STC-640.02S KNX Bus power supply with diagnosis function, 640mA Secure STC-0640.02S
MDT technologies GmbH · Order number STC-0640.02S · Power supply › KNX Bus power supply with diagnosis function
Download .knxprod Bus Power Supply 1.0 · 148 KB
Product
| Manufacturer | MDT technologies GmbH |
|---|---|
| Product name | STC-640.02S KNX Bus power supply with diagnosis function, 640mA Secure |
| Order number | STC-0640.02S |
| Hardware | Busspannungsversorgung mit Diagnosefunktion, 640mA |
| Medium | Twisted Pair |
| Bus current (mA) | 640 |
| Rail mounted | Yes |
| Width (mm) | 71 |
| Device kind | PowerSupply, Choke |
| Registration | Registered · 2026-11-27 |
| Languages | de-DE, en-US, es-ES, fr-FR |
| Catalog entry | M-0083_H-486-1_HP-0457-10-52A5_CI-STC.2D0640.2E02S-1 |
| Fingerprint | 52A5 |
| SHA-256 | 0eea3e15ee5a55f6a200e2d9165070e22c3d3f8c4b3fd3ff46bb223f28cbac35 |
| First seen | 2026-11-27 |
| Markets | 69 markets |
Application program: Bus Power Supply 1.0
| Application number | $0457 |
|---|---|
| Version | 1.0 |
| Mask version | MV-07B0 (System B) |
| KNX Data Secure | Yes |
| Minimum ETS version | 5.0 |
| Parameters | 215 |
| Group objects | 65 |
Group objects (65)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Device {{Dev_No}}: {{0}} | Monitoring result | 1 Bit | 1.5 alarm | CRT |
| 0 | Device {{Dev_No}}: {{0}} | Monitoring via group address | 1 Bit | 1.1 switch | CWTU |
| 0 | Device {{Dev_No}}: {{0}} | Monitoring via group address | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 0 | Device {{Dev_No}}: {{0}} | Monitoring via group address | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 0 | Device {{Dev_No}}: {{0}} | Monitoring via group address | 4 Bytes | 12.1 counter pulses (unsigned) | CWTU |
| 0 | Device {{Dev_No}}: {{0}} | Monitoring via group address | 1 Bit | 1.1 switch | CW |
| 0 | Device {{Dev_No}}: {{0}} | Monitoring via group address | 1 Byte | 5.1 percentage (0..100%) | CW |
| 0 | Device {{Dev_No}}: {{0}} | Monitoring via group address | 2 Bytes | 9.1 temperature (°C) | CW |
| 0 | Device {{Dev_No}}: {{0}} | Monitoring via group address | 4 Bytes | 12.1 counter pulses (unsigned) | CW |
| 1 | In operation | Send status | 1 Bit | 1.11 state | CT |
| 2 | Bus reset | Activate | 1 Bit | 1.15 reset | CW |
| 3 | Time | Receive value | 3 Bytes | 10.1 time of day | CW |
| 4 | Date | Receive value | 3 Bytes | 11.1 date | CW |
| 5 | Date and time | Receive values | 8 Bytes | 19.1 date time | CW |
| 6 | Measured value: Current | Send measured value | 2 Bytes | 7.12 current (mA) | CRT |
| 6 | Measured value: Current | Send measured value | 2 Bytes | 9.21 current (mA) | CRT |
| 6 | Measured value: Current | Send measured value | 4 Bytes | 14.19 electric current (A) | CRT |
| 7 | Measured value: Voltage | Send measured value | 4 Bytes | 14.27 electric potential (V) | CRT |
| 7 | Measured value: Voltage | Send measured value | 2 Bytes | 9.20 voltage (mV) | CRT |
| 8 | Bus traffic | Monitoring | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 9 | Current: Overload | Alarm message | 1 Bit | 1.5 alarm | CRT |
| 10 | Voltage: Overrun | Alarm message | 1 Bit | 1.5 alarm | CRT |
| 11 | Low voltage | Alarm message | 1 Bit | 1.5 alarm | CRT |
| 12 | Temperature monitoring | Alarm when exceeded | 1 Bit | 1.5 alarm | CRT |
| 13 | Temperature monitoring | Warning if exceeded | 1 Bit | 1.5 alarm | CRT |
| 14 | Bus traffic: Exceedance | Alarm message | 1 Bit | 1.5 alarm | CRT |
| 15 | Current monitoring | Maximum value | 2 Bytes | 7.12 current (mA) | CRT |
| 15 | Current monitoring | Maximum value | 2 Bytes | 9.21 current (mA) | CRT |
| 15 | Current monitoring | Maximum value | 4 Bytes | 14.19 electric current (A) | CRT |
| 16 | Current monitoring | Minimum value | 2 Bytes | 7.12 current (mA) | CRT |
| 16 | Current monitoring | Minimum value | 2 Bytes | 9.21 current (mA) | CRT |
| 16 | Current monitoring | Minimum value | 4 Bytes | 14.19 electric current (A) | CRT |
| 17 | Voltage monitoring | Maximum value | 4 Bytes | 14.27 electric potential (V) | CRT |
