KNX Database
MDT technologies GmbH AZI-0616.03 AZI-0616.03 Switch Actuator 6-channel with active power meter

AZI-0616.03 Switch Actuator 6-channel with active power meter AZI-0616.03

MDT technologies GmbH · Order number AZI-0616.03 · Actuators › Actuators with active power meter

Download .knxprod Switch, Staircase light, Active power meter, 6-channel 3.1 · 232 KB

Product

ManufacturerMDT technologies GmbH
Product nameAZI-0616.03 Switch Actuator 6-channel with active power meter
Order numberAZI-0616.03
HardwareSchaltaktor 6-fach mit Wirkleistungszähler
MediumTwisted Pair
Bus current (mA)10
Rail mountedYes
Width (mm)144
RegistrationRegistered · 2023-05-05
Languagesde-DE, en-US, es-ES, fr-FR
Catalog entryM-0083_H-228-1_HP-0211-31-2283_CI-AZI.2D0616.2E03-1
Fingerprint2283
SHA-25661364556e78cdbb5708b6183eeb3ae75d32bcabd25e6b37aed73cdbf10eb1560
First seen2026-11-25
Markets69 markets

Application program: Switch, Staircase light, Active power meter, 6-channel 3.1

Application number$0211
Version3.1
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version5.0
Parameters801
Group objects147
Group objects (147)
NoNameFunctionSizeDPTFlags
0Channel {{ChNo}}: {{0}}Switch1 Bit1.1 switchCW
1Channel {{ChNo}}: {{0}}Service required1 Bit1.5 alarmCRT
1Channel {{ChNo}}: {{0}}Staircase light1 Bit1.1 switchCW
1Channel A: {{0}}Switch pulse1 Bit1.1 switchCW
1Channel B: {{0}}Switch pulse1 Bit1.1 switchCW
1Channel C: {{0}}Switch pulse1 Bit1.1 switchCW
1Channel D: {{0}}Switch pulse1 Bit1.1 switchCW
1Channel E: {{0}}Switch pulse1 Bit1.1 switchCW
1Channel F: {{0}}Switch pulse1 Bit1.1 switchCW
2Channel {{ChNo}}: {{0}}Meter reading: Operating hours4 Bytes13.100 time lag (s)CRT
2Channel {{ChNo}}: {{0}}Meter reading: Operating hours2 Bytes7.7 time (h)CRT
2Channel {{ChNo}}: {{0}}Time until next service4 Bytes13.100 time lag (s)CRT
2Channel {{ChNo}}: {{0}}Time until next service2 Bytes7.7 time (h)CRT
2Channel {{ChNo}}: {{0}}Staircase light with time1 Byte5.5 ratio (0..255)CW
3Channel {{ChNo}}: {{0}}Reset: Operating hours1 Bit1.1 switchCW
3Channel {{ChNo}}: {{0}}Reset: Service message1 Bit1.1 switchCW
3Channel {{ChNo}}: {{0}}Prewarning1 Bit1.1 switchCT
4Channel {{ChNo}}: {{0}}Lock1 Bit1.3 enableCW
4Channel A: {{0}}Lock1 Bit1.3 enableCW
4Channel B: {{0}}Lock1 Bit1.3 enableCW
4Channel C: {{0}}Lock1 Bit1.3 enableCW
4Channel D: {{0}}Lock1 Bit1.3 enableCW
4Channel E: {{0}}Lock1 Bit1.3 enableCW
4Channel F: {{0}}Lock1 Bit1.3 enableCW
5Channel {{ChNo}}: {{0}}Forced guidance2 Bit2.1 switch controlCW
5Channel {{ChNo}}: {{0}}Priority1 Bit1.1 switchCW
6Channel {{ChNo}}: {{0}}Scene1 Byte17.1 scene numberCW
6Channel {{ChNo}}: {{0}}Scene1 Byte18.1 scene controlCW
7Channel {{ChNo}}: {{0}}Status1 Bit1.11 stateCRT
8Channel {{ChNo}}: {{0}}Inverted status1 Bit1.11 stateCRT
9Channel {{ChNo}}: {{0}}Logic 11 Bit1.2 booleanCW
10Channel {{ChNo}}: {{0}}Logic 21 Bit1.2 booleanCW
11Channel {{ChNo}}: {{0}}Threshold switch1 Byte5.1 percentage (0..100%)CW
11Channel {{ChNo}}: {{0}}Threshold switch1 Byte5.5 ratio (0..255)CW
11Channel {{ChNo}}: {{0}}Threshold switch2 Bytes7.1 pulsesCW
11Channel {{ChNo}}: {{0}}Threshold switch2 Bytes9.1 temperature (°C)CW
11Channel {{ChNo}}: {{0}}Threshold switch2 Bytes9.4 lux (Lux)CW
12Channel {{ChNo}}: {{0}}Active power4 Bytes14.56 power (W)CRT
