| Control option | list | heating |
| Disable object additional stage | list | NO |
| Transmit actuating variables for
heating and cooling to shared object | list | NO |
| Type of heating control | list | continuous PI control |
| Type of basic stage heating | list | continuous PI control |
| Type of control | list | continuous PI control |
| Type of basic stage control | list | continuous PI control |
| Type of heating | list | hot-water heating (5 K / 150 min) |
| Type of basic heating | list | hot-water heating (5 K / 150 min) |
| Proportional range heating
(10 ... 127) * 0.1 K | unsignedInt 10…127 | 50 |
| Lower hysteresis of the 2-state contr.
heating (5 ... 127) * 0.1 K | signedInt -128…-5 | -5 |
| Proportional range basic stage
(10 ... 127) * 0.1 K | unsignedInt 10…127 | 50 |
| Lower hysteresis of the 2-state contr.
basic heating (5 ... 127) * 0.1 K | signedInt -128…-5 | -5 |
| Reset time heating
(0 ... 250) * 1 min; 0 = inactive | unsignedInt 0…255 | 150 |
| Upper hysteresis of the 2-state contr.
heating (5 ... 127) * 0.1 K | signedInt 5…127 | 5 |
| Upper hysteresis of the 2-state contr.
cooling (5 ... 127) * 0.1 K | signedInt 5…127 | 5 |
| Reset time basic stage
(0 ... 250) * 1 min; 0 = inactive | unsignedInt 0…255 | 150 |
| Upper hysteresis of the 2-state contr.
basic heating (5 ... 127) * 0.1 K | signedInt 5…127 | 5 |
| Upper hysteresis of the 2-state contr.
basic cooling (5 ... 127) * 0.1 K | signedInt 5…127 | 5 |
| Type of additional stage cooling | list | hot-water heating (5 K / 150 min) |
| Type of basic cooling | list | cooling ceiling (5 K / 240 min) |
| Lower hysteresis of the 2-state contr.
basic cooling (5 ... 127) * 0.1 K | signedInt -128…-5 | -5 |
| Type of additional stage heating | list | continuous PI control |
| Reset time basic stage
(0 ... 250) * 1 min; 0 = inactive | unsignedInt 0…255 | 240 |
| Type of additional stage control | list | continuous PI control |
| Type of additional stage heating | list | hot-water heating (5 K / 150 min) |
| Lower hysteresis of the 2-state contr.
additional heating (5 ... 127) * 0.1 K | signedInt -128…-5 | -5 |
| Reset time heating
(0 ... 250) * 1 min; 0 = inactive | unsignedInt 0…255 | 100 |
| Upper hysteresis of the 2-state contr.
additional heating (5 ... 127) * 0.1 K | signedInt 5…127 | 5 |
| Upper hysteresis of the 2-state contr.
additional cooling (5 ... 127) * 0.1 K | signedInt 5…127 | 5 |
| Type of cooling control | list | continuous PI control |
| Type of basic stage cooling | list | continuous PI control |
| Type of cooling | list | cooling ceiling (5 K / 240 min) |
| Type of cooling | list | hot-water heating (5 K / 150 min) |
| Type of basic cooling | list | hot-water heating (5 K / 150 min) |
| Proportional range cooling
(10 ... 127) * 0.1 K | unsignedInt 10…127 | 50 |
| Lower hysteresis of the 2-state contr.
cooling (5 ... 127) * 0.1 K | signedInt -128…-5 | -5 |
| Reset time cooling
(0 ... 250) * 1 min; 0 = inactive | unsignedInt 0…255 | 240 |
| Type of additional stage cooling | list | continuous PI control |
| Type of additional stage cooling | list | cooling ceiling (5 K / 240 min) |
| Lower hysteresis of the 2-state contr.
