AZI-0616.03 Switch Actuator 6-channel with active power meter AZI-0616.03
MDT technologies GmbH · Order number AZI-0616.03 · Actuators › Actuators with active power meter
Download .knxprod Switch, Staircase light, Active power meter, 6-channel 3.1 · 232 KB
Product
| Manufacturer | MDT technologies GmbH |
|---|---|
| Product name | AZI-0616.03 Switch Actuator 6-channel with active power meter |
| Order number | AZI-0616.03 |
| Hardware | Schaltaktor 6-fach mit Wirkleistungszähler |
| Medium | Twisted Pair |
| Bus current (mA) | 10 |
| Rail mounted | Yes |
| Width (mm) | 144 |
| Registration | Registered · 2023-05-05 |
| Languages | de-DE, en-US, es-ES, fr-FR |
| Catalog entry | M-0083_H-228-1_HP-0211-31-2283_CI-AZI.2D0616.2E03-1 |
| Fingerprint | 2283 |
| SHA-256 | 61364556e78cdbb5708b6183eeb3ae75d32bcabd25e6b37aed73cdbf10eb1560 |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: Switch, Staircase light, Active power meter, 6-channel 3.1
| Application number | $0211 |
|---|---|
| Version | 3.1 |
| Mask version | MV-0705 (7.5) |
| KNX Data Secure | No |
| Minimum ETS version | 5.0 |
| Parameters | 801 |
| Group objects | 147 |
Group objects (147)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Channel {{ChNo}}: {{0}} | Switch | 1 Bit | 1.1 switch | CW |
| 1 | Channel {{ChNo}}: {{0}} | Service required | 1 Bit | 1.5 alarm | CRT |
| 1 | Channel {{ChNo}}: {{0}} | Staircase light | 1 Bit | 1.1 switch | CW |
| 1 | Channel A: {{0}} | Switch pulse | 1 Bit | 1.1 switch | CW |
| 1 | Channel B: {{0}} | Switch pulse | 1 Bit | 1.1 switch | CW |
| 1 | Channel C: {{0}} | Switch pulse | 1 Bit | 1.1 switch | CW |
| 1 | Channel D: {{0}} | Switch pulse | 1 Bit | 1.1 switch | CW |
| 1 | Channel E: {{0}} | Switch pulse | 1 Bit | 1.1 switch | CW |
| 1 | Channel F: {{0}} | Switch pulse | 1 Bit | 1.1 switch | CW |
| 2 | Channel {{ChNo}}: {{0}} | Meter reading: Operating hours | 4 Bytes | 13.100 time lag (s) | CRT |
| 2 | Channel {{ChNo}}: {{0}} | Meter reading: Operating hours | 2 Bytes | 7.7 time (h) | CRT |
| 2 | Channel {{ChNo}}: {{0}} | Time until next service | 4 Bytes | 13.100 time lag (s) | CRT |
| 2 | Channel {{ChNo}}: {{0}} | Time until next service | 2 Bytes | 7.7 time (h) | CRT |
| 2 | Channel {{ChNo}}: {{0}} | Staircase light with time | 1 Byte | 5.5 ratio (0..255) | CW |
| 3 | Channel {{ChNo}}: {{0}} | Reset: Operating hours | 1 Bit | 1.1 switch | CW |
| 3 | Channel {{ChNo}}: {{0}} | Reset: Service message | 1 Bit | 1.1 switch | CW |
| 3 | Channel {{ChNo}}: {{0}} | Prewarning | 1 Bit | 1.1 switch | CT |
| 4 | Channel {{ChNo}}: {{0}} | Lock | 1 Bit | 1.3 enable | CW |
| 4 | Channel A: {{0}} | Lock | 1 Bit | 1.3 enable | CW |
| 4 | Channel B: {{0}} | Lock | 1 Bit | 1.3 enable | CW |
| 4 | Channel C: {{0}} | Lock | 1 Bit | 1.3 enable | CW |
| 4 | Channel D: {{0}} | Lock | 1 Bit | 1.3 enable | CW |
| 4 | Channel E: {{0}} | Lock | 1 Bit | 1.3 enable | CW |
| 4 | Channel F: {{0}} | Lock | 1 Bit | 1.3 enable | CW |
| 5 | Channel {{ChNo}}: {{0}} | Forced guidance | 2 Bit | 2.1 switch control | CW |
| 5 | Channel {{ChNo}}: {{0}} | Priority | 1 Bit | 1.1 switch | CW |
| 6 | Channel {{ChNo}}: {{0}} | Scene | 1 Byte | 17.1 scene number | CW |
