STR-640.02S KNX Redundant Bus power supply with diagnosis function, 640mA STR-0640.02S

MDT technologies GmbH · Order number STR-0640.02S · Power supply › KNX Bus power supply with diagnosis function

Download .knxprod Bus Power Supply 1.0 · 148 KB

Product

ManufacturerMDT technologies GmbH
Product nameSTR-640.02S KNX Redundant Bus power supply with diagnosis function, 640mA
Order numberSTR-0640.02S
HardwareRedundante Busspannungsversorgung mit Diagnosefunktion, 640mA
MediumTwisted Pair
Bus current (mA)640
Rail mountedYes
Width (mm)107
Device kindPowerSupply, Choke
RegistrationRegistered · 2026-11-27
Languagesde-DE, en-US, es-ES, fr-FR
Catalog entryM-0083_H-489-1_HP-0457-10-52A5_CI-STR.2D0640.2E02S-1
Fingerprint52A5
SHA-256f81682d008f0034cb9186cf02ec98f8bc3f13c882890ab922f59e88a9d0843be
First seen2026-11-27
Markets69 markets

Application program: Bus Power Supply 1.0

Application number$0457
Version1.0
Mask versionMV-07B0 (System B)
KNX Data SecureYes
Minimum ETS version5.0
Parameters215
Group objects65
Group objects (65)
NoNameFunctionSizeDPTFlags
0Device {{Dev_No}}: {{0}}Monitoring result1 Bit1.5 alarmCRT
0Device {{Dev_No}}: {{0}}Monitoring via group address1 Bit1.1 switchCWTU
0Device {{Dev_No}}: {{0}}Monitoring via group address1 Byte5.1 percentage (0..100%)CWTU
0Device {{Dev_No}}: {{0}}Monitoring via group address2 Bytes9.1 temperature (°C)CWTU
0Device {{Dev_No}}: {{0}}Monitoring via group address4 Bytes12.1 counter pulses (unsigned)CWTU
0Device {{Dev_No}}: {{0}}Monitoring via group address1 Bit1.1 switchCW
0Device {{Dev_No}}: {{0}}Monitoring via group address1 Byte5.1 percentage (0..100%)CW
0Device {{Dev_No}}: {{0}}Monitoring via group address2 Bytes9.1 temperature (°C)CW
0Device {{Dev_No}}: {{0}}Monitoring via group address4 Bytes12.1 counter pulses (unsigned)CW
1In operationSend status1 Bit1.11 stateCT
2Bus resetActivate1 Bit1.15 resetCW
3TimeReceive value3 Bytes10.1 time of dayCW
4DateReceive value3 Bytes11.1 dateCW
5Date and timeReceive values8 Bytes19.1 date timeCW
6Measured value: CurrentSend measured value2 Bytes7.12 current (mA)CRT
6Measured value: CurrentSend measured value2 Bytes9.21 current (mA)CRT
6Measured value: CurrentSend measured value4 Bytes14.19 electric current (A)CRT
7Measured value: VoltageSend measured value4 Bytes14.27 electric potential (V)CRT
7Measured value: VoltageSend measured value2 Bytes9.20 voltage (mV)CRT
8Bus trafficMonitoring1 Byte5.1 percentage (0..100%)CRT
9Current: OverloadAlarm message1 Bit1.5 alarmCRT
10Voltage: OverrunAlarm message1 Bit1.5 alarmCRT
11Low voltageAlarm message1 Bit1.5 alarmCRT
12Temperature monitoringAlarm when exceeded1 Bit1.5 alarmCRT
13Temperature monitoringWarning if exceeded1 Bit1.5 alarmCRT
14Bus traffic: ExceedanceAlarm message1 Bit1.5 alarmCRT
15Current monitoringMaximum value2 Bytes7.12 current (mA)CRT
15Current monitoringMaximum value2 Bytes9.21 current (mA)CRT
15Current monitoringMaximum value4 Bytes14.19 electric current (A)CRT
16Current monitoringMinimum value2 Bytes7.12 current (mA)CRT
16Current monitoringMinimum value2 Bytes9.21 current (mA)CRT
16Current monitoringMinimum value4 Bytes14.19 electric current (A)CRT
17Voltage monitoringMaximum value4 Bytes14.27 electric potential (V)CRT
17Voltage monitoringMaximum value2 Bytes9.20 voltage (mV)CRT
18Voltage monitoringMinimum value4 Bytes14.27 electric potential (V)CRT
18Voltage monitoringMinimum value2 Bytes9.20 voltage (mV)CRT
19Bus traffic monitoringMaximum value1 Byte5.1 percentage (0..100%)CRT
20Bus traffic monitoringMinimum value1 Byte5.1 percentage (0..100%)CRT
21All measured valuesStart request1 Bit1.10 start/stopCW
22All minimum/maximum valuesReset1 Bit1.15 resetCW
223Device group 1Monitoring result1 Bit1.5 alarmCRT
224Device group 2Monitoring result1 Bit1.5 alarmCRT
225Device group 3Monitoring result1 Bit1.5 alarmCRT
226Device group 4Monitoring result1 Bit1.5 alarmCRT
227Device group 5Monitoring result1 Bit1.5 alarmCRT
228Device group 1Switch1 Bit1.1 switchCT
229Device group 2Switch1 Bit1.1 switchCT
230Device group 3Switch1 Bit1.1 switchCT
231Device group 4Switch1 Bit1.1 switchCT
232Device group 5Switch1 Bit1.1 switchCT
233All devicesMonitoring result1 Bit1.5 alarmCRT
234Device monitoringLock1 Bit1.3 enableCW
235Device monitoringStatus1 Bit1.11 stateCRT
236Status outputStatus of last event14 Bytes16.1 Character String (ISO 8859-1)CRT
237Status outputStatus text for visualisation14 Bytes16.1 Character String (ISO 8859-1)CRT
238Navigation for visualisationScroll text messages1 Bit1.7 stepCW