12Channel {{ChNo}}: {{0}}Active power2 Bytes9.24 power (kW)CRT
13Channel {{ChNo}}: {{0}}Current value2 Bytes7.12 current (mA)CRT
13Channel {{ChNo}}: {{0}}Current value2 Bytes9.21 current (mA)CRT
13Channel {{ChNo}}: {{0}}Current value4 Bytes14.19 electric current (A)CRT
14Channel {{ChNo}}: {{0}}Voltage value4 Bytes14.27 electric potential (V)CRT
15Channel {{ChNo}}: {{0}}Extended power measurement: Apparent power4 Bytes14.56 power (W)CRT
15Channel {{ChNo}}: {{0}}Extended power measurement: Apparent power2 Bytes9.24 power (kW)CRT
15Channel {{ChNo}}: {{0}}Extended power measurement: Reactive power4 Bytes14.56 power (W)CRT
15Channel {{ChNo}}: {{0}}Extended power measurement: Reactive power2 Bytes9.24 power (kW)CRT
15Channel {{ChNo}}: {{0}}Extended power measurement: Power factor cos Phi4 Bytes14.57 power factor (cos Φ)CRT
16Channel {{ChNo}}: {{0}}Load exceedance1 Bit1.1 switchCRT
16Channel {{ChNo}}: {{0}}Load exceedance1 Byte17.1 scene numberCRT
17Channel {{ChNo}}: {{0}}Load undercut1 Bit1.1 switchCRT
17Channel {{ChNo}}: {{0}}Load undercut1 Byte17.1 scene numberCRT
18Channel {{ChNo}}: {{0}}Current exceedance1 Bit1.1 switchCRT
18Channel {{ChNo}}: {{0}}Current exceedance1 Byte17.1 scene numberCRT
19Channel {{ChNo}}: {{0}}Current undercut1 Bit1.1 switchCRT
19Channel {{ChNo}}: {{0}}Current undercut1 Byte17.1 scene numberCRT
20Channel {{ChNo}}: {{0}}Voltage exceedance1 Bit1.1 switchCRT
20Channel {{ChNo}}: {{0}}Voltage exceedance1 Byte17.1 scene numberCRT
21Channel {{ChNo}}: {{0}}Voltage undercut1 Bit1.1 switchCRT
21Channel {{ChNo}}: {{0}}Voltage undercut1 Byte17.1 scene numberCRT
22Channel {{ChNo}}: {{0}}Intermediate meter: Electrical active energy (24 h)4 Bytes13.10 active energy (Wh)CRWT
22Channel {{ChNo}}: {{0}}Intermediate meter: Electrical active energy (24 h)4 Bytes13.13 active energy (kWh)CRWT
23Channel {{ChNo}}: {{0}}Intermediate meter: Costs in Cent - Output4 BytesCRT
23Channel {{ChNo}}: {{0}}Intermediate meter: Costs in Cent - Output2 BytesCRT
23Channel {{ChNo}}: {{0}}Intermediate meter: Costs in Euro - Output4 BytesCRT
23Channel {{ChNo}}: {{0}}Intermediate meter: Costs in Euro - Output2 BytesCRT
24Channel {{ChNo}}: {{0}}Intermediate meter: Meter reading "Day"4 Bytes13.10 active energy (Wh)CRWT
24Channel {{ChNo}}: {{0}}Intermediate meter: Meter reading "Day"4 Bytes13.13 active energy (kWh)CRWT
25Channel {{ChNo}}: {{0}}Intermediate meter: Meter reading "Night"4 Bytes13.10 active energy (Wh)CRWT
25Channel {{ChNo}}: {{0}}Intermediate meter: Meter reading "Night"4 Bytes13.13 active energy (kWh)CRWT
26Channel {{ChNo}}: {{0}}Intermediate meter: Reset1 Bit1.3 enableCW
27Channel {{ChNo}}: {{0}}Main meter: Electrical active energy (24 h)4 Bytes13.13 active energy (kWh)CRWT
27Channel {{ChNo}}: {{0}}Main meter: Electrical active energy (24 h)4 Bytes13.10 active energy (Wh)CRWT
28Channel {{ChNo}}: {{0}}Main meter: Costs in Cent - Output4 BytesCRT
28Channel {{ChNo}}: {{0}}Main meter: Costs in Cent - Output2 BytesCRT
28Channel {{ChNo}}: {{0}}Main meter: Costs in Euro - Output4 BytesCRT
28Channel {{ChNo}}: {{0}}Main meter: Costs in Euro - Output2 BytesCRT
29Channel {{ChNo}}: {{0}}Main meter: Meter reading "Day"4 Bytes13.13 active energy (kWh)CRWT
29Channel {{ChNo}}: {{0}}Main meter: Meter reading "Day"4 Bytes13.10 active energy (Wh)CRWT