| 6 | Channel {{ChNo}}: {{0}} | Scene | 1 Byte | 18.1 scene control | CW |
| 7 | Channel {{ChNo}}: {{0}} | Status | 1 Bit | 1.11 state | CRT |
| 8 | Channel {{ChNo}}: {{0}} | Inverted status | 1 Bit | 1.11 state | CRT |
| 9 | Channel {{ChNo}}: {{0}} | Logic 1 | 1 Bit | 1.2 boolean | CW |
| 10 | Channel {{ChNo}}: {{0}} | Logic 2 | 1 Bit | 1.2 boolean | CW |
| 11 | Channel {{ChNo}}: {{0}} | Threshold switch | 1 Byte | 5.1 percentage (0..100%) | CW |
| 11 | Channel {{ChNo}}: {{0}} | Threshold switch | 1 Byte | 5.5 ratio (0..255) | CW |
| 11 | Channel {{ChNo}}: {{0}} | Threshold switch | 2 Bytes | 7.1 pulses | CW |
| 11 | Channel {{ChNo}}: {{0}} | Threshold switch | 2 Bytes | 9.1 temperature (°C) | CW |
| 11 | Channel {{ChNo}}: {{0}} | Threshold switch | 2 Bytes | 9.4 lux (Lux) | CW |
| 12 | Channel {{ChNo}}: {{0}} | Active power | 4 Bytes | 14.56 power (W) | CRT |
| 12 | Channel {{ChNo}}: {{0}} | Active power | 2 Bytes | 9.24 power (kW) | CRT |
| 13 | Channel {{ChNo}}: {{0}} | Current value | 2 Bytes | 7.12 current (mA) | CRT |
| 13 | Channel {{ChNo}}: {{0}} | Current value | 2 Bytes | 9.21 current (mA) | CRT |
| 13 | Channel {{ChNo}}: {{0}} | Current value | 4 Bytes | 14.19 electric current (A) | CRT |
| 14 | Channel {{ChNo}}: {{0}} | Voltage value | 4 Bytes | 14.27 electric potential (V) | CRT |
| 15 | Channel {{ChNo}}: {{0}} | Extended power measurement: Apparent power | 4 Bytes | 14.56 power (W) | CRT |
| 15 | Channel {{ChNo}}: {{0}} | Extended power measurement: Apparent power | 2 Bytes | 9.24 power (kW) | CRT |
| 15 | Channel {{ChNo}}: {{0}} | Extended power measurement: Reactive power | 4 Bytes | 14.56 power (W) | CRT |
| 15 | Channel {{ChNo}}: {{0}} | Extended power measurement: Reactive power | 2 Bytes | 9.24 power (kW) | CRT |
| 15 | Channel {{ChNo}}: {{0}} | Extended power measurement: Power factor cos Phi | 4 Bytes | 14.57 power factor (cos Φ) | CRT |
| 16 | Channel {{ChNo}}: {{0}} | Load exceedance | 1 Bit | 1.1 switch | CRT |
| 16 | Channel {{ChNo}}: {{0}} | Load exceedance | 1 Byte | 17.1 scene number | CRT |
| 17 | Channel {{ChNo}}: {{0}} | Load undercut | 1 Bit | 1.1 switch | CRT |
| 17 | Channel {{ChNo}}: {{0}} | Load undercut | 1 Byte | 17.1 scene number | CRT |
| 18 | Channel {{ChNo}}: {{0}} | Current exceedance | 1 Bit | 1.1 switch | CRT |
| 18 | Channel {{ChNo}}: {{0}} | Current exceedance | 1 Byte | 17.1 scene number | CRT |
| 19 | Channel {{ChNo}}: {{0}} | Current undercut | 1 Bit | 1.1 switch | CRT |
| 19 | Channel {{ChNo}}: {{0}} | Current undercut | 1 Byte | 17.1 scene number | CRT |
| 20 | Channel {{ChNo}}: {{0}} | Voltage exceedance | 1 Bit | 1.1 switch | CRT |
| 20 | Channel {{ChNo}}: {{0}} | Voltage exceedance | 1 Byte | 17.1 scene number | CRT |
| 21 | Channel {{ChNo}}: {{0}} | Voltage undercut | 1 Bit | 1.1 switch | CRT |
| 21 | Channel {{ChNo}}: {{0}} | Voltage undercut | 1 Byte | 17.1 scene number | CRT |
| 22 | Channel {{ChNo}}: {{0}} | Intermediate meter: Electrical active energy (24 h) | 4 Bytes | 13.10 active energy (Wh) | CRWT |
| 22 | Channel {{ChNo}}: {{0}} | Intermediate meter: Electrical active energy (24 h) | 4 Bytes | 13.13 active energy (kWh) | CRWT |