239Navigation for visualisationConfirm selection1 Bit1.10 start/stopCW
240Event buffer for status outputReset1 Bit1.15 resetCW
241Operating hours meterMeter reading: Operating hours (h)2 Bytes7.7 time (h)CRT
242Operating hours meterOperating hours (h) since last restart2 Bytes7.7 time (h)CRT
243Operating hours meterReset operating hours1 Bit1.15 resetCW
244Operating hours meterMeter reading: Operating hours (s)4 Bytes13.100 time lag (s)CRT
245Operating hours meterOperating hours (s) since last restart4 Bytes13.100 time lag (s)CRT
246Status outputStatus: Power Supply 11 Bit1.11 stateCRT
247Status outputStatus: Power Supply 21 Bit1.11 stateCRT
Parameters (79)
ParameterTypeDefault
Startup timeunsignedInt 2…20010
"In operation" cycle timetime1800
Language selection for status outputlistGerman
Zeitumstellung Sommer/Winterlistactive
Operating hours meterlistactive
Datapoint typelistDPT 7.007 Value in h
Send cyclically every ... (0 = not active)unsignedInt 0…2550
Temperature warninglistnot active
Action on exceedinglistsend "1" to object
Action on falling below (normal operation)listsend "0" to object
Send cyclically every …listnot active
Temperature alarmlistnot active
Action on alarmlistnot active
Action on withdrawal of alarmlistnot active
Datapoint type: Bus current measurementlistDPT 7.012 Value in mA
Send measured value on change oflistnot active
Send value cyclically every ...listnot active
Overcurrentlistnot active
Action on not exceeding (normal operation)listsend "0" to object
Reaction ratelistmedium (5 s)
Send minimum/maximum valueslistnot active
Datapoint type: Bus voltage measurementlistDPT 9.020 Value in mV
Undervoltagelistnot active
Action on falling belowlistsend "1" to object
Action on not falling below (normal operation)listsend "0" to object
Threshold: Maximum bus trafficlistnot active
Reaction ratelisthigh (0 s)
Output via object "Status of last event"listsending the event once
Switching time between string sequencestime2
Number of repetitionslist2
Overtemperaturelistactive
Overcurrentlistactive
Undervoltagelistactive
Exceedence of bus trafficlistactive
Device monitoring of group 1listactive
Device monitoring of group 2listactive
Device monitoring of group 3listactive
Device monitoring of group 4listactive
Device monitoring of group 5listactive
Send status "Error/OK" of Power Supply 1listnot active
Send status "Error/OK" of Power Supply 2listnot active
Status of Power failurelistactive
Download ETS protocol / Restartlistactive
Send status of Power Supply 1 cyclicallylistnot active
Send status of Power Supply 2 cyclicallylistnot active
Status "Bus reset"listby pressing the Reset button and activating via object
Device monitoringlistactive
Send status aslistalarm (if available = "Off")
Duration of lock: Device monitoring on bus power returnlist10 min
Duration of lock: Device monitoring via lock objectlist10 min
Cyclical sending: Collective message "All devices"listnot active
Cyclical sending: Collective message "Group 1"listnot active
Cyclical sending: Collective message "Group 2"listnot active
Cyclical sending: Collective message "Group 3"listnot active
Cyclical sending: Collective message "Group 4"listnot active
Cyclical sending: Collective message "Group 5"listnot active
Objects for disconnecting from KNX devices (all groups)listnot active
Time of disconnection (OFF telegram)list5 s
Object "Bus Reset - Activate" withlistValue "1"
"Reset" button (on the device)listactive
Sending conditions: Minimum/Maximum valuesliston change and when resetting value (Cycle/Object)
Minimum/Maximum values: Cyclical resettime0
Device selectionlistPlease select a device
Lower limitunsignedInt 0…6553528000
Upper limitunsignedInt 20…9060
HysteresisunsignedInt 0…10010
Evaluation intervaltime1
Device monitoringlistnot active
Address selectionlistsame area and line as power supply
Arealist0
Linelist0
DeviceunsignedInt 0…2550
Monitoring intervallist30 s
Group assignmentlistnot active
Object lengthlist1 Bit
Expected object valuelistDevice valid with ON and OFF
Device / Object descriptiontext
Monitoring intervallist2 min
Monitoring intervallist20 min

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Bus Power Supply 1.0 latest$045752A52026-11-27148 KBDownload

About this file

This is the official ETS product database for the MDT technologies GmbH STR-640.02S KNX Redundant Bus power supply with diagnosis function, 640mA (STR-0640.02S), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.