30Channel {{ChNo}}: {{0}}Main meter: Meter reading "Night"4 Bytes13.13 active energy (kWh)CRWT
30Channel {{ChNo}}: {{0}}Main meter: Meter reading "Night"4 Bytes13.10 active energy (Wh)CRWT
31Channel {{ChNo}}: {{0}}Main meter: Reset1 Bit1.3 enableCW
32Channel {{ChNo}}: {{0}}Meter: Event A1 Bit1.10 start/stopCT
33Channel {{ChNo}}: {{0}}Meter: Event B1 Bit1.10 start/stopCT
34Channel {{ChNo}}: {{0}}Load failure1 Bit1.5 alarmCRT
34Channel {{ChNo}}: {{0}}Residual current1 Bit1.5 alarmCRT
34Channel {{ChNo}}: {{0}}Residual current / Load failure1 Bit1.5 alarmCRT
210Central functionSwitch1 Bit1.1 switchCW
211Central functionLock manual operation1 Bit1.3 enableCW
212Central functionIn operation1 Bit1.11 stateCRT
213Central functionDay/Night1 Bit1.2 booleanCWTU
214Central functionTime3 Bytes10.1 time of dayCWTU
215Total: Active powerTotal value4 Bytes14.56 power (W)CRT
215Total: Active powerTotal value2 Bytes9.24 power (kW)CRT
216Total currentCurrent value2 Bytes9.21 current (mA)CRT
216Total currentCurrent value4 Bytes14.19 electric current (A)CRT
216Total currentCurrent value2 Bytes7.12 current (mA)CRT
217Total: Extended power measurementApparent power4 Bytes14.56 power (W)CRT
217Total: Extended power measurementApparent power2 Bytes9.24 power (kW)CRT
217Total: Extended power measurementApparent power4 Bytes14.57 power factor (cos Φ)CRT
218Total: Active powerLoad exceedance1 Bit1.1 switchCRT
218Total: Active powerLoad exceedance1 Byte17.1 scene numberCRT
219Total: Active powerLoad undercut1 Bit1.1 switchCRT
219Total: Active powerLoad undercut1 Byte17.1 scene numberCRT
220Total currentCurrent exceedance1 Bit1.1 switchCRT
220Total currentCurrent exceedance1 Byte17.1 scene numberCRT
221Total currentCurrent undercut1 Bit1.1 switchCRT
221Total currentCurrent undercut1 Byte17.1 scene numberCRT
222Total: Intermediate meterElectrical active energy (24 h)4 Bytes13.10 active energy (Wh)CRT
222Total: Intermediate meterElectrical active energy (24 h)4 Bytes13.13 active energy (kWh)CRT
223Total: Intermediate meterCosts in Cent - Output4 BytesCRT
223Total: Intermediate meterCosts in Cent - Output2 BytesCRT
223Total: Intermediate meterCosts in Euro - Output4 BytesCRT
223Total: Intermediate meterCosts in Euro - Output2 BytesCRT
224Total: Intermediate meterMeter reading: "Day"4 Bytes13.10 active energy (Wh)CRT
224Total: Intermediate meterMeter reading: "Day"4 Bytes13.13 active energy (kWh)CRT
225Total: Intermediate meterMeter reading: "Night"4 Bytes13.10 active energy (Wh)CRT
225Total: Intermediate meterMeter reading: "Night"4 Bytes13.13 active energy (kWh)CRT
226Total: Intermediate meterReset1 Bit1.3 enableCW
227Total: Main meterElectrical active energy (24 h)4 Bytes13.13 active energy (kWh)CRT
227Total: Main meterElectrical active energy (24 h)4 Bytes13.10 active energy (Wh)CRT
228Total: Main meterCosts in Cent - Output4 BytesCRT
228Total: Main meterCosts in Cent - Output2 BytesCRT
228Total: Main meterCosts in Euro - Output4 BytesCRT
228Total: Main meterCosts in Euro - Output2 BytesCRT
229Total: Main meterMeter reading: "Day"4 Bytes13.13 active energy (kWh)CRT
229Total: Main meterMeter reading: "Day"4 Bytes13.10 active energy (Wh)CRT
230Total: Main meterMeter reading: "Night"4 Bytes13.13 active energy (kWh)CRT