additional cooling (5 ... 127) * 0.1 K | signedInt -128…-5 | -5 |
| Proportional range additional stage
(10 ... 127) * 0.1 K | unsignedInt 10…127 | 50 |
| Reset time additional stage
(0 ... 250) * 1 min; 0 = inactive | unsignedInt 0…255 | 240 |
| Operating mode switch-over | list | via value (1-byte) |
| Operating mode after reset | list | standby mode |
| Operating mode when all
bit objects = 0 (preferred state) | list | standby mode |
| Basic temperature after reset
(7 ... 40) * 1 °C | unsignedInt 7…40 | 21 |
| Basic temperature setpoint change | list | permit via the bus |
| Adopt basic temperature setpoint
permanently | list | NO |
| Frost protection setpoint temperature
(7...40) * 1 °C | unsignedInt 7…40 | 7 |
| Heat protection setpoint temperature
(7...45) * 1 °C | unsignedInt 0…255 | 35 |
| Dead zone position | list | symmetrical |
| Dead zone between heating and cooling
(0...127) * 0,1 K | unsignedInt 0…255 | 20 |
| Stage offset from the basic to the
additional stage (0...127) * 0.,1 K | unsignedInt 0…255 | 20 |
| Transmission when setpoint temperature
changes by (0..255) * 0,1 K; 0=inactive | unsignedInt 0…255 | 1 |
| Cyclical transmission of setpoint
temperature (0...255)*1 min; 0=inactive | unsignedInt 0…255 | 0 |
| Adjustment of setpoint to higher
temperatures | list | + 3 K |
| Adjustment of setpoint to lower
temperatures | list | - 3 K |
| Decreasing the setpoint temperature in
standby mode (heating) (-128...0)*0.1 K | signedInt -128…0 | -20 |
| Decreasing the setpoint temperature in
night mode (heating) (-128...0)*0,1 K | signedInt -128…0 | -40 |
| Increasing the setpoint temperature in
standby mode (cooling) (-128...0)*0,1 K | signedInt 0…127 | 20 |
| Increasing the setpoint temperature in
night mode (cooling) (-128...0)*0,1 K | signedInt 0…127 | 40 |
| Presence detection | list | none |
| Duration of comfort mode extension
(0 .. 255) * 1 min; 0 = OFF | unsignedInt 0…255 | 30 |
| Switching-over between heating
and cooling | list | automatically |
| Automatic transmission heating/cooling
switch-over | list | when control option changes |
| Cycl. transm. of heating/cooling
switch-over (0...255)*1 min;0=inactive | unsignedInt 0…255 | 0 |
| Control option heating/cooling
after Reset | list | heating |
| Switch-off controller (dew-point) | list | NO |
| Valve protection | list | NO |
| Temperature detection | list | internal sensor |
| Determination of measured value from
internal / external ratio | list | 50 % to 50 % |
| Calibration of internal sensor
(-128...127) * 0.1 K | signedInt -128…127 | 10 |
| Calibration of external sensor
(-128...127) * 0.1 K | signedInt -128…127 | 0 |
| Interrogation interval for ext. sensor
(0...255) * 1 min; 0 = inactive | unsignedInt 0…255 | 0 |
| Transmission when room temperature
changes by (0..255) * 0,1 K; 0=inactive | unsignedInt 0…255 | 3 |
| Cyclical transmission of room
temperature (0...255)*1 min; 0=inactive | unsignedInt 0…255 | 15 |
| Actuating variable and status output | list | normal (opened when sourcing current) |
| Automatic transm. if value changes by
(0...100) * 1 %; 0 = inactive | unsignedInt 0…100 | 3 |
| Cycle time of switching
variable (1...255) * 1 min | unsignedInt 1…255 | 15 |
| Cycle time for automatic
transmission (0...100)*1 %; 0=inactive | unsignedInt 0…255 | 10 |
| Output of actuating variable heating | list | normal (opened when sourcing current) |
| Output of actuating variable | list | normal (opened when sourcing current) |
| Output of actuating variable
basic stage heating | list | normal (opened when sourcing current) |
| Output of actuating variable
basic stage cooling | list | normal (opened when sourcing current) |
| Output of actuating variable
basic stage | list | normal (opened when sourcing current) |
| Output of actuating variable
additional stage heating | list | normal (opened when sourcing current) |
