KNX Database

Universal dimming actuator REG-K/2x230/300W 649330

Merten · Order number 649330 · 4.6 Dimming Actuator › 4.6.01 DIN rail mounted REG-K

649330

Download .knxprod Universal dimming 3242/1.0 1.0 · 115 KB

Product

ManufacturerMerten
Product nameUniversal dimming actuator REG-K/2x230/300W
Order number649330
HardwareUniversal-Dimmaktor REG-K
MediumTwisted Pair
Rail mountedYes
Width (mm)105
RegistrationRegistered
Languagesen-US, de-DE
Catalog entryM-000C_H-6493xx-1_HP-3242-10-B5BC_CI-649330-1
FingerprintB5BC
SHA-256c6c146dc65f2cfeb1bb7f461a1ba3fcc050c790837ad99af6437776789639874
First seen2026-11-25
MarketsArgentina, Australia, Austria, Germany, Uruguay

Application program: Universal dimming 3242/1.0 1.0

Application number$3242
Version1.0
Mask versionMV-0021 (2.1)
KNX Data SecureNo
Parameters697
Group objects65
Group objects (65)
NoNameFunctionSizeDPTFlags
0Switch objectChannel 1, general1 BitCW
1Dimming objectChannel 1, general4 BitCW
2Value objectChannel 1, general1 ByteCW
3Set objectChannel 1, dimming speed1 ByteCW
4Dimming time reduction objectChannel 1, dimming speed1 ByteCW
5Staircase timer objectChannel 1, staircase lighting1 BitCW
6Logic objectChannel1, high.priority funct.1 BitCW
6PriorityChannel1, high.priority funct.2 BitCW
7Locking objectChannel1, high.priority funct.1 BitCW
8Status feedback switchChannel 1, status feedback1 BitCT
8Status switchChannel 1, status1 BitCR
9Status feedback value object/brightness valueChannel 1, status feedback1 ByteCT
9Status value object/brightness valueChannel 1, status1 ByteCR
10Switch objectChannel 2, general1 BitCW
11Dimming objectChannel 2, general4 BitCW
12Value objectChannel 2, general1 ByteCW
13Set objectChannel 2, dimming speed1 ByteCW
14Dimming time reduction objectChannel 2, dimming speed1 ByteCW
15Staircase timer objectChannel 2, staircase lighting1 BitCW
16Logic objectChannel2, high.priority funct.1 BitCW
16PriorityChannel2, high.priority funct.2 BitCW
17Locking objectChannel2, high.priority funct.1 BitCW
18Status feedback switchChannel 2, status feedback1 BitCT
18Status switchChannel 2, status1 BitCR
19Status feedback value object/brightness valueChannel 2, status feedback1 ByteCT
19Status value object/brightness valueChannel 2, status1 ByteCR
20Switch objectChannel 3, general1 BitCW
21Dimming objectChannel 3, general4 BitCW
22Value objectChannel 3, general1 ByteCW
23Set objectChannel 3, dimming speed1 ByteCW
24Dimming time reduction objectChannel 3, dimming speed1 ByteCW
25Staircase timer objectChannel 3, staircase lighting1 BitCW
26Logic objectChannel3, high.priority funct.1 BitCW
26PriorityChannel3, high.priority funct.2 BitCW
27Locking objectChannel3, high.priority funct.1 BitCW
28Status feedback switchChannel 3, status feedback1 BitCT
28Status switchChannel 3, status1 BitCR
29Status feedback value object/brightness valueChannel 3, status feedback1 ByteCT
29Status value object/brightness valueChannel 3, status1 ByteCR
30Switch objectChannel 4, general1 BitCW
31Dimming objectChannel 4, general4 BitCW
32Value objectChannel 4, general1 ByteCW
33Set objectChannel 4, dimming speed1 ByteCW
34Dimming time reduction objectChannel 4, dimming speed1 ByteCW
35Staircase timer objectChannel 4, staircase lighting1 BitCW
36Logic objectChannel4, high.priority funct.1 BitCW
36PriorityChannel4, high.priority funct.2 BitCW
37Locking objectChannel4, high.priority funct.1 BitCW
38Status feedback switchChannel 4, status feedback1 BitCT
38Status switchChannel 4, status1 BitCR
39Status feedback value object/brightness valueChannel 4, status feedback1 ByteCT
39Status value object/brightness valueChannel 4, status1 ByteCR
40Scene objectScenes1 ByteCW
41Recall scene 1/2Scene extension input1 BitCW
42Recall scene 3/4Scene extension input1 BitCW
43Save scene 1/2Scene extension input1 BitCW
44Save scene 3/4Scene extension input1 BitCW
45Central switch objectCentral function1 BitCW
46Central dimming objectCentral function4 BitCW
47Central value objectCentral function1 ByteCW
48Status feedback errorStatus feedback1 BitCT
48Status errorStatus1 BitCR
49Block channel operationOperation1 BitCRW
50Block extension inputsOperation1 BitCRW
51Factor for identical dimming timeSame dimming time1 ByteCW
Parameters (205)
ParameterTypeDefault
GenerallistDummy
Internal ETS identification highunsignedInt 66…6666
Internal ETS identification lowunsignedInt 50…5050
Internal ETS version highunsignedInt 64…6464
Internal ETS version lowunsignedInt 0…00
Channel 1listdeactivated