| 23 | Channel {{ChNo}}: {{0}} | Intermediate meter: Costs in Cent - Output | 4 Bytes | CRT | |
| 23 | Channel {{ChNo}}: {{0}} | Intermediate meter: Costs in Cent - Output | 2 Bytes | CRT | |
| 23 | Channel {{ChNo}}: {{0}} | Intermediate meter: Costs in Euro - Output | 4 Bytes | CRT | |
| 23 | Channel {{ChNo}}: {{0}} | Intermediate meter: Costs in Euro - Output | 2 Bytes | CRT | |
| 24 | Channel {{ChNo}}: {{0}} | Intermediate meter: Meter reading "Day" | 4 Bytes | 13.10 active energy (Wh) | CRWT |
| 24 | Channel {{ChNo}}: {{0}} | Intermediate meter: Meter reading "Day" | 4 Bytes | 13.13 active energy (kWh) | CRWT |
| 25 | Channel {{ChNo}}: {{0}} | Intermediate meter: Meter reading "Night" | 4 Bytes | 13.10 active energy (Wh) | CRWT |
| 25 | Channel {{ChNo}}: {{0}} | Intermediate meter: Meter reading "Night" | 4 Bytes | 13.13 active energy (kWh) | CRWT |
| 26 | Channel {{ChNo}}: {{0}} | Intermediate meter: Reset | 1 Bit | 1.3 enable | CW |
| 27 | Channel {{ChNo}}: {{0}} | Main meter: Electrical active energy (24 h) | 4 Bytes | 13.13 active energy (kWh) | CRWT |
| 27 | Channel {{ChNo}}: {{0}} | Main meter: Electrical active energy (24 h) | 4 Bytes | 13.10 active energy (Wh) | CRWT |
| 28 | Channel {{ChNo}}: {{0}} | Main meter: Costs in Cent - Output | 4 Bytes | CRT | |
| 28 | Channel {{ChNo}}: {{0}} | Main meter: Costs in Cent - Output | 2 Bytes | CRT | |
| 28 | Channel {{ChNo}}: {{0}} | Main meter: Costs in Euro - Output | 4 Bytes | CRT | |
| 28 | Channel {{ChNo}}: {{0}} | Main meter: Costs in Euro - Output | 2 Bytes | CRT | |
| 29 | Channel {{ChNo}}: {{0}} | Main meter: Meter reading "Day" | 4 Bytes | 13.13 active energy (kWh) | CRWT |
| 29 | Channel {{ChNo}}: {{0}} | Main meter: Meter reading "Day" | 4 Bytes | 13.10 active energy (Wh) | CRWT |
| 30 | Channel {{ChNo}}: {{0}} | Main meter: Meter reading "Night" | 4 Bytes | 13.13 active energy (kWh) | CRWT |
| 30 | Channel {{ChNo}}: {{0}} | Main meter: Meter reading "Night" | 4 Bytes | 13.10 active energy (Wh) | CRWT |
| 31 | Channel {{ChNo}}: {{0}} | Main meter: Reset | 1 Bit | 1.3 enable | CW |
| 32 | Channel {{ChNo}}: {{0}} | Meter: Event A | 1 Bit | 1.10 start/stop | CT |
| 33 | Channel {{ChNo}}: {{0}} | Meter: Event B | 1 Bit | 1.10 start/stop | CT |
| 34 | Channel {{ChNo}}: {{0}} | Load failure | 1 Bit | 1.5 alarm | CRT |
| 34 | Channel {{ChNo}}: {{0}} | Residual current | 1 Bit | 1.5 alarm | CRT |
| 34 | Channel {{ChNo}}: {{0}} | Residual current / Load failure | 1 Bit | 1.5 alarm | CRT |
| 210 | Central function | Switch | 1 Bit | 1.1 switch | CW |
| 211 | Central function | Lock manual operation | 1 Bit | 1.3 enable | CW |
| 212 | Central function | In operation | 1 Bit | 1.11 state | CRT |
| 213 | Central function | Day/Night | 1 Bit | 1.2 boolean | CWTU |
| 214 | Central function | Time | 3 Bytes | 10.1 time of day | CWTU |
| 215 | Total: Active power | Total value | 4 Bytes | 14.56 power (W) | CRT |
| 215 | Total: Active power | Total value | 2 Bytes | 9.24 power (kW) | CRT |
| 216 | Total current | Current value | 2 Bytes | 9.21 current (mA) | CRT |
| 216 | Total current | Current value | 4 Bytes | 14.19 electric current (A) | CRT |