| Output of actuating variable cooling | list | normal (opened when sourcing current) |
| Output of actuating variable
additional stage cooling | list | normal (opened when sourcing current) |
| Output of actuating variable
additional stage | list | normal (opened when sourcing current) |
| Heating message | list | NO |
| Cooling message | list | NO |
| Controller status | list | controller general |
| Individual status | list | comfort mode active |
| Function of channel 1 | list | binary input |
| Function of channel 2 | list | binary input |
| Function of channel 3 | list | binary input |
| Function of channel 4 | list | binary input |
| Delay on return of bus voltage
base | list | 1 s |
| Delay on return of bus voltage,
factor (3 … 127) | unsignedInt 3…127 | 17 |
| Debouncing time, (factor 10 … 255)
(base = 0.5 ms) | unsignedInt 10…255 | 60 |
| Telegram rate limitation | list | disabled |
| Telegrams per 17 s | list | 30 |
| Function of input 1 | list | switching |
| Function of output 1 | list | 1-bit actuating variable basic stage heating |
| Function as | list | dimming value transmitter |
| Command on rising edge
switching object 1.1 | list | ON |
| Transmit value on | list | rising edge (key as make contact) |
| Operation | list | two-surface control brighter (ON) |
| Command on rising edge | list | UP |
| Transmit light-scene number on | list | rising edge (key as make contact) |
| Command on falling edge
switching object 1.1 | list | OFF |
| Value on rising edge
(0…255) | unsignedInt 0…255 | 100 |
| Time between switching and dimming,
base | list | 130 ms |
| Behaviour on return of bus voltage | list | no function |
| Value on rising edge | list | 200 lux |
| Value on rising edge | list | 20 °C |
| Light-scene on rising edge
(1…64) | unsignedInt 1…64 | 1 |
| Light-scene on falling edge
(1…64) | unsignedInt 1…64 | 1 |
| Command on rising edge
switching object 1.2 | list | no function |
| Value on falling edge
(0…255) | unsignedInt 0…255 | 100 |
| Time between switching and dimming,
factor (4 … 127) | unsignedInt 4…127 | 4 |
| Operation concept | list | short - long - short |
| Value on falling edge | list | 0 lux |
| Value on falling edge | list | 18 °C |
| Command on falling edge
switching object 1.2 | list | no function |
| Time between short- and long-time
operation, base | list | 130 ms |
| Value adjustment by long press | list | NO |
| Increase brightness by | list | 100% |
| Time between short- and long-time
operation, factor (4 … 127) | unsignedInt 4…127 | 4 |
| Storage function only? | list | NO |
| Cyclical transmission? | list | no cyclical transmission |
| Time between two telegrams,
base | list | 520 ms |
| Reduce brightness by | list | 100% |
| Slat adjustment time base | list | 130 ms |
| Time between two telegrams,
base | list | 130 ms |
| Time of a long press for storage
base | list | 130 ms |
| Time between two telegrams,
factor (3…127) | unsignedInt 3…127 | 3 |
| Transmit stop telegram | list | YES |
| Slat adjustment time factor
time factor (3 … 127) | unsignedInt 3…127 | 20 |
| Time of a long press for storage
factor (9 … 127) | unsignedInt 9…127 | 10 |
| Step width (1 … 10) | unsignedInt 0…15 | 10 |
| Telegram repetition | list | NO |
| Time base for cyclical transmission
switching object 1.1 | list | 1 s |
| Time base for cyclical transmission
switching object 1.2 | list | no cyclical transmission via switching object X.2 |
| Time factor for cyclical transmission
switching object 1.1 and 1.2 (3…127) | unsignedInt 3…127 | 60 |
| Disabling function for
switching object 1.1 | list | disabled |
| Disabling function | list | disabled |
| Polarity of disable object | list | disable = 1 (enable = 0) |
| Behaviour at the beginning of disable
Switching object 1.1 | list | no function |
| Behaviour at the beginning of disable | list | no function |
| Behaviour at the end of disable
Switching object 1.1 | list | no function |