| 17 | Voltage monitoring | Maximum value | 2 Bytes | 9.20 voltage (mV) | CRT |
| 18 | Voltage monitoring | Minimum value | 4 Bytes | 14.27 electric potential (V) | CRT |
| 18 | Voltage monitoring | Minimum value | 2 Bytes | 9.20 voltage (mV) | CRT |
| 19 | Bus traffic monitoring | Maximum value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 20 | Bus traffic monitoring | Minimum value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 21 | All measured values | Start request | 1 Bit | 1.10 start/stop | CW |
| 22 | All minimum/maximum values | Reset | 1 Bit | 1.15 reset | CW |
| 223 | Device group 1 | Monitoring result | 1 Bit | 1.5 alarm | CRT |
| 224 | Device group 2 | Monitoring result | 1 Bit | 1.5 alarm | CRT |
| 225 | Device group 3 | Monitoring result | 1 Bit | 1.5 alarm | CRT |
| 226 | Device group 4 | Monitoring result | 1 Bit | 1.5 alarm | CRT |
| 227 | Device group 5 | Monitoring result | 1 Bit | 1.5 alarm | CRT |
| 228 | Device group 1 | Switch | 1 Bit | 1.1 switch | CT |
| 229 | Device group 2 | Switch | 1 Bit | 1.1 switch | CT |
| 230 | Device group 3 | Switch | 1 Bit | 1.1 switch | CT |
| 231 | Device group 4 | Switch | 1 Bit | 1.1 switch | CT |
| 232 | Device group 5 | Switch | 1 Bit | 1.1 switch | CT |
| 233 | All devices | Monitoring result | 1 Bit | 1.5 alarm | CRT |
| 234 | Device monitoring | Lock | 1 Bit | 1.3 enable | CW |
| 235 | Device monitoring | Status | 1 Bit | 1.11 state | CRT |
| 236 | Status output | Status of last event | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 237 | Status output | Status text for visualisation | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 238 | Navigation for visualisation | Scroll text messages | 1 Bit | 1.7 step | CW |
| 239 | Navigation for visualisation | Confirm selection | 1 Bit | 1.10 start/stop | CW |
| 240 | Event buffer for status output | Reset | 1 Bit | 1.15 reset | CW |
| 241 | Operating hours meter | Meter reading: Operating hours (h) | 2 Bytes | 7.7 time (h) | CRT |
| 242 | Operating hours meter | Operating hours (h) since last restart | 2 Bytes | 7.7 time (h) | CRT |
| 243 | Operating hours meter | Reset operating hours | 1 Bit | 1.15 reset | CW |
| 244 | Operating hours meter | Meter reading: Operating hours (s) | 4 Bytes | 13.100 time lag (s) | CRT |
| 245 | Operating hours meter | Operating hours (s) since last restart | 4 Bytes | 13.100 time lag (s) | CRT |
| 246 | Status output | Status: Power Supply 1 | 1 Bit | 1.11 state | CRT |
| 247 | Status output | Status: Power Supply 2 | 1 Bit | 1.11 state | CRT |
Parameters (79)
| Parameter | Type | Default |
|---|---|---|
| Startup time | unsignedInt 2…200 | 10 |
| "In operation" cycle time | time | 1800 |
| Language selection for status output | list | German |
| Zeitumstellung Sommer/Winter | list | active |
| Operating hours meter | list | active |
| Datapoint type | list | DPT 7.007 Value in h |
| Send cyclically every ... (0 = not active) | unsignedInt 0…255 | 0 |
| Temperature warning | list | not active |
| Action on exceeding | list | send "1" to object |
| Action on falling below (normal operation) | list | send "0" to object |
| Send cyclically every … | list | not active |
| Temperature alarm | list | not active |
| Action on alarm | list | not active |
| Action on withdrawal of alarm | list | not active |
| Datapoint type: Bus current measurement | list | DPT 7.012 Value in mA |
| Send measured value on change of | list | not active |
| Send value cyclically every ... | list | not active |
| Overcurrent | list | not active |
| Action on not exceeding (normal operation) | list | send "0" to object |
| Reaction rate | list | medium (5 s) |
| Send minimum/maximum values | list | not active |
| Datapoint type: Bus voltage measurement | list | DPT 9.020 Value in mV |
| Undervoltage | list | not active |
| Action on falling below | list | send "1" to object |
| Action on not falling below (normal operation) | list | send "0" to object |