| 216 | Total current | Current value | 2 Bytes | 7.12 current (mA) | CRT |
| 217 | Total: Extended power measurement | Apparent power | 4 Bytes | 14.56 power (W) | CRT |
| 217 | Total: Extended power measurement | Apparent power | 2 Bytes | 9.24 power (kW) | CRT |
| 217 | Total: Extended power measurement | Apparent power | 4 Bytes | 14.57 power factor (cos Φ) | CRT |
| 218 | Total: Active power | Load exceedance | 1 Bit | 1.1 switch | CRT |
| 218 | Total: Active power | Load exceedance | 1 Byte | 17.1 scene number | CRT |
| 219 | Total: Active power | Load undercut | 1 Bit | 1.1 switch | CRT |
| 219 | Total: Active power | Load undercut | 1 Byte | 17.1 scene number | CRT |
| 220 | Total current | Current exceedance | 1 Bit | 1.1 switch | CRT |
| 220 | Total current | Current exceedance | 1 Byte | 17.1 scene number | CRT |
| 221 | Total current | Current undercut | 1 Bit | 1.1 switch | CRT |
| 221 | Total current | Current undercut | 1 Byte | 17.1 scene number | CRT |
| 222 | Total: Intermediate meter | Electrical active energy (24 h) | 4 Bytes | 13.10 active energy (Wh) | CRT |
| 222 | Total: Intermediate meter | Electrical active energy (24 h) | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 223 | Total: Intermediate meter | Costs in Cent - Output | 4 Bytes | CRT | |
| 223 | Total: Intermediate meter | Costs in Cent - Output | 2 Bytes | CRT | |
| 223 | Total: Intermediate meter | Costs in Euro - Output | 4 Bytes | CRT | |
| 223 | Total: Intermediate meter | Costs in Euro - Output | 2 Bytes | CRT | |
| 224 | Total: Intermediate meter | Meter reading: "Day" | 4 Bytes | 13.10 active energy (Wh) | CRT |
| 224 | Total: Intermediate meter | Meter reading: "Day" | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 225 | Total: Intermediate meter | Meter reading: "Night" | 4 Bytes | 13.10 active energy (Wh) | CRT |
| 225 | Total: Intermediate meter | Meter reading: "Night" | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 226 | Total: Intermediate meter | Reset | 1 Bit | 1.3 enable | CW |
| 227 | Total: Main meter | Electrical active energy (24 h) | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 227 | Total: Main meter | Electrical active energy (24 h) | 4 Bytes | 13.10 active energy (Wh) | CRT |
| 228 | Total: Main meter | Costs in Cent - Output | 4 Bytes | CRT | |
| 228 | Total: Main meter | Costs in Cent - Output | 2 Bytes | CRT | |
| 228 | Total: Main meter | Costs in Euro - Output | 4 Bytes | CRT | |
| 228 | Total: Main meter | Costs in Euro - Output | 2 Bytes | CRT | |
| 229 | Total: Main meter | Meter reading: "Day" | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 229 | Total: Main meter | Meter reading: "Day" | 4 Bytes | 13.10 active energy (Wh) | CRT |
| 230 | Total: Main meter | Meter reading: "Night" | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 230 | Total: Main meter | Meter reading: "Night" | 4 Bytes | 13.10 active energy (Wh) | CRT |
| 231 | Total: Main meter | Reset | 1 Bit | 1.3 enable | CW |
| 232 | Total: Meter | Event A | 1 Bit | 1.10 start/stop | CT |
| 233 | Total: Meter | Event B | 1 Bit | 1.10 start/stop | CT |