| Behaviour at the end of disable | list | no function |
| Disabling function for
switching object 1.2 | list | disabled |
| Behaviour at the beginning of disable
Switching object 1.2 | list | no function |
| Behaviour at the end of disable
Switching object 1.2 | list | no function |
| Function of input 2 | list | switching |
| Function of output 2 | list | 1-bit actuating variable basic stage heating |
| Command on rising edge
switching object 2.1 | list | ON |
| Command on falling edge
switching object 2.1 | list | OFF |
| Command on rising edge
switching object 2.2 | list | no function |
| Command on falling edge
switching object 2.2 | list | no function |
| Time between two telegrams,
factor (3…127) | unsignedInt 3…127 | 10 |
| Time base for cyclical transmission
switching object 2.1 | list | 1 s |
| Time base for cyclical transmission
switching object 2.2 | list | no cyclical transmission via switching object X.2 |
| Time factor for cyclical transmission
switching object 2.1 and 2.2 (3…127) | unsignedInt 3…127 | 60 |
| Disabling function for
switching object 2.1 | list | disabled |
| Behaviour at the beginning of disable
Switching object 2.1 | list | no function |
| Behaviour at the end of disable
Switching object 2.1 | list | no function |
| Disabling function for
switching object 2.2 | list | disabled |
| Behaviour at the beginning of disable
Switching object 2.2 | list | no function |
| Behaviour at the end of disable
Switching object 2.2 | list | no function |
| Function of input 3 | list | switching |
| Command on rising edge
switching object 3.1 | list | ON |
| Value on rising edge
(0…255) | unsignedInt 0…255 | 0 |
| Command on falling edge
switching object 3.1 | list | OFF |
| Value on falling edge
(0…255) | unsignedInt 0…255 | 0 |
| Command on rising edge
switching object 3.2 | list | no function |
| Command on falling edge
switching object 3.2 | list | no function |
| Time base for cyclical transmission
switching object 3.1 | list | 1 s |
| Time base for cyclical transmission
switching object 3.2 | list | no cyclical transmission via switching object X.2 |
| Time factor for cyclical transmission
switching object 3.1 and 3.2 (3…127) | unsignedInt 3…127 | 60 |
| Disabling function for
switching object 3.1 | list | disabled |
| Behaviour at the beginning of disable
Switching object 3.1 | list | no function |
| Behaviour at the end of disable
Switching object 3.1 | list | no function |
| Disabling function for
switching object 3.2 | list | disabled |
| Behaviour at the beginning of disable
Switching object 3.2 | list | no function |
| Behaviour at the end of disable
Switching object 3.2 | list | no function |
| Function of input 4 | list | switching |
| Command on rising edge
switching object 4.1 | list | ON |
| Limit temperature (10 … 60) * 1 °C | unsignedInt 10…60 | 35 |
| Command on falling edge
switching object 4.1 | list | OFF |
| Hysteresis | list | 2 K |
| Command on rising edge
switching object 4.2 | list | no function |
| Acting on | list | basic stage heating |
| Command on falling edge
switching object 4.2 | list | no function |
| Time base for cyclical transmission
switching object 4.1 | list | 1 s |
| Time base for cyclical transmission
switching object 4.2 | list | no cyclical transmission via switching object X.2 |
| Time factor for cyclical transmission
switching object 4.1 and 4.2 (3…127) | unsignedInt 3…127 | 60 |
| Disabling function for
switching object 4.1 | list | disabled |
| Behaviour at the beginning of disable
Switching object 4.1 | list | no function |
| Behaviour at the end of disable
Switching object 4.1 | list | no function |
| Disabling function for
switching object 4.2 | list | disabled |
| Behaviour at the beginning of disable
Switching object 4.2 | list | no function |
| Behaviour at the end of disable
Switching object 4.2 | list | no function |
| Output of actuating variable heating | list | $00 F4 00 00 00 01 |