230Total: Main meterMeter reading: "Night"4 Bytes13.10 active energy (Wh)CRT
231Total: Main meterReset1 Bit1.3 enableCW
232Total: MeterEvent A1 Bit1.10 start/stopCT
233Total: MeterEvent B1 Bit1.10 start/stopCT
234Electricity price: "Day"Electricity rate in Cent - Input4 BytesCW
234Electricity price: "Day"Electricity rate in Cent - Input2 BytesCW
234Electricity price: "Day"Electricity rate in Euro - Input4 BytesCW
234Electricity price: "Day"Electricity rate in Euro - Input2 BytesCW
235Electricity price: "Night"Electricity rate in Cent - Input4 BytesCW
235Electricity price: "Night"Electricity rate in Cent - Input2 BytesCW
235Electricity price: "Night"Electricity rate in Euro - Input4 BytesCW
235Electricity price: "Night"Electricity rate in Euro - Input2 BytesCW
236Actual electricity priceElectricity rate in Cent - Output4 BytesCRT
236Actual electricity priceElectricity rate in Cent - Output2 BytesCRT
236Actual electricity priceElectricity rate in Euro - Output4 BytesCRT
236Actual electricity priceElectricity rate in Euro - Output2 BytesCRT
237Central functionVoltage error1 Bit1.5 alarmCRT
238Total: Active powerExternal - Input4 Bytes14.56 power (W)CW
238Total: Active powerExternal - Input2 Bytes9.24 power (kW)CW
Parameters (209)
ParameterTypeDefault
Startup timeunsignedInt 2…2402
Channel AlistSwitch
Economy mode, switch off LEDs afterlistnot active
Send "In operation" cyclicallylistnot active
Manual operationlistactive
Channel BlistSwitch
Channel ClistSwitch
Channel DlistSwitch
Set energy meters to "0" after transmitting the application.listnot active
Total current measurementlistnot active
All energy meters in the channel are writable via objectlistnot active
Object selectionlist2 Byte value in mA (DPT 7.012)
Send value on change of ...listno change
Send cyclically every …list1 h
Monitoring of current exceedancelistnot active
Send output cyclicallylistnot active
Minimum changelistnot active
Send value if exceededlistvalue "1"
Send scene if exceededlist1
Send value on withdrawallistvalue "0"
Send scene on withdrawallist2
Value for exceedancefloat 1…7020
Value rangelist100 mA - 1000 mA
Value for exceedanceunsignedInt 100…10001000
Value range for withdrawallist100 mA - 1000 mA
Value for withdrawalunsignedInt 100…1000100
Value for withdrawalfloat 1…7010
Channel ElistSwitch
Channel FlistSwitch
Total: Active power measurementlistactive
Object selectionlist4 Byte floating value in W (DPT 14.056)
Send value on change of ...listnot active
Monitoring of load exceedancelistnot active
Value for exceedanceunsignedInt 0…27600100
Delay timetime0
Monitoring of load undercutlistnot active
Value for undercutunsignedInt 0…276005
Object selectionlistApparent power in VA (DPT 14.056)
Send cyclically every …listnot active
Calculate costs vialista fixed value (Day)
Electricity rate "Day"float 0…100.22
DPT for object "Actual Electricity Price"list4 Byte floating value [Cent]
Electricity rate "Night"float 0…100.18
"Day" <-> "Night" change is controlled vialist"Day/Night" object (Day = 1, Night = 0)
Time to switch from "Day" to "Night"unsignedInt 0…230
Time to switch from "Day" to "Night"unsignedInt 0…590
Time to switch from "Night" to "Day"unsignedInt 0…230
Time to switch from "Night" to "Day"unsignedInt 0…590