| 234 | Electricity price: "Day" | Electricity rate in Cent - Input | 4 Bytes | CW | |
| 234 | Electricity price: "Day" | Electricity rate in Cent - Input | 2 Bytes | CW | |
| 234 | Electricity price: "Day" | Electricity rate in Euro - Input | 4 Bytes | CW | |
| 234 | Electricity price: "Day" | Electricity rate in Euro - Input | 2 Bytes | CW | |
| 235 | Electricity price: "Night" | Electricity rate in Cent - Input | 4 Bytes | CW | |
| 235 | Electricity price: "Night" | Electricity rate in Cent - Input | 2 Bytes | CW | |
| 235 | Electricity price: "Night" | Electricity rate in Euro - Input | 4 Bytes | CW | |
| 235 | Electricity price: "Night" | Electricity rate in Euro - Input | 2 Bytes | CW | |
| 236 | Actual electricity price | Electricity rate in Cent - Output | 4 Bytes | CRT | |
| 236 | Actual electricity price | Electricity rate in Cent - Output | 2 Bytes | CRT | |
| 236 | Actual electricity price | Electricity rate in Euro - Output | 4 Bytes | CRT | |
| 236 | Actual electricity price | Electricity rate in Euro - Output | 2 Bytes | CRT | |
| 237 | Central function | Voltage error | 1 Bit | 1.5 alarm | CRT |
| 238 | Total: Active power | External - Input | 4 Bytes | 14.56 power (W) | CW |
| 238 | Total: Active power | External - Input | 2 Bytes | 9.24 power (kW) | CW |
Parameters (209)
| Parameter | Type | Default |
|---|---|---|
| Startup time | unsignedInt 2…240 | 2 |
| Channel A | list | Switch |
| Economy mode, switch off LEDs after | list | not active |
| Send "In operation" cyclically | list | not active |
| Manual operation | list | active |
| Channel B | list | Switch |
| Channel C | list | Switch |
| Channel D | list | Switch |
| Set energy meters to "0" after transmitting the application. | list | not active |
| Total current measurement | list | not active |
| All energy meters in the channel are writable via object | list | not active |
| Object selection | list | 2 Byte value in mA (DPT 7.012) |
| Send value on change of ... | list | no change |
| Send cyclically every … | list | 1 h |
| Monitoring of current exceedance | list | not active |
| Send output cyclically | list | not active |
| Minimum change | list | not active |
| Send value if exceeded | list | value "1" |
| Send scene if exceeded | list | 1 |
| Send value on withdrawal | list | value "0" |
| Send scene on withdrawal | list | 2 |
| Value for exceedance | float 1…70 | 20 |
| Value range | list | 100 mA - 1000 mA |
| Value for exceedance | unsignedInt 100…1000 | 1000 |
| Value range for withdrawal | list | 100 mA - 1000 mA |
| Value for withdrawal | unsignedInt 100…1000 | 100 |
| Value for withdrawal | float 1…70 | 10 |
| Channel E | list | Switch |
| Channel F | list | Switch |
| Total: Active power measurement | list | active |
| Object selection | list | 4 Byte floating value in W (DPT 14.056) |
| Send value on change of ... | list | not active |
| Monitoring of load exceedance | list | not active |
| Value for exceedance | unsignedInt 0…27600 | 100 |
| Delay time | time | 0 |
| Monitoring of load undercut | list | not active |
| Value for undercut | unsignedInt 0…27600 | 5 |
| Object selection | list | Apparent power in VA (DPT 14.056) |
