KNX RF+Heating Valve Drive with display and Longlife-Batteries, Secure RF-HVA1DLB.01S
MDT technologies GmbH · Order number RF-HVA1DLB.01S · KNX RF+ Device › KNX RF+ Valve Drive
Download .knxprod RF+ Heating Valve Drive 1.1 · 123 KB
Product
| Manufacturer | MDT technologies GmbH |
|---|---|
| Product name | KNX RF+Heating Valve Drive with display and Longlife-Batteries, Secure |
| Order number | RF-HVA1DLB.01S |
| Product text | KNX RF+Heating Valve Drive with display and Longlife-Batterie, Secure |
| Hardware | KNX RF+ Stellantrieb |
| Medium | KNX RF |
| Rail mounted | No |
| Registration | Registered · 2025-12-15 |
| Languages | de-DE, en-US |
| Catalog entry | M-0083_H-265-1_HP-00F3-11-E0F2_CI-RF.2DHVA1DLB.2E01S-1 |
| Fingerprint | E0F2 |
| SHA-256 | 9e49fb25962c2e6763831b1bb7b5a4443937e68d5423d7cb579e3f647d31cac4 |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: RF+ Heating Valve Drive 1.1
| Application number | $00F3 |
|---|---|
| Version | 1.1 |
| Mask version | MV-27B0 (RF System B) |
| KNX Data Secure | Yes |
| Minimum ETS version | 5.0 |
| Parameters | 79 |
| Group objects | 13 |
Group objects (13)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | In operation | Output | 1 Bit | 1.1 switch | CT |
| 2 | Temperature controller | Send current setpoint | 2 Bytes | 9.1 temperature (°C) | CT |
| 2 | Temperature controller | Preset setpoint | 2 Bytes | 9.1 temperature (°C) | CT |
| 3 | Temperature controller | Preset setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 3 | Temperature controller | Receive current setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 4 | Temperature controller | Receive control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 5 | Temperature controller | Send valve position | 1 Byte | 5.1 percentage (0..100%) | CT |
| 6 | Temperature | Send measured value | 2 Bytes | 9.1 temperature (°C) | CT |
| 7 | Temperature | Receive measured value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 10 | Window contact | Input | 1 Bit | 1.19 window/door | CWTU |
| 11 | Battery | Status | 1 Byte | 5.1 percentage (0..100%) | CT |
| 12 | Battery | Warning | 1 Bit | 1.5 alarm | CT |
| 13 | Diagnosis | Diagnosis | 14 Bytes | 16.0 Character String (ASCII) | CT |
Parameters (59)
| Parameter | Type | Default |
|---|---|---|
| Cycle time: Low battery voltage | time | 720 |
| "Boost" - function | list | active |
| Send battery level cyclically | list | active |
| Send cyclically | list | active |
| Buttons on device | list | active |
| Display language | list | German |
| Room temperature controller | list | internal |
| Calibration value | list | 0 |
| Temperature sensor | list | internal |
| Temperature | list | 2.0 K per minute |
| Fallback to normal operation after ... | unsignedInt 1…30 | 10 |
| Send "In operation" cyclically | list | not active |
| Cycle time | time | 60 |
| Send temperature measurement value | list | not active |
| Request inverval setpoint | time | 15 |
| Cycle time | time | 5 |
| Request interval | time | 5 |
| Low battery voltage warning | list | not active |
| Diagnosis (up from SW V1.1.2) | list | not active |
| Send on change | list | not active |
| On change of | unsignedInt 1…50 | 10 |
| Send cyclically | list | not active |
| On change of | list | 0,5 K |
| Send valve position | list | not active |
| Threshold | unsignedInt 1…100 | 20 |
| Threshold | list | not active |
| Window contact | list | not active |
| Temperature | list | not active |
| Request interval | time | 15 |
| Value for open | list | Value = 1 |
| Lower when “Window open” | unsignedInt 3…25 | 10 |
| Ready to receive data after "In operation" | list | active |
| Device stays ready to receive data for | list | not active |
| Duration | time | 3 |
| Ready to receive data after keypress | list | not active |
| Ready to receive data after restart | list | active |
| Duration | time | 5 |
| Send battery warning cyclically | list | active |
| Cycle time: Battery level | time | 720 |
| Cycle time: Battery level / low battery voltage | time | 720 |
| Fallback to normal operation after ... | unsignedInt 1…1440 | 30 |
| HWT Check | list | RF-HVA1DAA.01 |
| Device | list | Select device |
| Request interval setpoint / control value | time | 15 |
| Rotate Display (up from SW V1.1.2) | list | no |
| Initial Setpoint Value (up from SW V1.1.2) | unsignedInt 3…40 | 7 |
| Proportional range | list | 4 K |
| Reset time | list | 120 min |
| Minimal control value | list | 0% |
| Maximum control value (up from SW V1.1.2) | list | 100% |
| offline_valve_position | list | 0% |
| "Boost" - Time (up from SW V1.1.2) | time | 5 |
| Fallback time | time | 30 |
| Heating System (up from SW V1.1.2) | list | Water Heating (4K / 120min) |
| Status display device | list | not active |
| Send internal temperature measurement value | list | not active |
| Fallback after manual switch-off via keypress (up from SW V1.1.2) | list | not active |
| LED Warning | list | not active |
| led_warning_min | list | not active |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| RF+ Heating Valve Drive 1.1 latest | $00F3 | E0F2 | 2026-11-25 | 123 KB | Download |
About this file
This is the official ETS product database for the MDT technologies GmbH KNX RF+Heating Valve Drive with display and Longlife-Batteries, Secure (RF-HVA1DLB.01S), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from MDT technologies GmbH
- RF-AKD230CC.02S KNX RF+ LED Controller CC/CV 30 W / 230 V 2-channel RF-AKD230CC.02S
- RF-AKD260CC.02S KNX RF+ LED Controller CC/CV 60 W / 230 V 2-channel RF-AKD260CC.02S
- KNX RF+ Socket 1-fold RF-AKK1ST.01
- KNX RF+ Switch Actuator 1-fold, UP RF-AKK1UP.01
- KNX RF+ Switch Actuator 2-fold, UP RF-AKK2UP.01
- KNX RF+ Socket with active power meter RF-AZK1ST.01
- RF-FGxS.01S KNX RF+ Window Handle, Secure RF-FGxS.01S
- RF-FKxx.01S KNX RF Window Contact RF-FKWS.01S
- KNX RF+ Glass Push Button 4-fold Plus RF-GTA4x.01
- KNX RF+ Glass Push Button 8-fold Plus RF-GTA8x.01
- KNX RF+ Glass Push Button 4-fold Plus, Temperature RF-GTT4x.01
- KNX RF+ Glass Push Button 8-fold Plus, Temperature RF-GTT8x.01