| 1. Download OK | list | yes |
| Download bereits bearbeitet ? | list | no |
| General | list | Page |
| Supported functions | list | heating and cooling |
| Only ventilation | list | yes |
| Heating installation | list | fan coil |
| Model of heat exchanger | list | fan coil |
| Cooling installation | list | fan coil |
| Kind of installation | list | 2-pipe system |
| Kind of used controler | list | remote controller |
| Test mode | list | disabled |
| Report filter change | list | no |
| activate monitoring of actuating value | list | no |
| Switch fan between Auto and forced mode | list | via obj. Auto/forced, forced = 1 |
| Fan | list | Page |
| Number of fan steps | list | 3 steps |
| Switch-on threshold for fan step 1 | list | 10 % |
| Switch-on threshold for fan step 2 | list | 40 % |
| Switch-on threshold for fan step 3 | list | 70 % |
| Fan starting strategy | list | directly |
| Switching delay between 2 fan steps | list | 0,5 s |
| Minimum time to stay within a fan step | list | 2 min |
| Hysteresis between the fan steps | list | 10 % |
| Additional ventilation | list | no |
| Warm start | list | no warm start |
| Follow-up time for utilisation
of the remaining energy | list | no follow-up |
| Cyclical transmission of fan step | list | Format %, don´t transmit cyclically |
| Heating valve | list | Page |
| Heating/cooling valve | list | Page |
| Cooling valve | list | Page |
| Type of valve | list | 3-point valve |
| Direction of control action of valve | list | normal |
| Runtime for 100% travel (5 .. 2000s) | unsignedInt 5…2000 | 90 |
| PWM time | list | 5 min |
| Time for the heating valve to close | list | 3 min |
| Time for the valve to close | list | 3 min |
| Time for the cooling valve to close | list | 3 min |
| New position at change of | list | 5 % |
| Open for actuating value above | list | 0,4 % |
| Minimum valve position | list | 0 % |
| Maximum valve position above | list | 50 % |
| Maximum valve position | list | 100 % |
| Cyclical transmission of heating status | list | don´t transmit cyclically |
| Delay between heating and cooling | list | 0 min |
| Cyclical transmission of
cooling status every | list | don´t transmit cyclically |
| Cyclical transmission of
heating/cooling status | list | don´t transmit cyclically |
| Auxilliary relay | list | Page |
| Switch ON auxilliary relay | list | via object |
| Cyclical transmission of aux.
relay status every | list | don´t transmit cyclically |
| E1 | list | Page |
| E1 in case of remote controller | list | yes |
| E1 in case of internal controller | list | yes |
| Function of E1 | list | E1 = window contact |
| Direction of operation of window contact | list | contact closed = window closed |
| Actual value offset in 0.1 K (-50..50) | signedInt -50…50 | 0 |
| Transmission of actual value
at change of | list | every 0,5 K |
| Cyclical transmission of window contact | list | don´t transmit cyclically |
| Cyclical transmission of actual value | list | don´t transmit cyclically |
| Actuating value in case of sensor
failure or short circuit | list | 20 % |
| Report sensor failure
(1 = failure) | list | only if object value = 1 |
| Report cyclically | list | every 30 min |
| Drip tray monitoring | list | Page |
| E2 | list | Page |
| Source for drip tray monitoring | list | E2 |
| Direction of operation of contact | list | contact closed = condensate |
| Direction of action of E2 | list | contact closed = condensate |
| Direction of operation of contact | list | contact closed = window closed |
| Behaviour in case of drip tray alarm | list | cooling and fan OFF |
| Cyclical transmission of alarm status | list | don´t transmit cyclically |
| Cyclical transmission of E2 status | list | don´t transmit cyclically |
| Set point adjustment | list | Page |
| Set point adjustment | list | yes |
| Set point adjustment from | list | 25 °C |
| Adjustment | list | 1 K per 3 K outdoor temperature |
| Format of the adjustment value | list | relative |
| Base set point without adjustment | list | 21 °C |
| Cyclical transmission of set point
adjustment | list | don´t transmit cyclically |
| Use set point adjustment for regulation | list | no |
| Set point values | list | Page |
| Set point values | list | yes |
| Base set point after reset | list | 21 °C |
| Reduction in standby operating mode | list | 2 K |
| Reduction in standby operating mode
at heating | list | 2 K |
| Reduction in night operating mode | list | 5 K |
| Reduction in night operating mode
at heating | list | 5 K |
| Set point value for frost protection
mode | list | 6 °C |
| Set point value for frost protection
(at heating) | list | 6 °C |
| Dead zone between heating and cooling | list | 2 K |
| Cyclical transmission of
current set point value | list | don´t transmit cyclically |
| Increasing in standby mode
at cooling | list | 2 K |
| Increasing in standby mode | list | 2 K |
| Increasing in night mode
at cooling | list | 5 K |
| Increasing in night mode | list | 5 K |
| Set point value for heat protection
(at cooling) | list | 42 °C ( = no heat protection) |
| Set point value for heat protection | list | 42 °C ( = no heat protection) |
| Current set point value in comfort mode | list | transmit actual temp. setpoint (heating<>cooling) |
| Regulation | list | Page |
| Regulation | list | yes |
| Setting of control parameters | list | standard |
| Proportional band of heating controller | list | 2 K |
| Integral action time constant
of heating controller | list | 150 min |
| Proportional band of cooling controller | list | 4 K |
| Integral time of cooling controller | list | 90 min |
| Cyclical transmission of actuating
value every | list | 15 min |
| Heating/cooling | list | auto |
| Report, when no energy medium | list | only if object value = 1 |
| Transmission of actuating value | list | at change of 5 % |
| Report, when heating required
but heating disabled | list | only if object value = 1 |
| Report, when cooling required
but cooling disabled | list | only if object value = 1 |
| Operating mode and operation | list | Page |
| Operating mode | list | yes |
| Operating mode after reset | list | standby |
| Cyclical transmission of
current op. mode every | list | don´t transmit cyclically |
| Mode setting objects | list | new: operating mode, presence, window state |
| Kind of presence detector | list | presence detector |
| Time for comfort extension | list | 2 h |
| Limitation of manual value
increasing/decreasing | list | +/- 3 K |
| Filter monitoring | list | Page |
| Message for filter change after duty
time of (1..127 weeks) | unsignedInt 1…127 | 12 |
| transmit filter replacement cyclically | list | only at filter change |
| transmit fan duty time
(in hours) | list | never transmit (reading is possible) |
| Cycle time for filter replacement
and fan duty time | list | every 60 min |
| Monitor actuating value | list | yes |
| Actuating value loss | list | Page |
| Monitoring time for actuating value | list | 60 min |
| Substitute actuating value
emergency program | list | 20 % |
| Report actuating value loss cyclically
(1 = no act. value) | list | only if object value = 1 |
| Objects 15 and 20 visible | list | yes |