| Send cyclically every … | list | not active |
| Calculate costs via | list | a fixed value (Day) |
| Electricity rate "Day" | float 0…10 | 0.22 |
| DPT for object "Actual Electricity Price" | list | 4 Byte floating value [Cent] |
| Electricity rate "Night" | float 0…10 | 0.18 |
| "Day" <-> "Night" change is controlled via | list | "Day/Night" object (Day = 1, Night = 0) |
| Time to switch from "Day" to "Night" | unsignedInt 0…23 | 0 |
| Time to switch from "Day" to "Night" | unsignedInt 0…59 | 0 |
| Time to switch from "Night" to "Day" | unsignedInt 0…23 | 0 |
| Time to switch from "Night" to "Day" | unsignedInt 0…59 | 0 |
| DPT for objects "Electricity price Day" and "Actual electricity price" | list | 4 Byte floating value [Cent] |
| DPT for objects "Electricity price Day/Night" and "Actual electricity price" | list | 4 Byte floating value [Cent] |
| DPT for costs at intermediate and main meter | list | 4 Byte floating value [Cent] |
| Meter | list | not active |
| Object selection | list | Value in Wh (DPT 13.010) |
| Send meter reading on change | list | not active |
| Send meter reading every ... | unsignedInt 10…50000 | 10 |
| Send meter reading cyclically every … | list | 1 h |
| Send meter reading every ... | unsignedInt 1…255 | 10 |
| Send meter reading cyclically every ... | list | 1 h |
| Send meter reading every ... | unsignedInt 1…65535 | 10 |
| Send meter reading every ... | unsignedInt 1…255 | 100 |
| Activate "Event A" with | list | not active |
| Final value | unsignedInt 1…4294967295 | 200 |
| Object "Event A" sends | list | OFF |
| Intermediate meter: Send all values | list | not active |
| Intermediate meter: Reset | list | not active |
| Main meter: Send all values | list | not active |
| Main meter: Reset | list | not active |
| Intermediate meter: Send costs | list | not active |
| Main meter: Send costs | list | not active |
| Hours | unsignedInt 0…23 | 0 |
| Minutes | unsignedInt 0…59 | 0 |
| Day | list | every day |
| Activate "Event B" with | list | not active |
| Object "Event B" sends | list | OFF |
| Switch off all channels | list | not active |
| Monitoring of current undercut | list | not active |
| Value for undercut | unsignedInt 100…1000 | 100 |
| Value for undercut | float 1…70 | 10 |
| Send value if undercut | list | value "1" |
| Value for withdrawal | unsignedInt 100…1000 | 1000 |
| Value for withdrawal | float 1…70 | 20 |
| Send scene if undercut | list | 1 |
| Value for withdrawal | unsignedInt 0…27600 | 100 |
| Type of delay | list | Delay after activation |
| Value for withdrawal | unsignedInt 0…27600 | 5 |
| Description of channel/objects | text | |
| Additional text | text | |
| Separate "Day/Night" meters | list | not active |
| Cost meter | list | not active |
| Intermediate meter | list | not active |
| Object "Day/Night" | list | no request |
| Object "Time" | list | no request |
| Object selection (from HW R4.2) | list | Value in Wh (DPT 13.010) |
| Mode | list | normally open |
| Switch-on delay | unsignedInt 0…30000 | 0 |
| Switch-off delay | unsignedInt 0…30000 | 0 |
| Central function | list | active |
| Send status | list | on change |