DPT for objects "Electricity price Day" and "Actual electricity price"list4 Byte floating value [Cent]
DPT for objects "Electricity price Day/Night" and "Actual electricity price"list4 Byte floating value [Cent]
DPT for costs at intermediate and main meterlist4 Byte floating value [Cent]
Meterlistnot active
Object selectionlistValue in Wh (DPT 13.010)
Send meter reading on changelistnot active
Send meter reading every ...unsignedInt 10…5000010
Send meter reading cyclically every …list1 h
Send meter reading every ...unsignedInt 1…25510
Send meter reading cyclically every ...list1 h
Send meter reading every ...unsignedInt 1…6553510
Send meter reading every ...unsignedInt 1…255100
Activate "Event A" withlistnot active
Final valueunsignedInt 1…4294967295200
Object "Event A" sendslistOFF
Intermediate meter: Send all valueslistnot active
Intermediate meter: Resetlistnot active
Main meter: Send all valueslistnot active
Main meter: Resetlistnot active
Intermediate meter: Send costslistnot active
Main meter: Send costslistnot active
HoursunsignedInt 0…230
MinutesunsignedInt 0…590
Daylistevery day
Activate "Event B" withlistnot active
Object "Event B" sendslistOFF
Switch off all channelslistnot active
Monitoring of current undercutlistnot active
Value for undercutunsignedInt 100…1000100
Value for undercutfloat 1…7010
Send value if undercutlistvalue "1"
Value for withdrawalunsignedInt 100…10001000
Value for withdrawalfloat 1…7020
Send scene if undercutlist1
Value for withdrawalunsignedInt 0…27600100
Type of delaylistDelay after activation
Value for withdrawalunsignedInt 0…276005
Description of channel/objectstext
Additional texttext
Separate "Day/Night" meterslistnot active
Cost meterlistnot active
Intermediate meterlistnot active
Object "Day/Night"listno request
Object "Time"listno request
Object selection (from HW R4.2)listValue in Wh (DPT 13.010)
Modelistnormally open
Switch-on delayunsignedInt 0…300000
Switch-off delayunsignedInt 0…300000
Central functionlistactive
Send statusliston change
Send status cyclically (0 = not active)unsignedInt 0…300000
Additional inverted statuslistnot active
Behaviour on lockinglistno change
Behaviour on unlockinglistno change
Priority / Forced guidancelistnot active
Fallback time for forced guidance ( 0 = not active)unsignedInt 0…6000
Behaviour after forced guidancelistno change
Fallback time for priority (0 = not active)unsignedInt 0…6000
Behavior after deactivation of prioritylistno change
Behaviour on bus power returnlistno change
Behaviour on bus power failurelistno change
Logiclistnot active
Sceneslistnot active
Threshold switchlistnot active
Operating hours meterlistnot active
Logical operationlistOR
Logic functionlistwith switch object and one logic object
Invert inputslistnot active
Invert outputlistnot active
Set objects to value after bus power returnlistnot active
Value for object "Switch"listnot active
Value for object "Logic 1"listnot active
Value for object "Logic 2"listnot active
Learn scenelistnot active
Scene Alistnot active
Scene numberlist1
Scene behaviourlistON
Scene Blistnot active
Scene numberlist2
Scene Clistnot active
Scene numberlist3
Scene Dlistnot active
Scene numberlist4
Scene Elistnot active
Scene numberlist5
Scene Flistnot active
Scene numberlist6
Scene Glistnot active
