KNX Database

TCU UP/PI with 4-gang push-button interface 6169xx

Merten · Order number 6169xx · 7.1 Heating/Single Room Thermostat › 7.1.16 System design thermostat

6169xx

Download .knxprod Heating/cooling 705C/0.1 0.1 · 134 KB

Product

ManufacturerMerten
Product nameTCU UP/PI with 4-gang push-button interface
Order number6169xx
HardwareRTR UP/PI mit Tasterschnittstelle 4fach
MediumTwisted Pair
Rail mountedNo
RegistrationCertified
Languagesen-US, de-DE
Catalog entryM-000C_H-6169xx-1-O00F4_HP-705C-01-0971-O00F4_CI-6169xx-2
Fingerprint0971
SHA-2562015ceabdc7bf61017f6cb7331c17ae4e4a153b785798ba87c26df4e614cf933
First seen2026-11-25
MarketsArgentina, Australia, Austria, Germany, Uruguay

Application program: Heating/cooling 705C/0.1 0.1

Application number$705C
Version0.1
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Parameters399
Group objects138
Group objects (138)
NoNameFunctionSizeDPTFlags
0PBI output 1Switching status1 BitCTU
0PBI input 1Switching object 1.11 BitCWTU
0PBI input 1Switching1 BitCWTU
0PBI input 1Short-time operation1 BitCTU
0PBI input 1Value1 ByteCT
0PBI input 1Brightness value2 BytesCT
0PBI input 1Temperature value2 BytesCT
0PBI input 1Light-scene extension1 ByteCT
1PBI input 2Switching1 BitCWTU
1PBI input 2Short-time operation1 BitCTU
1PBI input 2Switching object 2.11 BitCWTU
1PBI input 2Value1 ByteCT
1PBI input 2Temperature value2 BytesCT
1PBI input 2Light-scene extension1 ByteCT
1PBI input 2Brightness value2 BytesCT
1PBI output 2Switching status1 BitCTU
2PBI input 3Switching1 BitCWTU
2PBI input 3Short-time operation1 BitCTU
2PBI input 3Switching object 3.11 BitCWTU
2PBI input 3Temperature value2 BytesCT
2PBI input 3Brightness value2 BytesCT
2PBI input 3Light-scene extension1 ByteCT
2PBI input 3Value1 ByteCT
3PBI input 4Switching1 BitCWTU
3PBI input 4Short-time operation1 BitCTU
3PBI input 4Switching object 4.11 BitCWTU
3PBI input 4Temperature value2 BytesCT
3PBI input 4Light-scene extension1 ByteCT
3PBI input 4Brightness value2 BytesCT
3PBI input 4Value1 ByteCT
3PBI input 4Floor temperature2 BytesCTU
4PBI output 1External switching object1 BitCWTU
4PBI input 1Switching object 1.21 BitCWTU
4PBI input 1dimming4 BitCT
4PBI input 1Long-time operation1 BitCT
5PBI input 2dimming4 BitCT
5PBI input 2Long-time operation1 BitCT
5PBI input 2Switching object 2.21 BitCWTU
5PBI output 2External switching object1 BitCWTU
6PBI input 3dimming4 BitCT
6PBI input 3Long-time operation1 BitCT
6PBI input 3Switching object 3.21 BitCWTU
7PBI input 4dimming4 BitCT
7PBI input 4Long-time operation1 BitCT
7PBI input 4Switching object 4.21 BitCWTU
8PBI input 1Disable switching object 1.11 BitCWU
8PBI input 1Disabling1 BitCWU
9PBI input 2Disabling1 BitCWU
9PBI input 2Disable switching object 2.11 BitCWU
10PBI input 3Disabling1 BitCWU
10PBI input 3Disable switching object 3.11 BitCWU
11PBI input 4Disabling1 BitCWU
11PBI input 4Disable switching object 4.11 BitCWU
12PBI input 1Disable switching object 1.21 BitCWU
13PBI input 2Disable switching object 2.21 BitCWU
14PBI input 3Disable switching object 3.21 BitCWU
15PBI input 4Disable switching object 4.21 BitCWU
16unneeded1 BitCRWTU
17unneeded1 BitCRWTU
18unneeded1 BitCRWTU
19unneeded1 BitCRWTU
20unneeded1 BitCRWTU
21unneeded1 BitCRWTU
22unneeded1 BitCRWTU
23RTC outputActual temperature2 BytesCT
24RTC inputExternal temperature sensor2 BytesCWU
25unneeded2 BytesCRWTU
26RTC inputBasic setpoint2 BytesCW
27unneeded2 BytesCT
28RTC inputOperating mode switch-over1 ByteCW
28RTC inputComfort mode1 BitCWTU
29RTC inputStandby mode1 BitCWTU
30RTC inputNight mode1 BitCWTU
31RTC inputFrost/ heat protection1 BitCWTU
32RTC inputOperating mode forcing object1 ByteCW
33RTC input / outputPresence object1 BitCWTU
34RTC inputWindow status1 BitCWTU
35RTC inputHeating / cooling switch-over1 BitCWTU
35RTC inputHeating / cooling switch-over1 BitCTU
36RTC outputController status1 ByteCT
36RTC outputContr. status, comfort mode1 BitCT