| Send status cyclically (0 = not active) | unsignedInt 0…30000 | 0 |
| Additional inverted status | list | not active |
| Behaviour on locking | list | no change |
| Behaviour on unlocking | list | no change |
| Priority / Forced guidance | list | not active |
| Fallback time for forced guidance ( 0 = not active) | unsignedInt 0…600 | 0 |
| Behaviour after forced guidance | list | no change |
| Fallback time for priority (0 = not active) | unsignedInt 0…600 | 0 |
| Behavior after deactivation of priority | list | no change |
| Behaviour on bus power return | list | no change |
| Behaviour on bus power failure | list | no change |
| Logic | list | not active |
| Scenes | list | not active |
| Threshold switch | list | not active |
| Operating hours meter | list | not active |
| Logical operation | list | OR |
| Logic function | list | with switch object and one logic object |
| Invert inputs | list | not active |
| Invert output | list | not active |
| Set objects to value after bus power return | list | not active |
| Value for object "Switch" | list | not active |
| Value for object "Logic 1" | list | not active |
| Value for object "Logic 2" | list | not active |
| Learn scene | list | not active |
| Scene A | list | not active |
| Scene number | list | 1 |
| Scene behaviour | list | ON |
| Scene B | list | not active |
| Scene number | list | 2 |
| Scene C | list | not active |
| Scene number | list | 3 |
| Scene D | list | not active |
| Scene number | list | 4 |
| Scene E | list | not active |
| Scene number | list | 5 |
| Scene F | list | not active |
| Scene number | list | 6 |
| Scene G | list | not active |
| Scene number | list | 7 |
| Scene H | list | not active |
| Scene number | list | 8 |
| Datapoint type | list | 1 Byte DPT 5.001 Percent (0…100 %) |
| Behaviour when undercut | list | not active |
| Lower threshold | list | 0 % |
| Behaviour when exceeded | list | not active |
| Upper threshold | list | 90 % |
| Set value | list | 50 % |
| Lower threshold | unsignedInt 0…255 | 0 |
| Upper threshold | unsignedInt 0…255 | 0 |
| Set value | unsignedInt 1…255 | 10 |
| Lower threshold | unsignedInt 0…65500 | 0 |
| Upper threshold | unsignedInt 0…65500 | 0 |
| Set value | unsignedInt 1…65500 | 100 |
| Lower threshold | float -100…200 | 10 |
| Upper threshold | float -100…200 | 30 |
| Set value | float -100…200 | 20 |
| Lower threshold | float 0…100000 | 100 |
| Upper threshold | float 0…100000 | 60000 |
| Set value | float 0…100000 | 400 |
| Type of meter | list | Operating hours meter |
| Datapoint type | list | 4 Byte value in s (DPT 13.100) |
| Send operating hours every ... (0 = not active) | unsignedInt 0…10000 | 0 |
| Send operating hours cyclically every … | list | not active |
| Send "Time until next service" every ... (0 = not active) | unsignedInt 0…10000 | 0 |
| Send service message at intervals of ... | unsignedInt 0…60000 | 0 |
| Add channel to overall evaluation (current, active power, energy meter and voltage error) | list | active |
| Send value on change of ... | list | 10 % |
| Value range | list | 10 mA - 1000 mA |
| Value for exceedance | unsignedInt 10…1000 | 10 |