| Threshold: Maximum bus traffic | list | not active |
| Reaction rate | list | high (0 s) |
| Output via object "Status of last event" | list | sending the event once |
| Switching time between string sequences | time | 2 |
| Number of repetitions | list | 2 |
| Overtemperature | list | active |
| Overcurrent | list | active |
| Undervoltage | list | active |
| Exceedence of bus traffic | list | active |
| Device monitoring of group 1 | list | active |
| Device monitoring of group 2 | list | active |
| Device monitoring of group 3 | list | active |
| Device monitoring of group 4 | list | active |
| Device monitoring of group 5 | list | active |
| Send status "Error/OK" of Power Supply 1 | list | not active |
| Send status "Error/OK" of Power Supply 2 | list | not active |
| Status of Power failure | list | active |
| Download ETS protocol / Restart | list | active |
| Send status of Power Supply 1 cyclically | list | not active |
| Send status of Power Supply 2 cyclically | list | not active |
| Status "Bus reset" | list | by pressing the Reset button and activating via object |
| Device monitoring | list | active |
| Send status as | list | alarm (if available = "Off") |
| Duration of lock: Device monitoring on bus power return | list | 10 min |
| Duration of lock: Device monitoring via lock object | list | 10 min |
| Cyclical sending: Collective message "All devices" | list | not active |
| Cyclical sending: Collective message "Group 1" | list | not active |
| Cyclical sending: Collective message "Group 2" | list | not active |
| Cyclical sending: Collective message "Group 3" | list | not active |
| Cyclical sending: Collective message "Group 4" | list | not active |
| Cyclical sending: Collective message "Group 5" | list | not active |
| Objects for disconnecting from KNX devices (all groups) | list | not active |
| Time of disconnection (OFF telegram) | list | 5 s |
| Object "Bus Reset - Activate" with | list | Value "1" |
| "Reset" button (on the device) | list | active |
| Sending conditions: Minimum/Maximum values | list | on change and when resetting value (Cycle/Object) |
| Minimum/Maximum values: Cyclical reset | time | 0 |
| Device selection | list | Please select a device |
| Lower limit | unsignedInt 0…65535 | 28000 |
| Upper limit | unsignedInt 20…90 | 60 |
| Hysteresis | unsignedInt 0…100 | 10 |
| Evaluation interval | time | 1 |
| Device monitoring | list | not active |
| Address selection | list | same area and line as power supply |
| Area | list | 0 |
| Line | list | 0 |
| Device | unsignedInt 0…255 | 0 |
| Monitoring interval | list | 30 s |
| Group assignment | list | not active |
| Object length | list | 1 Bit |
| Expected object value | list | Device valid with ON and OFF |
| Device / Object description | text | |
| Monitoring interval | list | 2 min |
| Monitoring interval | list | 20 min |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Bus Power Supply 1.0 latest | $0457 | 52A5 | 2026-11-27 | 148 KB | Download |
About this file
This is the official ETS product database for the MDT technologies GmbH STC-640.02S KNX Bus power supply with diagnosis function, 640mA Secure (STC-0640.02S), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from MDT technologies GmbH
- STC-0640.01 Bus power supply with diagnosis function, 640mA STC-0640.01
- STC-0960.01 Bus power supply with diagnosis function, 960mA STC-0960.01
- STC-0960.02S KNX Bus power supply with diagnosis function, 960mA Secure STC-0960.02S
- STC-1280.01 Bus power supply with diagnosis function, 1280mA STC-1280.01
- STR-0640.01 Redundant Bus power supply with diagnosis function, 640mA STR-0640.01
- STR-640.02S KNX Redundant Bus power supply with diagnosis function, 640mA STR-0640.02S
- STV-0160.02 KNX Bus Power Supply 160mA STV-0160.02
- STV-0320.02 KNX Bus Power Supply 320mA STV-0320.02
- STV-0640.02 KNX Bus Power Supply 640mA STV-0640.02
- Analog I/O 2fold, flush mounted AIO-0210V.01
- Analog I/O 4fold, MDRC AIO-0410V.01
- AKD-0103.01 Dimming actuator 1-f, 4TE, 230VAC,600W AKD-0103.01