36RTC outputContr. status, standby mode1 BitCT
36RTC outputController status, night mode1 BitCT
36RTC outputContr.status, frost/heat prot.1 BitCT
36RTC outputContr. status, contr. Disabled1 BitCT
36RTC outputContr. status, heating/cooling1 BitCT
36RTC outputContr. status, contr. Inactive1 BitCT
36RTC outputController status, frost alarm1 BitCT
37RTC outputHeating message1 BitCT
38RTC outputCooling message1 BitCT
39unneeded1 BitCRWTU
40RTC inputDisable controller1 BitCWT
41RTC inputDisable additional stage1 BitCW
42RTC outputActuating variable heating1 ByteCT
42RTC outputAct. variable heating (PWM)1 BitCT
42RTC outputActuating variable heating1 BitCT
42RTC outputAct. variable basic heating1 ByteCT
42RTC outputAct. var. basic heating (PWM)1 BitCT
42RTC outputAct. variable basic heating1 BitCT
42RTC outputAct. variable heating/cooling1 ByteCT
42RTC outputAct. var. heating/cooling(PWM)1 BitCT
42RTC outputAct. variable heating/cooling1 BitCT
42RTC outputActuating variable basic stage1 BitCT
42RTC outputAct. var. basic stage (PWM)1 BitCT
42RTC outputActuating variable basic stage1 ByteCT
43RTC outputAct. Var. add. heating (PWM)1 BitCT
43RTC outputAct. variable add. heating1 BitCT
43RTC outputAct. variable add. heating1 ByteCT
43RTC outputAct. variable additional stage1 ByteCT
43RTC outputAct. variable additional stage1 BitCT
43RTC outputAct. var. add. stage (PWM)1 BitCT
44RTC outputActuating variable cooling1 ByteCT
44RTC outputAct. variable cooling (PWM)1 BitCT
44RTC outputActuating variable cooling1 BitCT
44RTC outputAct. variable basic cooling1 BitCT
44RTC outputAct. var. basic cooling (PWM)1 BitCT
44RTC outputAct. variable basic cooling1 ByteCT
45RTC outputAct. var. add. cooling (PWM)1 BitCT
45RTC outputAct. variable add. cooling1 BitCT
45RTC outputAct. variable add. cooling1 ByteCT
46RTC outputPWM act. var. heating1 ByteCT
46RTC outputPWM act. var. basic heating1 ByteCT
46RTC outputPWM act. var. heating/cooling1 ByteCT
46RTC outputPWM act. var. basic stage1 ByteCT
47RTC outputPWM act. var. add. heating1 ByteCT
47RTC outputPWM act. var. add. Stage1 ByteCT
48RTC outputPWM act. var. cooling1 ByteCT
48RTC outputPWM act. var. basic cooling1 ByteCT
49RTC outputPWM act. var. add. cooling1 ByteCT
50RTC outputSetpoint temperature2 BytesCTU
51unneeded2 BytesCRWTU
52RTC outputSetpoint shift feedback1 ByteCTU
53RTC inputSetpoint shift preset1 ByteCWU
54unneeded1 ByteCRWTU
55unneeded1 BitCRWTU
56unneeded1 BitCRWTU
57RTC outputStatus report additional stage1 ByteCTU
58RTC outputActual temp. not adjusted2 BytesCT
Parameters (206)
ParameterTypeDefault
Control optionlistheating
Disable object additional stagelistNO
Transmit actuating variables for heating and cooling to shared objectlistNO
Type of heating controllistcontinuous PI control
Type of basic stage heatinglistcontinuous PI control
Type of controllistcontinuous PI control
Type of basic stage controllistcontinuous PI control
Type of heatinglisthot-water heating (5 K / 150 min)
Type of basic heatinglisthot-water heating (5 K / 150 min)
Proportional range heating (10 ... 127) * 0.1 KunsignedInt 10…12750
Lower hysteresis of the 2-state contr. heating (5 ... 127) * 0.1 KsignedInt -128…-5-5
Proportional range basic stage (10 ... 127) * 0.1 KunsignedInt 10…12750
Lower hysteresis of the 2-state contr. basic heating (5 ... 127) * 0.1 KsignedInt -128…-5-5
Reset time heating (0 ... 250) * 1 min; 0 = inactiveunsignedInt 0…255150
Upper hysteresis of the 2-state contr. heating (5 ... 127) * 0.1 KsignedInt 5…1275
Upper hysteresis of the 2-state contr. cooling (5 ... 127) * 0.1 KsignedInt 5…1275
Reset time basic stage (0 ... 250) * 1 min; 0 = inactiveunsignedInt 0…255150
Upper hysteresis of the 2-state contr. basic heating (5 ... 127) * 0.1 KsignedInt 5…1275
Upper hysteresis of the 2-state contr. basic cooling (5 ... 127) * 0.1 KsignedInt 5…1275
Type of additional stage coolinglisthot-water heating (5 K / 150 min)
Type of basic coolinglistcooling ceiling (5 K / 240 min)