| Error message | list | not active |
| Threshold | list | 20 mA |
| Current measurement | list | active |
| Value for exceedance | float 1…20 | 1 |
| Value range for withdrawal | list | 10 mA - 1000 mA |
| Value for withdrawal | unsignedInt 10…1000 | 10 |
| Value for withdrawal | float 1…20 | 1 |
| Value for undercut | unsignedInt 10…1000 | 10 |
| Value for undercut | float 1…20 | 1 |
| Active power measurement | list | active |
| Value for exceedance | unsignedInt 0…4600 | 100 |
| Value for undercut | unsignedInt 1…4600 | 5 |
| Extended power measurement | list | not active |
| Voltage measurement | list | active |
| Monitoring of voltage exceedance | list | not active |
| Value for exceedance | unsignedInt 180…300 | 260 |
| Monitoring of voltage undercut | list | not active |
| Value for undercut | unsignedInt 180…300 | 210 |
| Energy and cost meter | list | not active |
| Send meter reading cyclically every ... | list | not active |
| Send meter reading every ... | unsignedInt 1…65535 | 1 |
| Send meter reading cyclically every ... | list | 5 min |
| Switch off channel | list | not active |
| Value for withdrawal | unsignedInt 180…300 | 240 |
| Value for withdrawal | unsignedInt 180…300 | 230 |
| Value for withdrawal | unsignedInt 0…4600 | 100 |
| Object selection (from HW R4.2) | list | Value in kWh (DPT 13.013) |
| Additional switch object | list | not active |
| Staircase light timer | unsignedInt 1…30000 | 1 |
| Prewarning | list | not active |
| Prewarning duration | unsignedInt 0…30000 | 1 |
| Prewarning time | unsignedInt 0…30000 | 0 |
| Manual switch-off | list | active |
| Extend staircase light timer | list | restart time |
| Factor for object "Staircase light with time" | list | 1 s |
| Behaviour on unlocking | list | OFF |
| Behaviour after forced guidance | list | OFF |
| Behavior after deactivation of priority | list | OFF |
| Behaviour on bus power return | list | state before bus power failure |
| Pulse time | list | 500 ms |
| Repeat pulse once | list | not active |
| Time until the next pulse | list | 0,5 s |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Switch, Staircase light, Active power meter, 6-channel 3.1 latest | $0211 | 2283 | 2026-11-25 | 232 KB | Download |
About this file
This is the official ETS product database for the MDT technologies GmbH AZI-0616.03 Switch Actuator 6-channel with active power meter (AZI-0616.03), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from MDT technologies GmbH
- Analog I/O 2fold, flush mounted AIO-0210V.01
- Analog I/O 4fold, MDRC AIO-0410V.01
- AKD-0103.01 Dimming actuator 1-f, 4TE, 230VAC,600W AKD-0103.01
- AKD-0201.01 Dimming actuator 2-f, 4TE, 230VAC,250W AKD-0201.01
- AKD-0201.02 Dimming Actuator 2-fold AKD-0201.02
- AKD-0203.01 Dimming actuator 2-f, 8TE, 230VAC,600W AKD-0203.01
- AKD-0224V.02 LED Controler 2 Ch AKD-0224V.02
- AKD-0230CC.02 LED Controller CC/CV 30 W / 230 V 2-channel AKD-0230CC.02
- AKD-0260CC.02 LED Controller CC/CV 60 W / 230 V 2-channel AKD-0260CC.02
- AKD-0324V.02 LED Controler 3 Ch/RGB AKD-0324V.02
- AKD-0401.01 Dimming actuator 4-f, 8TE, 230VAC,250W AKD-0401.01
- AKD-0401.02 Dimming Actuator 4-fold AKD-0401.02