | list | no |
| Measured value 4 | list | no |
| Measured value 5 | list | no |
| Measured value for 0% of the measuring signal (-32768…32767) | signedInt -32768…32767 | 0 |
| Measured value for 0% of the measuring signal (0…255) | signedInt 0…255 | 0 |
| Measured value for 100% of the measuring signal (-32768…32767) | signedInt -32768…32767 | 1000 |
| Measured value for 100% of the measuring signal (0…255) | signedInt 0…255 | 255 |
| Measured value 6 | list | no |
| Measured value 7 | list | no |
| Measured value 8 | list | no |
| Input 1 | list | no |
| Limit value 1 (in % of measuring range) | unsignedInt 0…100 | 20 |
| Hysteresis of limit value 1 | unsignedInt 0…100 | 10 |
| Activation of limit value 1 | list | below LV=ON, above LV+Hys.=OFF |
| External limit value object LV 1 | list | no |
| Format external limit value object LV 1 | list | 16 bit EIS% |
| Limit value 2 (in % of measuring range) | unsignedInt 0…100 | 80 |
| Hysteresis of limit value 2 | unsignedInt 0…100 | 10 |
| Activation of limit value 2 | list | above LV=ON, below LV-Hys.=OFF |
| External limit value object LV 2 | list | no |
| Format external limit value object LV 2 | list | 16 bit EIS% |
| Input 2 | list | no |
| Input 3 | list | no |
| Input 4 | list | no |
| Input 5 | list | no |
| Input 6 | list | no |
| Input 7 | list | no |
| Input 8 | list | no |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Analogue output floating point/value B007/1.3 1.3 latest | $B007 | 0A51 | 2026-11-25 | 106 KB | Download |
About this file
This is the official ETS product database for the Merten Analogue input REG-K/4-gang (682191), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Merten
- TCU UP/PI with 4-gang push-button interface 6167xx
- TCU UP/PI with 4-gang push-button interface 6168xx
- TCU UP/PI with 4-gang push-button interface 6169xx
- Push-button 1-gang plus 6171xx
- Push-button 2-gang plus 6172xx
- Push-button 4-gang plus 6174xx
- Push-button 4-gang plus with IR receiver 6175xx
- INSTABUS push-button module 1-gang, System M 625199
- INSTABUS push-button module 2-gang, System M 625299
- INSTABUS push-button module 1-gang, System Design 626199
- INSTABUS push-button module 2-gang, System Design 626299
- Push-button 1-gang plus 6275xx