Lower hysteresis of the 2-state contr. basic cooling (5 ... 127) * 0.1 KsignedInt -128…-5-5
Type of additional stage heatinglistcontinuous PI control
Reset time basic stage (0 ... 250) * 1 min; 0 = inactiveunsignedInt 0…255240
Type of additional stage controllistcontinuous PI control
Type of additional stage heatinglisthot-water heating (5 K / 150 min)
Lower hysteresis of the 2-state contr. additional heating (5 ... 127) * 0.1 KsignedInt -128…-5-5
Reset time heating (0 ... 250) * 1 min; 0 = inactiveunsignedInt 0…255100
Upper hysteresis of the 2-state contr. additional heating (5 ... 127) * 0.1 KsignedInt 5…1275
Upper hysteresis of the 2-state contr. additional cooling (5 ... 127) * 0.1 KsignedInt 5…1275
Type of cooling controllistcontinuous PI control
Type of basic stage coolinglistcontinuous PI control
Type of coolinglistcooling ceiling (5 K / 240 min)
Type of coolinglisthot-water heating (5 K / 150 min)
Type of basic coolinglisthot-water heating (5 K / 150 min)
Proportional range cooling (10 ... 127) * 0.1 KunsignedInt 10…12750
Lower hysteresis of the 2-state contr. cooling (5 ... 127) * 0.1 KsignedInt -128…-5-5
Reset time cooling (0 ... 250) * 1 min; 0 = inactiveunsignedInt 0…255240
Type of additional stage coolinglistcontinuous PI control
Type of additional stage coolinglistcooling ceiling (5 K / 240 min)
Lower hysteresis of the 2-state contr. additional cooling (5 ... 127) * 0.1 KsignedInt -128…-5-5
Proportional range additional stage (10 ... 127) * 0.1 KunsignedInt 10…12750
Reset time additional stage (0 ... 250) * 1 min; 0 = inactiveunsignedInt 0…255240
Operating mode switch-overlistvia value (1-byte)
Operating mode after resetliststandby mode
Operating mode when all bit objects = 0 (preferred state)liststandby mode
Basic temperature after reset (7 ... 40) * 1 °CunsignedInt 7…4021
Basic temperature setpoint changelistpermit via the bus
Adopt basic temperature setpoint permanentlylistNO
Frost protection setpoint temperature (7...40) * 1 °CunsignedInt 7…407
Heat protection setpoint temperature (7...45) * 1 °CunsignedInt 0…25535
Dead zone positionlistsymmetrical
Dead zone between heating and cooling (0...127) * 0,1 KunsignedInt 0…25520
Stage offset from the basic to the additional stage (0...127) * 0.,1 KunsignedInt 0…25520
Transmission when setpoint temperature changes by (0..255) * 0,1 K; 0=inactiveunsignedInt 0…2551
Cyclical transmission of setpoint temperature (0...255)*1 min; 0=inactiveunsignedInt 0…2550
Adjustment of setpoint to higher temperatureslist+ 3 K
Adjustment of setpoint to lower temperatureslist- 3 K
Decreasing the setpoint temperature in standby mode (heating) (-128...0)*0.1 KsignedInt -128…0-20
Decreasing the setpoint temperature in night mode (heating) (-128...0)*0,1 KsignedInt -128…0-40
Increasing the setpoint temperature in standby mode (cooling) (-128...0)*0,1 KsignedInt 0…12720
Increasing the setpoint temperature in night mode (cooling) (-128...0)*0,1 KsignedInt 0…12740
Presence detectionlistnone
Duration of comfort mode extension (0 .. 255) * 1 min; 0 = OFFunsignedInt 0…25530
Switching-over between heating and coolinglistautomatically
Automatic transmission heating/cooling switch-overlistwhen control option changes
Cycl. transm. of heating/cooling switch-over (0...255)*1 min;0=inactiveunsignedInt 0…2550
Control option heating/cooling after Resetlistheating
Switch-off controller (dew-point)listNO
Valve protectionlistNO
Temperature detectionlistinternal sensor
Determination of measured value from internal / external ratiolist50 % to 50 %
Calibration of internal sensor (-128...127) * 0.1 KsignedInt -128…12710
Calibration of external sensor (-128...127) * 0.1 KsignedInt -128…1270
Interrogation interval for ext. sensor (0...255) * 1 min; 0 = inactiveunsignedInt 0…2550
Transmission when room temperature changes by (0..255) * 0,1 K; 0=inactiveunsignedInt 0…2553
Cyclical transmission of room temperature (0...255)*1 min; 0=inactiveunsignedInt 0…25515