Scene numberlist7
Scene Hlistnot active
Scene numberlist8
Datapoint typelist1 Byte DPT 5.001 Percent (0…100 %)
Behaviour when undercutlistnot active
Lower thresholdlist0 %
Behaviour when exceededlistnot active
Upper thresholdlist90 %
Set valuelist50 %
Lower thresholdunsignedInt 0…2550
Upper thresholdunsignedInt 0…2550
Set valueunsignedInt 1…25510
Lower thresholdunsignedInt 0…655000
Upper thresholdunsignedInt 0…655000
Set valueunsignedInt 1…65500100
Lower thresholdfloat -100…20010
Upper thresholdfloat -100…20030
Set valuefloat -100…20020
Lower thresholdfloat 0…100000100
Upper thresholdfloat 0…10000060000
Set valuefloat 0…100000400
Type of meterlistOperating hours meter
Datapoint typelist4 Byte value in s (DPT 13.100)
Send operating hours every ... (0 = not active)unsignedInt 0…100000
Send operating hours cyclically every …listnot active
Send "Time until next service" every ... (0 = not active)unsignedInt 0…100000
Send service message at intervals of ...unsignedInt 0…600000
Add channel to overall evaluation (current, active power, energy meter and voltage error)listactive
Send value on change of ...list10 %
Value rangelist10 mA - 1000 mA
Value for exceedanceunsignedInt 10…100010
Error messagelistnot active
Thresholdlist20 mA
Current measurementlistactive
Value for exceedancefloat 1…201
Value range for withdrawallist10 mA - 1000 mA
Value for withdrawalunsignedInt 10…100010
Value for withdrawalfloat 1…201
Value for undercutunsignedInt 10…100010
Value for undercutfloat 1…201
Active power measurementlistactive
Value for exceedanceunsignedInt 0…4600100
Value for undercutunsignedInt 1…46005
Extended power measurementlistnot active
Voltage measurementlistactive
Monitoring of voltage exceedancelistnot active
Value for exceedanceunsignedInt 180…300260
Monitoring of voltage undercutlistnot active
Value for undercutunsignedInt 180…300210
Energy and cost meterlistnot active
Send meter reading cyclically every ...listnot active
Send meter reading every ...unsignedInt 1…655351
Send meter reading cyclically every ...list5 min
Switch off channellistnot active
Value for withdrawalunsignedInt 180…300240
Value for withdrawalunsignedInt 180…300230
Value for withdrawalunsignedInt 0…4600100
Object selection (from HW R4.2)listValue in kWh (DPT 13.013)
Additional switch objectlistnot active
Staircase light timerunsignedInt 1…300001
Prewarninglistnot active
Prewarning durationunsignedInt 0…300001
Prewarning timeunsignedInt 0…300000
Manual switch-offlistactive
Extend staircase light timerlistrestart time
Factor for object "Staircase light with time"list1 s
Behaviour on unlockinglistOFF
Behaviour after forced guidancelistOFF
Behavior after deactivation of prioritylistOFF
Behaviour on bus power returnliststate before bus power failure
Pulse timelist500 ms
Repeat pulse oncelistnot active
Time until the next pulselist0,5 s

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Switch, Staircase light, Active power meter, 6-channel 3.1 latest$021122832026-11-25232 KBDownload

About this file

This is the official ETS product database for the MDT technologies GmbH AZI-0616.03 Switch Actuator 6-channel with active power meter (AZI-0616.03), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from MDT technologies GmbH

All MDT technologies GmbH products