Channel 2listdeactivated
Channel 3listdeactivated
Channel 4listdeactivated
Sceneslistdisabled
Ext. input Sceneslistdisabled
Central functionlistdisabled
Central switch objectlistactivated
Central dimming objectlistdeactivated
Central value objectlistdeactivated
Same dimming time at central function and sceneslistdisabled
Channel operationlistenabled
Extension inputslistenabled
Status errorlistdeactivated
Same dimming timelistDummy
Time base for same dimming timelist1 s
Time factor for same dimming time 1-255unsignedInt 1…2555
Time factor for same dimming time selectable via buslistdeactivated
1: GenerallistDummy
Minimum dimming value in %unsignedInt 1…10015
Maximum dimming value in %unsignedInt 1…100100
Starting behaviourlistmax. brightness
Initial brightness in %unsignedInt 5…100100
Base dimming curvelistincandescent lamps
Dimming object switches channellistonly ON, not OFF
Value object switches channellistON and OFF
Extension unit input influenceslistSwitch object
Extension inputlistenabled
Delay timeslistdisabled
Staircase lighting functionlistdeactivated
Switch object effectivelistunchanged
Higher priority functionlistdeactivated
Disable functionlistdeactivated
Behaviour on bus voltage recovery and downloadlistno reaction
Status switchlistdeactivated
Status value object/brightness valuelistdeactivated
1: Base dimming curvelistDummy
1st threshold value in %unsignedInt 0…10025
2nd threshold value in %unsignedInt 0…10050
3rd threshold value in %unsignedInt 0…10075
Time base of 1st dimming sectionlist100 ms
Time factor of 1st dimming section (1-255)unsignedInt 1…255230
Time base of 2nd dimming sectionlist100 ms
Time factor of 2nd dimming section (1-255)unsignedInt 1…255180
Time base of 3rd dimming sectionlist100 ms
Time factor of 3rd dimming section (1-255)unsignedInt 1…255120
Time base of 4th dimming sectionlist100 ms
Time factor of 4th dimming section (1-255)unsignedInt 1…25570
1: Dimming time reductionlistDummy
Dimming time reduction object for dimming curvelistdeactivated
Format of dimming time reductionlist1 - 100 %
for switching telegrams and staircase lighting, switch on atlist2 %
for switching telegrams and staircase lighting, switch on at x/2.55 %unsignedInt 1…2555
for dimming telegrams tolist6 %
for dimming telegrams to x/2.55 %unsignedInt 1…25516
for staircase lighting switch off atlist50 %
for staircase lighting switch off at x/2.55 %unsignedInt 1…255128
for value telegrams atlist20 %
for value telegrams at x/2.55 %unsignedInt 1…25551
for scene telegrams atlist32 %
for scene telegrams at x/2.55 %unsignedInt 1…25582
for priority functions atlist2 %
for prioritised functions at x/2.55 %unsignedInt 1…2555
Set 1 to 3listdisabled
for switching telegrams and staircase lighting, switch on atlist6 %
for switching telegrams and staircase lighting, switch on at x/2.55 %unsignedInt 1…25515
for dimming telegrams tolist20 %
for dimming telegrams to x/2.55 %unsignedInt 1…25551
for staircase lighting switch off atlist70 %
for staircase lighting switch off at x/2.55 %unsignedInt 1…255179
for value telegrams atlist30 %
for value telegrams at x/2.55 %unsignedInt 1…25577
for scene telegrams atlist70 %
for scene telegrams at x/2.55 %unsignedInt 1…255179
for priority functions atlist5 %
for prioritised functions at x/2.55 %unsignedInt 1…25513
for switching telegrams and staircase lighting, switch on atlist3 %
for switching telegrams and staircase lighting, switch on at x/2.55 %unsignedInt 1…2558
for dimming telegrams tolist15 %
for dimming telegrams to x/2.55 %unsignedInt 1…25538
for staircase lighting switch off atlist40 %
for staircase lighting switch off at x/2.55 %unsignedInt 1…255102
for value telegrams atlist15 %
for value telegrams at x/2.55 %unsignedInt 1…25538
for scene telegrams atlist25 %
for scene telegrams at x/2.55 %unsignedInt 1…25564
for priority functions atlist3 %
for prioritised functions at x/2.55 %unsignedInt 1…2558
for switching telegrams and staircase lighting, switch on atlist1 %
for switching telegrams and staircase lighting, switch on at x/2.55 %unsignedInt 1…2553
for dimming telegrams tolist7 %
for dimming telegrams to x/2.55 %unsignedInt 1…25518
for staircase lighting switch off atlist25 %
for staircase lighting switch off at x/2.55 %unsignedInt 1…25564
for value telegrams atlist10 %
for value telegrams at x/2.55 %unsignedInt 1…25526
for scene telegrams atlist20 %
for scene telegrams at x/2.55 %unsignedInt 1…25551
for priority functions atlist1 %