Actuating variable and status outputlistnormal (opened when sourcing current)
Automatic transm. if value changes by (0...100) * 1 %; 0 = inactiveunsignedInt 0…1003
Cycle time of switching variable (1...255) * 1 minunsignedInt 1…25515
Cycle time for automatic transmission (0...100)*1 %; 0=inactiveunsignedInt 0…25510
Output of actuating variable heatinglistnormal (opened when sourcing current)
Output of actuating variablelistnormal (opened when sourcing current)
Output of actuating variable basic stage heatinglistnormal (opened when sourcing current)
Output of actuating variable basic stage coolinglistnormal (opened when sourcing current)
Output of actuating variable basic stagelistnormal (opened when sourcing current)
Output of actuating variable additional stage heatinglistnormal (opened when sourcing current)
Output of actuating variable coolinglistnormal (opened when sourcing current)
Output of actuating variable additional stage coolinglistnormal (opened when sourcing current)
Output of actuating variable additional stagelistnormal (opened when sourcing current)
Heating messagelistNO
Cooling messagelistNO
Controller statuslistcontroller general
Individual statuslistcomfort mode active
Function of channel 1listbinary input
Function of channel 2listbinary input
Function of channel 3listbinary input
Function of channel 4listbinary input
Delay on return of bus voltage baselist1 s
Delay on return of bus voltage, factor (3 … 127)unsignedInt 3…12717
Debouncing time, (factor 10 … 255) (base = 0.5 ms)unsignedInt 10…25560
Telegram rate limitationlistdisabled
Telegrams per 17 slist30
Function of input 1listswitching
Function of output 1list1-bit actuating variable basic stage heating
Function aslistdimming value transmitter
Command on rising edge switching object 1.1listON
Transmit value onlistrising edge (key as make contact)
Operationlisttwo-surface control brighter (ON)
Command on rising edgelistUP
Transmit light-scene number onlistrising edge (key as make contact)
Command on falling edge switching object 1.1listOFF
Value on rising edge (0…255)unsignedInt 0…255100
Time between switching and dimming, baselist130 ms
Behaviour on return of bus voltagelistno function
Value on rising edgelist200 lux
Value on rising edgelist20 °C
Light-scene on rising edge (1…64)unsignedInt 1…641
Light-scene on falling edge (1…64)unsignedInt 1…641
Command on rising edge switching object 1.2listno function
Value on falling edge (0…255)unsignedInt 0…255100
Time between switching and dimming, factor (4 … 127)unsignedInt 4…1274
Operation conceptlistshort - long - short
Value on falling edgelist0 lux
Value on falling edgelist18 °C
Command on falling edge switching object 1.2listno function
Time between short- and long-time operation, baselist130 ms
Value adjustment by long presslistNO
Increase brightness bylist100%
Time between short- and long-time operation, factor (4 … 127)unsignedInt 4…1274
Storage function only?listNO
Cyclical transmission?listno cyclical transmission
Time between two telegrams, baselist520 ms
Reduce brightness bylist100%
Slat adjustment time baselist130 ms
Time between two telegrams, baselist130 ms
Time of a long press for storage baselist130 ms
Time between two telegrams, factor (3…127)unsignedInt 3…1273
Transmit stop telegramlistYES
Slat adjustment time factor time factor (3 … 127)unsignedInt 3…12720
Time of a long press for storage factor (9 … 127)unsignedInt 9…12710
Step width (1 … 10)unsignedInt 0…1510
Telegram repetitionlistNO
Time base for cyclical transmission switching object 1.1list1 s
Time base for cyclical transmission switching object 1.2listno cyclical transmission via switching object X.2
Time factor for cyclical transmission switching object 1.1 and 1.2 (3…127)unsignedInt 3…12760
Disabling function for switching object 1.1listdisabled
Disabling functionlistdisabled
Polarity of disable objectlistdisable = 1 (enable = 0)
Behaviour at the beginning of disable Switching object 1.1listno function
Behaviour at the beginning of disablelistno function
Behaviour at the end of disable Switching object 1.1listno function
Behaviour at the end of disablelistno function
Disabling function for switching object 1.2listdisabled
Behaviour at the beginning of disable Switching object 1.2listno function
Behaviour at the end of disable Switching object 1.2listno function
Function of input 2listswitching
Function of output 2list1-bit actuating variable basic stage heating
Command on rising edge switching object 2.1listON
Command on falling edge switching object 2.1listOFF
Command on rising edge switching object 2.2listno function
Command on falling edge switching object 2.2listno function
Time between two telegrams, factor (3…127)unsignedInt 3…12710
Time base for cyclical transmission switching object 2.1list1 s
Time base for cyclical transmission switching object 2.2listno cyclical transmission via switching object X.2
Time factor for cyclical transmission switching object 2.1 and 2.2 (3…127)unsignedInt 3…12760
Disabling function for switching object 2.1listdisabled
Behaviour at the beginning of disable Switching object 2.1listno function
Behaviour at the end of disable Switching object 2.1listno function
Disabling function for switching object 2.2listdisabled
Behaviour at the beginning of disable Switching object 2.2listno function
Behaviour at the end of disable Switching object 2.2listno function
Function of input 3listswitching
Command on rising edge switching object 3.1listON
Value on rising edge (0…255)unsignedInt 0…2550
Command on falling edge switching object 3.1listOFF
Value on falling edge (0…255)unsignedInt 0…2550
Command on rising edge switching object 3.2listno function
Command on falling edge switching object 3.2listno function
Time base for cyclical transmission switching object 3.1list1 s
Time base for cyclical transmission switching object 3.2listno cyclical transmission via switching object X.2
Time factor for cyclical transmission switching object 3.1 and 3.2 (3…127)unsignedInt 3…12760
Disabling function for switching object 3.1listdisabled
Behaviour at the beginning of disable Switching object 3.1listno function
Behaviour at the end of disable Switching object 3.1listno function
Disabling function for switching object 3.2listdisabled
Behaviour at the beginning of disable Switching object 3.2listno function
Behaviour at the end of disable Switching object 3.2listno function
Function of input 4listswitching
Command on rising edge switching object 4.1listON
Limit temperature (10 … 60) * 1 °CunsignedInt 10…6035
Command on falling edge switching object 4.1listOFF
Hysteresislist2 K
Command on rising edge switching object 4.2listno function
Acting onlistbasic stage heating
Command on falling edge switching object 4.2listno function
Time base for cyclical transmission switching object 4.1list1 s
Time base for cyclical transmission switching object 4.2listno cyclical transmission via switching object X.2
Time factor for cyclical transmission switching object 4.1 and 4.2 (3…127)unsignedInt 3…12760
Disabling function for switching object 4.1listdisabled
Behaviour at the beginning of disable Switching object 4.1listno function
Behaviour at the end of disable Switching object 4.1listno function
Disabling function for switching object 4.2listdisabled
Behaviour at the beginning of disable Switching object 4.2listno function
Behaviour at the end of disable Switching object 4.2listno function
Output of actuating variable heatinglist$00 F4 00 00 00 01

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Heating/cooling 705C/0.1 0.1 latest$705C09712026-11-25134 KBDownload
Heating/cooling 705C/0.1 0.1$705C09712026-11-25134 KBDownload

About this file

This is the official ETS product database for the Merten TCU UP/PI with 4-gang push-button interface (6169xx), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from Merten

All Merten products