for prioritised functions at x/2.55 %unsignedInt 1…2553
1: Delay timeslistDummy
ON delaylistdeactivated
Output during ON delaylistswitched off
Time base for ON delaylist1 min
Time factor for ON delay (1-255)unsignedInt 1…2553
OFF delaylistdeactivated
Time base for OFF delaylist1 min
Time factor for OFF delay (1-255)unsignedInt 1…2553
1: Staircase timerlistDummy
Staircase lighting functionlistnot retriggerable with manual OFF
Time base for staircase timerlist1 min
Max.number of time accumulations (1-255)unsignedInt 1…2553
Time factor for staircase timer (1-255)unsignedInt 1…2553
Staircase lighting object effectivelistunchanged
Staircase lighting objectlistunchanged
Disconnection warning for stairc.timerlistdeactivated
Warning time for staircase timer in seconds (1-255)unsignedInt 1…25530
1: SceneslistDummy
Overwrite scene values in actuator during downloadlistactivated
Same dimming timelistdeactivated
Scene 1listdeactivated
Scene 1: Scene number (0-63)unsignedInt 0…630
Scene 1: Brightness value in %unsignedInt 0…10015
Scene 2listdeactivated
Scene 2: Scene number (0-63)unsignedInt 0…631
Scene 2: Brightness value in %unsignedInt 0…10035
Scene 3listdeactivated
Scene 3: Scene number (0-63)unsignedInt 0…632
Scene 3: Brightness value in %unsignedInt 0…10050
Scene 4listdeactivated
Scene 4: Scene number (0-63)unsignedInt 0…633
Scene 4: Brightness value in %unsignedInt 0…10065
Scene 5listdeactivated
Scene 5: Scene number (0-63)unsignedInt 0…634
Scene 5: Brightness value in %unsignedInt 0…10080
Scene 6listdeactivated
Scene 6: Scene number (0-63)unsignedInt 0…635
Scene 6: Brightness value in %unsignedInt 0…10080
Scene 7listdeactivated
Scene 7: Scene number (0-63)unsignedInt 0…636
Scene 7: Brightness value in %unsignedInt 0…10080
Scene 8listdeactivated
Scene 8: Scene number (0-63)unsignedInt 0…637
Scene 8: Brightness value in %unsignedInt 0…10080
1: Central functionlistDummy
Function at central switching value = 0listswitch off
Desired brightness at switching object central = 0 in %unsignedInt 5…100100
Function at central switching value = 1listswitch on at selectable brightness
Desired brightness at switching object central = 1 in %unsignedInt 5…100100
1: Logic operationlistDummy
Logic operationlistOR
Logic object effectivelistunchanged
Value of logic operation object after bus voltage recovery and downloadlist1
Brightness with logic object "0" in %unsignedInt 0…1000
Brightness with logic object "1" in %unsignedInt 0…1000
1: PrioritylistDummy
Behaviour at start of priority function "ON"listswitch on at selectable brightness
Desired brightness at start of priority function "ON" in %unsignedInt 5…100100
Behaviour at start of priority function "OFF"listswitch off
Desired brightness at start of priority function "OFF" in %unsignedInt 5…100100
Behaviour at end of priority functionlistfollows secondary functions
Desired brightness at end of priority function in %unsignedInt 5…100100
Behaviour of priority function after bus voltage recoverylistinactive
1: Disable functionlistDummy
Lockinglistat object value "1"
Behaviour at start of lockinglistno reaction
Desired brightness at start of disable function in %unsignedInt 5…100100
Behaviour at the end of lockinglistno reaction
Desired brightness at end of disable function in %unsignedInt 5…100100
Status of disable function after bus voltage recoverylistinactive
2: GenerallistDummy
2: Base dimming curvelistDummy
2: Dimming time reductionlistDummy
2: Delay timeslistDummy
2: Staircase timerlistDummy
2: SceneslistDummy
2: Central functionlistDummy
2: Logic operationlistDummy
2: PrioritylistDummy
2: Disable functionlistDummy
3: GenerallistDummy
3: Base dimming curvelistDummy
3: dimming time reductionlistDummy
3: Delay timeslistDummy
3: Staircase timerlistDummy
3: SceneslistDummy
3: Central functionlistDummy
3: Logic operationlistDummy
3: PrioritylistDummy
3: Disable functionlistDummy
4: GenerallistDummy
4: Base dimming curvelistDummy
4: dimming time reductionlistDummy
4: Delay timeslistDummy
4: Staircase timerlistDummy
4: SceneslistDummy
4: Central functionlistDummy
4: Logic operationlistDummy
4: PrioritylistDummy
4: Disable functionlistDummy

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Universal dimming 3242/1.0 1.0 latest$3242B5BC2026-11-25115 KBDownload

About this file

This is the official ETS product database for the Merten Universal dimming actuator REG-K/2x230/300W (649330), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from Merten

All Merten products